American Society of Heating and Ventilating Engineers Guide, 1934
nected to one or more sections of the heater, depending upon the con densation rate of the engine. The recirculation duct connected with the opening in the suction duct should be extended to a point as near the floor as possible.
When ventilation is not a requirement or is considered relatively unim portant, as in shop and factory heating, and the number of persons vitiat ing the air is small compared with the cubical contents of the building, or the process does not generate obnoxious gas or vapors, the air may be recirculated,' sufficient outside air for ventilation being supplied by infiltra-
Fig. 1. Arrangement of a Central Fan Heating System. (Draw-Through)
Canvas Connection
Heater
Fig. 2. Arrangement for Heating Unit and By-pass. (Blow-Through)
tion. The amount of heat to be supplied the heating unit in this case is the same as would be required for a direct radiation installation.
When ventilation is a requirement to be met, an arrangement similar to that shown by Fig. 1 may be employed. Since the amount of air necessary for heating is generally in excess of the amount required for ventilation, considerable fuel economy may be effected by recirculating a portion of the air. In this case only sufficient outside air is drawn into the system to meet the ventilation requirement and the remainder of the air, required for heating, is recirculated. This may be readily effected by an arrange ment of dqcts and dampers on the suction side of the fan as previously mentioned. If the outside air introduced is to be washed or conditioned the washer or humidifier and tempering coil may be added between theinlet for the recirculated air and the fresh air intake.
292
Chapter 22--Central Fan Heating Systems
Blow-Through, Draw-Through
When the heating unit is located on the suction side of the fan, the system is known as draw-through. (See Fig. 1). When the heating unit, is located in the discharge from the fan the system is known as blowthrough. (See Fig. 2). The draw-through combination is used for factory and toilet room installations because a more compact arrangement of the apparatus usually is possible. In addition, air leakage will be inward. The blow-through combination is used principally in schools and public buildings, and for all booster coil arrangements where different tempera tures and independent temperature regulation are required for different heated spaces. In public building installations, the fan frequently blows the heated air into a plenum chamber from which the air ducts radiate to the various rooms of the building; this arrangement is sometimes called
the plenum system.
HEATING UNITS
The heating units for central fan systems using steam as the heating
medium may be classified as (1) tempering coils, (2) preheater coils, (3)
reheater coils, (4) booster coils, and (5) water heaters, either open or
closed. Tempering coils are used with ventilating and air conditioning
systems for raising the temperature of the outside cold air to above freez ing, or 32 F. They are not required for heating systems where all of the
air is recirculated, since the temperature of the recirculated air will be
above freezing. Preheater coils are used with air conditioning systems to
raise the temperature of the air from that leaving the tempering coils to
such a temperature that in passing through the water sprays of the washer
(without water heater) the air will become partially saturated (adia-
batically) having a moisture content corresponding to the required dew
point temperature. Preheater coils therefore supply heat as necessary to
control the dew-point temperature. The reheater coils are used to raise the
temperature of the air leaving the tempering coils (in the case of a heating
or ventilating system) or the air leaving the washer (in the case of an air
conditioning system) to that necessary to maintain the desired tempera
ture in the rooms or spaces to be heated or conditioned, except where
booster coils are used in which case the reheater coils raise the air tem
perature to approximately room temperature, or slightly higher. Booster
coils are installed in the duct branches to control the temperature of the
air entering the rooms.or spaces for which it is intended. Water heaters are
used on an air conditioning system to control the dew-point temperature.
They are used mainly for industrial work, seldom for comfort conditioning.
They are not used where preheater coils are employed. The open type
supplies steam directly to the spray water, while the closed type utilizes a
heat interchanger by which the steam ifnparts its heat to the spray water.
Where water heaters are required for comfort conditioning, the closed
type is used.
'
.-
The heating units for central fan systems in use at the present time con
sist either of pipe coils, finned tubes of steel, copper, brass or other metal,
cast-iron sections with extended surfaces, or the cellular type. Steam is
passed through these heating units and the air to be heated is passed over
their exterior surfaces.
293