CHAPTER 18
1960 Guide
Table 14.... Determination of Free Areo and Total Pressure Loss of Register for No Deflection of Air** Register Free Air tn Squore inches (Upper vohM in eod> group)
Prtwirt Loss m Indies of Water Column (Lower value M eoch group!
* *
CFM
Distance from Register to Opposite Woti 19-21 22-24 25-27 28--30 31-34 35-39 40-49 50-59 60-59
190`-209
62 002
47 0.03
37 0.04
t 30 24 18 0.06 0.09 0.15
210t-229
76 58
45 36 29 22
0.02 0.02 0.04 0.05 0.08 0.12
230*-249
69 53 43 34 26 0.02 0.03 0.04 0.07 0.11
250l-269
81 63 50 40 31 21 0.02 0.03 0.04 0.06 0.09 0.18
270^299
93 73 59 47 36 24 0.02 0.02 0.03 0.05 0.08 0.16
300<-339
95 77 61 46 32 0.02 0.03 0.04 0.06 0.12
340t-379
120 97 77 59 40 0.02 0.02 0.03 0.05 0.10
380M19.
119 95 73 50 0.02 0.03 0.04 0.08
420M59
149 114 88 60 0.02 0.03 0.04 0.07
CFM
Distance from Register to Opposite Watt 35-39 40-49 50-59 60-69 70-79 80-69
660-699
210 0.02
A* ' 143 95 69 0.03 0.07 0.12
49 0.22
700-739
236 160 107 77 54 0.02 0.03 0.06 0.11 0.21
740-779
262 179 119 86 61 0.02 0:03 0.06 0.10 0.18
780-819
291 198 132 95 67 0.02 0.03 0.05 0.09 0.17
20-859
320 218 145 105 74 0.02 0.03 0-05 0.08 0.15
860-899
352 240 160 115 81 0.02 0.02 0.04 0.08 0.14
900-939
385 282 175 126 89 0.01 0.02 0.01 0.07 0.13
940-979
419 285 190 137
97
0.01 0.02 004 0.07 0.12
980-1019 455 309 206 148 105 0.01 0.02 0.04 0.06 0.11
460M99 500<-539 540I-679 sso'-eio
171 136 105 71 0.02 0.02 0.03 0.06
1920-1059
260 123 ' 84 0.02 0.03 0.05
1060-1099
186 143 97 65 47 0.02 0.02 0.05 0.09 0.17
1100-1139
213 164 111 74 54 .1140-1179 0.02 0.02 0.04 0.08 0.15
493 335 223 161 113 6.01 0.02 0.03 0.06 0.11
530 361 241 173 123 0:01 0.02 0.03 006 0.10
571 388 258 186 132 93 0.01 0.02 0.03 0.05 0.09 0.17
416 277 199 141 100 0-02 0.03 0.05 0.08 0.16
620*-659.
180 127 85 61 0.02 0.04 0.07 0.14
tl B
1180-1219 1220-1259
446 297 214 151 107 0.02 0.03 0.04 0.08 0.15
476 317 228 161 116 0.02 0.03 0.04 007 0.14
j! based on distance from register , to opposite well is unsatisfactory oo aeeooat etftise w poiun lo**> it is permissible to shift oao or more spaces left or right in the tables to obtain a more suitable register. II requirements fall io blank space, select twp registers in ol or* and divide CFM capacity between tbe two registers.
i T<*l
(atie nius velocity) loss is beeed on FLAT FACE ADJUSTABLE! BAB
TYPE and docs NOT include stackbead.
* Values on tbe right of line A and A' should not be osed m applications such as churches.
f Values on right of line B and B* should not be used in applications such as residential work, motion pfetore theaters, court rooms, and schools.
* For floor and baseboard registers wbere^valocity of approximately SCO PPM is used, the
1260-1299 1300-1339 1340-1379' 1380-1419 1420-1459
507 338 243 172 122 0.01 0.02 0.04 0-07 0.13
539 359 258 183 130 0.01 0.02 0.04 0-07 0.12
382 274 195 138 0.02 0.04 0.07 0.12
403 290 206 146 0.02 0.03 0.06 0.12
308 218 155 0.03- 0.06 0.10
1 Foe any volume under 190 CFM use Table 13.
1460-1500
324 230 163 0.03 0.06 0.10
A' B'
\
Worm Air Heating Systems
267
Table 15.... Suggested Bonnet Pressure ldm of Water
rote/ CFM Through
Any One Ouef
Suggested Boswat Pressure
in. Water
Total CFM Through Any One Duct
Suggested Bonnet Pressure
In. Water
800-1000 1000-1200 1200-1800 1800-24002400 to 3500
0.10 0.10 0.10 0.13 0.14
3500 to 5000 5000 to 7500 7500 to 10,000 10,000 to 12,000 12,000 to 14,000
0.15 0.25 0.375 0.500 0.750
the ducts. Hence, ducts need not be insulated except as fol
lows:
