HEATINC VENTILATING AIR CONDITIONING CUIDE 1944 OVERHEAD DISTRIBUTION In some industrial and institutional applications, the distribution piping may be installed, entirely or in part, above ground. This method of construction has the advantage of requiring no excavation and being easily maintained. INSIDE PIPING Figs. 2 and 3 show typical service connections used for low pressure steam service. , Fig. 2 shows installation of a reducing valve without a bypass, which is usually omitted in the case of smaller size valves. Fig. 3 illustrates the use of a reducing valve, with a bypass which is generally provided, for larger installations. This latter construction Pressure reducing valve CHAPTER 43. DISTRICT HEATINC consumption of heat when steam is again turned on in the morning, there is a large net saving which may be explained by the fact that the lower inside temperature maintained during the night obviously results in lower heat loss from the building, and less heat need therefore be supplied. Steam can be entirely shut off at night in most buildings even in very cold weather without endangering plumbing. It is necessary, however, to have an ample amount of heating surface so that the building can be quickly warmed in the morning. Where the hours of occupancy differ in various parts of the building, it is good practice to install separate supply pipes to the different parts. For example, in an office building with stores or restaurants on the first floor which are open in the evening, a separate main Fig. 4. Steam Supply Connection when Using Two Reducing Valves permits the operation of the line in case of failure in the reducing valve. In the smaller sizes, the reducing valve can be removed, a~filler installed, ' and the house valve used to throttle the flow of steam until'repairs are made. Fig. 4 shows a typical installation used for high pressure steam service1. The first reducing valve effects the initial pressure reduction. The second' reducing valve reduces the steam pressure to that required. Most district heating companies enforce certain regulations regarding the consumer's installation, partly to safeguard their own interests but principally to insure satisfactory and economical service to the consumer. There are certain fundamental principles that should be followed in. the design of a building heating system which is to be supplied from street mains. Although some of these apply to any building, they have been demonstrated to be especially important when steam is purchased. 1. Provision should be madefor conveniently shutting off the steam supply at night and at other times when heat is not needed.' It has been thoroughly demonstrated that a considerable amount of heat can be saved by shutting off steam at night. Although there is, in some cases, an increased `Code for Pressure Piping, B 31-1, 1942, American Standards Association, Paragraph 408, p. 115. 766 Fig, 5. Method of Installing a Water Heater and Economizer in a Gravity Heating System supplying the first floor will permit the steam to be shut off. from the remainder of the building in the late afternoon. The division of the building into zones each with a separately controlled heat supply is sometimes desirable, as it permits the heat to^be adjusted according to variations in sunshine and wind. 2. Residual heat in the condensate should be salvaged. This heat may be salvaged by means of a cooling coil, or as is more frequently done, by a water heating economizer (see Fig. 5) which preheats the hot water supply to the building. The condensation from the heating system, after leaving the trap, passes through the economizer. The supply to the hot water heater passes through the economizer, ab sorbing heat from the condensate. If the hot water system in the building is of the recirculating type, the recirculating connection should be tied in between the economizer ... and the water heater proper, not at the economizer inlet,.because the recirculated' hot water is itself at a high temperature. . Because of the lack of coincidence between the heating system load and the hot water demand, a greater amount of heat can be extracted from the condensate if storage capa- , city is provided for the preheated water. Frequently a type of economizer is used in which lie coils are submerged in a storage tank. S. Heat supply should be graduated'according to variations in the outside temperature. The maximum in economical operation and satisfactory heating can only be obtained by the use of some automatic temperature control system. 767