Document QgbvLpwxOVLKeLYRYOQd6KMr5
330
JOHNS-MANVILLE
22 East 40th Street, New York 16, N.Y.
Offices in All Large Cities Here and Abroad
Insulation
J-M MICRO-AIRE PREFORMED AIR DUCT
Product Data: Prefabricated, lightweight, cylindrical fiber glass duct for heating and cooling systems. Combines duct, thermal and acoustical insulation, and vapor barrier in one structurally strong product Resilient fiber glass resists impact damage duriog and after installation. Made of incombustible materials. Won't rot or mildew.
Nominal density is 335 pcf. Smooth inside surface reduces air friction and resists fiber erosion. Designed for velocities to 2000 fpm. Exterior vapor barrier is flame-retardant.
Thermal Performance: K at 75F mean--.23.
Installation: Connections easily made by integral "slip joints" (with or without standard metal fittings) and pres sure-sensitive tape.
Sixes: All sections 6 ft. long. Wall thickness 15/16 in. Made in all commonly used sizes from 2" to 18" I.D.
J-M MICRO-BAR FIBER GLASS DUCT LINER
Product Data: Resilient, blanket-type insulation featuring dual-density construction. Light density insulation for greater sound absorption and thermal resistance, covered with tough, heavy-density surface insulation to check air erosion and with stand shop handling. Made of strong, inorganic glass fibers bonded by thermosetting resin. Surface is treated and coated with flame-retardant, black-pigmented plastic.
Noise Reduction Coefficient: y2 in. thick--.60; 1 in. thick --30. No. 6 mounting used.
Underwriters' Laboratories Fire Hazard Rating: Flame spread 15, fuel contributed 25, smoke developed 5. This per mits design of system which reduces combustibles to a mini mum when installed with mechanical fasteners only.
Thermal Conductance: At 75F mean, % in. thick--.45; 1 in. thick--33.
Packaging: Thicknesses--1" 1%", 2". Widths--24" 36", 46V4", 48". Roll lengths--50' to 200' depending on thick ness.
Insulation
JOHNS-MANVILLE
22 East 40th Street, New York 16, N.Y.
Offices in All Large Cities Here and Abroad
331
MICROUTE
Product Data: Low density, resilient, blanket-type insula tion made of long, strong, extremely fine, flame blown glass fibers, bonded with a thermosetting resin.
Thermal Performance: k at 75F mean--6/10 pcf, 38; % pcf, 37; 1 pcf, 35; 1% pcf, 34; 2 pcf, 33; 2% pcf, 325; 3 pcf, 32.
Packaging: Densities--%i>, %, 1, IV2. 2, 2%, 3 pcf. Thicknesses range from yy to 4" (in y2" increments) de pending on density. Widths--24", 36", 48", 72". Roll lengths - --50', 100' and 200' depending on density and thickness.
MICROTEX
Product Data: Blanket insulation formed of long, strong glass fibers and reinforced with glass textile yam.
Thermal Performance: k at 75F mean--54 pcf, 0.29; 1 pcf, 365; 1% pcf, 345; 2 pcf, 33; 2% pcf, 326; 3 pcf, .225.
Packaging: Densities--pcf, 54. L 1%. 2, 2% and 3. Thick nesses--y2", 1", m", 2", 3". Widths--24", 36", 48". Roll lengths---50' to 200' depending on density and thickness.
FOR SWEATING LINES-- NEW J-M AEROTUBE
Description: A flexible, foamed plastic, tubular pipe insula tion for temperatures from 32F to 200F. Forms its own vapor barrier. Recommended for heating, plumbing, air-condition ing service where condensation is problem.
J-M MICRO-LOK FIBER GLASS PIPE INSULATION
Description: Micro-Lok Pipe insulation is made from long, fine glass fibers molded to form one-piece, three-foot sections in all standard wall thicknesses, for use on all standard iron pipe and copper tubing sizes. Temperature limits are from 370F maximum to sub-zero. (Consult J-M for low tempera ture applications.) For hot and cold water supply lines, heat ing supply and return lines, dual temperature lines and chilled water, brine, refrigerant and process piping. Properties: Density--3.50 lb nominal. Moisture absorption --less than 03% by volume. Alkalinity (expressed as NaaO) less than 2%. Corrosivity (with steel, copper, aluminum)-- does not cause or accelerate. Thermal diflusivity--@ 150F mean temperature 0.032 sq ft/hr. Thermal Conductivity: Average values for use in heat loss calculations.
Application: Micro-Lok features an automatic "spring hinge" opening and closing action, as shown below. It opens easily over the entire length and springs shut to assure a snug closure that minimizes heat loss or gain. The fiber lay up permits easy and accurate cutting of the inside diameter to conform to fittings, etc.
Micro-Bar Duct Liner forms readily with the metal in the brake without damage- Edges won't crumble. Conforms readily to irregu lar surfaces.
J-M Micro-Aire duct sections have factory-formed "slip joints" for strong, snug connections. Tight sea] is completed with pressuresensitive tape.
J-M FIBER GLASS DUCT WRAPS
Facings: All J-M fiber glass duct wraps are available plain, or with factory-applied vapor barriers such as standard and lightweight reinforced paper, reinforced foil and paper, alum* inum foil, vinyl film. Where required, a 2-inch sealing tab is available on one edge, and on 2 edges of some widths.
Aerotube slides onto even the most complex bends--6 feet at a time--in just seconds. This bend took only 7 seconds to insulate!
Physical Properties: WVT, less than 0.1 Perms. Water absorption, 3.9% by volume (60 days immersion). Density, 7.5 lbs/cu ft (All figures average values obtained in accord ance with accepted test methods.)
Application: 6' lengths slide onto even the most complex bends of iron pipe or copper tubing. On connected pipe, Aerotube is slit longitudinally, snapped on the pipe and cemented into place. Also available in sheets for use on flat surfaces.
Jackets: Micro-Lok is available in canvas, weather resistant or a variety of vapor barrier jackets, including genera] pur pose, dual temperature and the new Flame-Bar. All factoryapplied with a minimum 1%" longitudinal lap.
Compliance With .Government Specs:
HH-1-552, Type 1, Class A and B. HH-1-562, Type 2, Class 1 and 2.