1. Supply duets:
A. Located in enclosed, unAeoied spaces--1 in. of insula tion.
B. Located in spaces exposed to outdoor temperature-- 2 in. of insulation.
2. Return ducts--1 in. of insulation when not located in heated space.
The procedure for larger systems may also be used to design perimeter systems in which the trunk duct is em bedded in the concrete slab floor, usually just inside the foundation wall.11 In sucb systems the branch ducts are usually very short and consist only of the take-off fitting, the diffuser boot or stackhead, and a short length of riser. The trunk is installed in the same manner as the loop duct in a smaller installation, and is often insulated to-reduce heat loss and prevent overheated floors above the duct. Perimeter in sulation must be used between the foundation wall and duct.
AUTOMATIC CONTROLS
Air stratification, high bonnet temperatures, excessive flue gas temperatures, and heat overrun or lag in a properly de signed system, can be .largely eliminated through proper care in the planning and installation of the control system.1* Best results are obtained when the fan is operated as con tinuously as possible, coupled with frequent, short cycles of burner operation. Controls usually employed are:
1. A room thermostat located in the occupied space at a point where there is good air circulation and where the tempera ture is representative of the area being controlled. It .is the operating control which initiates the starting and stopping of the burner. It is frequently of the timed, two-position type. Refer to Chapter 43 for more information on types of room thermostats.
2. A fan thermostat located in the bonnet of the furnace to start the fan at a bonnet temperature 10 to 15 deg above room temperature and stop the fan at about 15 deg below the cut-in point. The lower settings are used for high side-wall register in stallations and the higher settings for baseboard register installa tions. For most satisfactory performance these settings should be as low as is feasible without resulting in drafts,
3. A high limit control, also in the bonnet of the furnace, to stop the burner independently of the room thermostat if the air temperature exceeds 200 F. The fan thermostat and highlimit control are sometimes combined into a single unit.
4. A humidistat to regulate the moisture supplied to the rooms on systems which are equipped with humidifying means. This may be of the room type, usually located adjacent to the room thermostat, or it may be of the insertion type located in the main return air duct.
5. Primary and limit controls for the various types of gas burners, oil burners and coal burners (stokers) should be pro vided as required, and are discussed in Chapter 34.
ADJUSTMENT OF SYSTEM
More even room temperatures will result if the controls are adjusted to produce long period fan operation. This is accomplished in automatically-fired forced warm air heat ing systems when the control arrangement is of the type where the room thermostat controls the fire, and the blower control (fan switch) controls the blower operation. This procedure as outlined in detail in Manual 6 of the National Warm Air Heating and Air Conditioning Association, is as follows:1
1. Adjust the fuel input in proper relation to the heat loss of the structure.
2. Determine the temperature rise through the furnace. 3. Adjust the air volume to produce a temperature rise through the furnace of about 90 deg. 4. If adjustable, set the fan switch differential to a minimum of about 15 deg. 5. Adjust the fan switch cut-out point as low as practicable. 6. Balance the system by adjusting dampers to produce even temperature distribution between rooms. 7. Set the room thermostat at the desired room temperature.
Close control of room temperature is facilitated by the use of a room thermostat having'a narrow operating differential. The heat anticipating thermostat is such a device.
WARM AIR CEIUNG PANEL SYSTEMS
Warm air ceiling panel heating systems utilize a false ceil ing suspended 39* in. from the ceiling joists which have previ ously been covered on the bottom with sheets of plaster board. Special hangers are used to suspend the false ceiling or heating panel from the joists. Steel supporting rods are installed through these hangers and metal lath is attached to the rods. The lath is then plastered to a thickness of V* in., making a completely sealed air space above the ceiling. Warm air is delivered to this sealed space through a stand ard warm air duct, installed in the usual maimer. The air is then circulated over the entire idling being guided by sheet-metal baffles. After the air has passed over the ceiling, it is returned to the furnace through a return air duct for reheating. The system is closed, and no air is introduced into tile heated space from the panel. (See also Chapter 30, Panel Heating.)
Because a warm air ceiling panel system involves a differ ent type of ceiling construction, its installation is practically limited to new construction. Only automatically-fired and thermostatically-controlled furnace-blower units may be used with this system. Hie standard automatic heating con trols consisting of a room thermostat, temperature limit con trol, blower control (fan switch), and primary control are all that are required. While warm air editing panel heating has particular advantages in one-story utility room houses, it can be just as effectively installed in one- and two-story ^ bouses with basements.
Complete design and installation procedure is given in Manual 7-A of the National Warm Air Heating and Air Conditioning Association.1*
SUMMER OPERATION
During hot summer periods a slight cooling effect may sometimes be obtained by the circulation of basement air through the system. This beneficial effect is due to both the increased air movement in the occupied spaces and the small reduction in dry-bulb temperature brought about by