_______ CHAPTER 23
;1948 Guide
either high pressure, low pressure, vapor, or' vacuum conditions. Either , the up-flow or the down-flow arrangement of mains may be employed.
Two-Pipe High Pressure Systems
Two-pipe high pressure systems operate at pressures above 15 psi,
usually from 30 to 150 psi. Large industrial type buildings, which are
equipped with unit heaters or large built up fan units, usually use high
pressure steam systems.
-
Fig. 8 illustrates a typical high pressure system.. Because of the high pressures and the great differential between steam- and return mains, it is possible to locate returns above the heating units and lift the conden' sate to these returns.
The condensate can be flashed into steam in low pressure mains if any are available or passed through an economizer heater before beingydis-
FROM HIGH PRESSURE BOILER
GATE VALVEv. PI PE, COIL
1
./ . ,FLOAT TRAP
CHECK VALVE
_ : y>
O' *m-GATE VALVE
l----------------------------- ----------------(------------------------ --------- ,
UNIT i HEATER
ECK VALVE FLOAT TRAP
f^GATE VALVE
CHECK VALVE FLOAT TRAPS':
. .. AIR VENT ECONOMIZER
FLOAT TRAP
^__ ^_____ \ r*.
L
VALVE
\p-_T-jlj I
ORIP
, VENT-vi
__ j
.
J____CJ--1 //LJ
''FINNED RADIATOR
I. I
/ AFLOAT TRAP
--tcTboiler N
VALVE
. ;,
. : RECEIVER .
Fig. 8. Typical High Pressure Heating'System
charged to a vented receiver. It is of course:necessary to provide for the elimination of air from high pressure systems, the same as in low pressure systems. " '
Return traps used on high pressure systems are usually of the bucket, inverted bucket, float or impulse type.
Two-Pipe Low Pressure Systems
Low pressure systems operate at pressures of 0 to 15 psi. The piping ' arrangement of both up-feed and down-feed low pressure systems is iden tical with these of two-pipe vapor systems described in the following sec tion. The only difference between the two systems is in the type of air valve used. The air valves used in low pressure systems do not contain the check discs and hence the system cannot operate under vacuum condi tions. The low pressure systems are not as popular as the vapor systems, because they have the disadvantage.^ not holding heat when the rate of steam generation is diminishing. They also have the disadvantage of
corroding to. a greater' extent than vapor systems .due to the continued
presence of new air.in the system. -
.- 1'
. .Low pressure systems have, the advantage, however of returning con densate to the boiler readily and not retaining .it in the piping , as. may
be possible in vapor systems.
.... .-
Fig; 9 ill ustrates a typical low pressure.system with, condensate pump.-
Two-Pipe Vapor Systems
Two-pipe vapor systems operate at pressures varying from .30. in: vacuum to 15 psi without the use of a vacuum pump. A typical two-
trap.
____
Air eliminating and pressure equalizing devtce.-See note below*. __
Boiler water line
Tf-sn_
^ .End of steam, main
,rapmay be dripped
J-- >5*^ through trap into
dry return
Wet retum-s.
Fig. 10.. Typical Up-Feed Two-Pipe System with Automatic Return Trap* *Propet piping connections are essentia] with special appliances for pressure,equalizing and air elimination.