Document Qgj0yOdmVq9g7kdZ3LxvZZMrR
K
a
124
CHAPTER 8
1962 Guide And Data Book
#10 .20 30 40 60 tO IOO
200 400 600
heat convened pea hour in thousands or btu
____
_____
lower eeaf* of chart U bated on 20-dog temperature difference between flow and nfon rhon. To Rod friction *6ea tempoi utur* drop It gttnr Act 20 dog, amdUptf At ocfwl boat conveyed by (20-l-oc(wf loop, drop) oad road At wrejpcoding friction.
Ft pot 100 ft MObtebot per ft
Ccmufiiot fl/DOO Ft) to M&ndtet/Ft
0.5-
1-2
3
#0 120 240 360
4 480
3 600
fig, 6.... Friction Loss duo to Row of Water in Type L Copper Tube
Table 2 .... iron and Copper Elbow Equivalents*- - * *
roii.0
Iron ftp* Copper Totes
Elbow, welded, POnleg....................... Open return bend........................
0.5
1.0 0.7
0.5
0.4 1.0 3.0 4.0
12.0 Table I for equivalent length at cot elbow.
4.0 0.7 17.0
should be calculated. The friction loffl at design flow for all individual sections of pipe and for all fittings in the longest piping circuit should then be summarised.
Table 2 shows the number of elbow equivalents for various fittings. These equivalents can be converted to equivalent feet of pipe by use of Table 3. Fig. 7 shows the elbpw equiva lents for determining friction los in tees. If the pipe site calculation indicates a required pump head different from that of a standard pump, pipe sizes in the system may be changed to establish a closer relationship between the two. The relationship between systems and pump heads is dis cussed in the section Circulating Pumps
If there are more circuits than one in a system, the fric tion loss for the longest circuit should be used to determine
Vtt.Fpt 1
6
Table 3.. . Equivalent length of Pipe for 90-Deg Elbows
Pipe Sixo
XH
IH IX 2 2X 3
1.2 1.7 2.2 3.0 3.5 4.5 5.4 6.7 l.v 3.3 3.9 5.1 6.0 7.5 3.6 4.2 5.4 6.4 8.0 4.4 5.6 6.7 8.3 2.9 3.9 4.5 5.9 7.0 8.7
1.7 2.3 3.0 4.0 4.7 6.0 7.2 8.9 4.1 4.8 6.2 7.4 9.1 4.2 4.9 6.3 7.5 9.3
1.8 4.3 5.0 6.4 7.7 9.5 2.5 5.1 6.6 7.8 9.7
3M
7.7 8.6 9.2 9.6 10.0
10.3 10.5 10.8 11.0 11.2
4
8.6 9.5 10.2 10.6 11.1
11.4 11.7 11.9 12.2 12.4
5
10.5 11.7 12.5 13.1 13.6
14.0 14.3 14.6 14.9 15.2
6
12.2 13.7 14.6 15.2 15.8
16.3 16.7 17.1 17.4 17.7
8 18.4 19.8
22.2
10 24.2 27.0
12 * 28.8 32.0
Hot Water Heating Systems
125
the pump bead requirement. Piping in the other circuits gjjoyjcJ be sized to obtain the same total friction loss.
Effects of Antifreeze Fluids. Antifreeze solutions are some times used in beating systems when the danger of freezing ^g+a. They should not be used in direct-fired boiler applica tion. Corrections must be made in flow rates, pipe size., and pump capacity relative to water when antifreeze solutions gje used. See Chapter 76, Snow Melting.
SaECTlON OF PIPING ARRANGEMENT
The type of distribution system selected for any particular building will depend primarily on the structural and archi tectural characteristics of the building, the need for separate control of different zones, the pressure head due to the height of the building, the space available for piping, and the rela tive cost of different arrangements of piping. Consequently, mains may be run in basement, separate floors, or in space above highest heating units.
There are four distinct arrangements of main piping: (1) the two-pipe reversed-retum system, (2) the one-pipe sys tem, (3) the series-loop system, and (4) the two-pipe directreturn system. The last is not recommended unless elaborate pipe firing technique and provision for adjustment are em
ployed-
Two-Pipe Reversed-Refum System--Description and Design
The iwo-pipe reversed-retum mam system. Fig. 8, has two mains, one supplying water to the heating units or to risers '
to heating units, and one collecting water returned from these units. The piping is arranged in such a manner that the sum of the equivalent length of supply and return piping to any unit is approximately equal to that of any other unit.
Compared with a one-pipe system, the two-pipe system
1. Have a smaller average pipe size. While two mains are re quired, the sizes of the mains vary as water passes from one main through the heating unit to the other. The maximum sixe of either main is no larger than the size of a one-pipe main
2. Be more flexible in its application because larger friction loss may be used in the beat-transfer unit circuits.
3. Require a minimum pumping head because the heating unit resistances are in parallel.
4. Permit adjustment of flow through individual units of ra diation over wider limits.
/S0M8H7 .
.-70M8H-
.-4.6 MBM-y
/ ho * yr
/wx /
/ Naa
is ---- L- L L---- r-l
----- ----- -----------1__
*v
-I
L4I 1
fiOIL.EC>*v
CWCtA.
\ PtM
'FVPLOW CHECH WkLVE.
X *7
TSX
Rg. 8.... A Two-Pipe Reversed-Retum System
Continuing the comparison, some disadvantages are*.'
1. Two mains may require more pipe fitting labor than a single main.
2. Some additional pipe may be required to achieve a re versed return.
3. A two-pipe system will be slightly more expensive for small systems.
4. The piping for two mains may be unsightly in occupied
mecaTACE of wtitn fujoins TMtoVftn eiKCLes mmcn
LThe chart It bated oo draighl loot, that it, brandtot A, B, end C
or* (he con* dm.
2. Hood (o in desired circurf it obtained by tolecting proper curve occord-
6>0 to Bhutrafinm, determining the flow at the drdod branch, and multipffing
the head lott for tbo tamo die elbow at (he flow rote in the drdod brooch
by the eqaivateat elbows indicated.
*
3. When the die of an outlet b reduced the eqwJrctent elbows shown
1 (he chart do not apply. The maximum loss for any arcuit for any Aow wfll
not exceed 2 elbow equivalent* at the mastmuet flow Igpai) occurring in any
breach of the tee.
4. The top corve of (he chart h the average of 4 curves, om for oodt of
*e toe draritt Shatrated.
Fig. 7....Elbow Equivalents of Tees at
Various Row Conditions*-u
Important considerations in the design of a two-pipe
reversed-return distribution system are:
1. The head which the pump must generate is equivalent to the friction drop through the circuit having the-highest resist ance. At Hew'gn flow, the resistance through the distribution system to any one hearing unit should be the same as that through any other unit. Where the length of pipe required to obtain distribution to a particular section must be shorter than to other sections, it is desirable to design that section with a higher friction loss.'
2. A reversed return, as indicated in the section Adjustment of Flow' and Capacity, mill reduce the need for adjustments neces sary to obtain equal total head through each beating unit cir cuit.
3. Fan-type air-heating units with extended-surface coils can be used with a higher water temperature drop than that recom mended for direct radiatiOQ. It is necessary, to avoid'a difference in air temperature across the face of the coil in such units. One method oi minimizing this difference is to install a minimum of two serpentine coils in each unit, one in front'of the other. Coil .
I________J