ZONOLITE MONO-KOTE*
DEFINITION
Mono-Koto Is the trade name for a fire protection material developed by Zonolite Division, W. R. Grace & Co. specifically for fast application, high fire resistance, and low cost. The material is spray applied by any one of several plastering machines. Mono-Kote is a cementitious, mill-mixed material re quiring only the addition of water at the job. It is applied directly to steel, concrete end other surfaces requiring fire protection.
TECHNICAL DATA
APPLIED DRY DENSITY: 1.5 lbs. per bd. ft. (15%).
BOND STRENGTH TO STEEL: More than 500 lb. per sq. ft. when set and dry.
BOND STRENGTH TO CONCRETE: More than 500 lb. per sq. ft when set and dry.
SOUND ATTENUATION: The combination of beams and ceiling when fireproofed with Mono-Kote gives sound absorption of .50 to .85 depending upon the ratio of beam area to flat area. This is of value to the designer in accomplishing attenuation objectives, especially when the fireproofed area is part of a plenum above a finished ceiling.
COMPRESSIVE STRENGTH: (Z in. cubes): More than 70 psi.
AIR EROSION RESISTANCE: Independent laboratory test subjected standard, machine-applied Mono-Kote surface to winds exceeding hurricane velocity . . . over 100 M.P.H. for 87 hours ... with no erosion. Copies of test description available.
FIRE RESISTANCE: Mono-Kote has been tested and rated according to ASTM E-119 by the Under writers' Laboratories, Inc. The material bears the U.L. label under a quality control inspection program. Fire resistance ratings and details for varied structural systems are available on request. To insure that architects and engineers have the benefit of the most recent ratings, it is suggested that they contact the local Zonolite office. Up to five hour ratings are available for steel beams. Ratings are also available on cellular, flat, or fluted, or blended steel floor systems and columns.
SPECIFICATION: (SHORT FORM) Fire protection material shall be Mono-Kote as manufactured by the Zonolite Division, W. R. Grace & Co. or its processing Distributors, applied by machine to the thickness and in the areas shown on the drawings. The method of mixing and application shall conform to the manufacturer's recommendation. See page 3 for Long Form Specification.
Federal Office Building, Jacksonville. Florida
Architects and Engineers: Reynolds. Smith and Hills, Jacksonville, Florida
General Contractor: Warrior Construction Co., Houston. Texas
Plastering Contractor: E. L. Thompson Plastering Co., Jacksonville. Florida
Zonolite Mono-Kote fireproofing
Niagara International Center and Skylon
Architects: Bregmsn end Hamann. Toronto, Ontario
Consulting Engineers: Farkas. Barron. Jablonsky, Toronto. Ont.
General Contractor: Pigott Construction Co.. Ltd.. Hamilton. Ont.
Fireproofing Applicator: George Hannaford & Son. Ltd. Hamilton, Ontario
Zonolite Mono-Kote fireproofing.
SPRAY-ON FIREPROOFING
SPECIFICATIONS
1. GENERAL CONDITIONS
All applicable revisions of the General Conditions and Spe cial Conditions shall form a part of this Specification Sec tion, except as may be modified herein.
2. SCORE
a) Work included -- The work required under this sec tion consists of furnishing all labor, materials and equipment necessary for sprayed fireproofing of structural steel members and metal decking, as in dicated in the drawings and as specified herein, and clean-up subsequent to that application.
b) Work not included --
1) Structural steel encased in concrete.
2) Trowelled plaster fireproofing is specified under the Plastering Section.
3) The cleaning of the surfaces to receive sprayed fireproofing.
4) In the event of sprayed fireproofing application in cold weather, the supply of temporary heat shall be by others, as defined in Section of the specifications.
3. EXAMINATION & COORDINATION
a) The contractor shall study the contract drawings and specifications with respect to the work, as shown and specified hereinafter, to assure its complete ness. Supplementary items necessary to complete the work, though not definitely shown or specified,
shall be brought to the architect's attention, and shall be included. The contractor's attention is di rected to the drawings'and specifications for both structural steel and metal decking, so that he may
properly determine the exact scope of the work required.
b) The contractor shall examine all surfaces to which the sprayed fireproofing is to be applied, and shall notify the General Contractor, in writing, if any con ditions exist which would be detrimental to the proper and expeditious installation of the work.
Starting of work, within an area, will be construed as acceptance of the conditions of that area.
c) All clips, hangers, supports, sleeves and other at tachments to the fireproofing bases, as covered under other sections of the specifications, are to be
placed by others prior to the application of the fire
proofing material, where these materials can be anticipated in adv=r-e.
d) Ducts, piping r
uit or other suspended equip
ment that cou: -
fere with the uniform applica
tion of the fireproofing material are to be positioned
after the application of the sprayed fireproofing.
e) The contractor shall cooperate in the coordination
and scheduling of the work of this section to avoid delays in the job progress.
4. SAMPLES
Samples of sprayed fireproofing shall be submitted for ap proval in accordance with the applicable provisions of the Special Conditions. These samples shall be representative of the material as applied in accordance with Acceptance & Performance Criteria as stated below.
5. ACCEPTANCE & PERFORMANCE CRITERIA
a) The sprayed fireproofing shall have been tested by Underwriters' Laboratories, Inc. in accordance with the procedures of A. S. T. M. El 19. The structural steel members shall be protected with adequate fire proofing thicknesses and densities to provide the fol lowing fire Resistance ratings:
Steel Columns.............................. ................-Hours Primary steel members (Girders)-Hours Secondary steel members (Beams)-Hours
(Note: Secondary steel members are those which support only the floor system, and are spaced at Vi the column spacing or less.)
b) The sprayed fireproofing beneath the deck assembly together with adequately proportioned concrete fill above the metal decking, shall provide a
Hour fire resistant deck assembly as substantiated by a fire test in accordance with the procedures of A. S. T. M. E119, and performed by Underwriters' Laboratories. Inc.
c) Minimum bond strength between the fireproofing material and the structural steel or galvanized deck ing shall beP. S. F.
d) The fireproofing material shall not be subject to losses from the finished application by sifting, flak ing or dusting. This performance shall be measured by the results of a test for erosion resistance when subjected to high velocity air flow across the sur face of dried samples. The samples thus tested must be representative of machine applied material simi lar to that which can be expected on the project. The air velocity shall be not less thanfeet per minute, and the duration of the test shall be at leasthours.
e) Documentation of the above performance shall be submitted with the bid. in order that all parties will fully understand the intention of application per formance at that time.
6. MATERIALS
a) The sprayed fireproofing shall be cementitious setting-type, and shall be Mono-Kote as manufac tured by Zonolite Division -- W. R. Grace & Co., or its processing distributors.
All manufactured materials shall be mill-mixed and shall be delivered in original/unopened packages bearing the name of the product, the manufacturer's name and the Underwriters' Laboratories, Inc. Label.
The materials shall be stored off the ground, under cover, and away from damp surfaces. Materials shall be kept dry until ready for use. Materials that have been exposed to water before actual use shall be discarded.
b) Water shall be clean, fresh and free from organic and mineral impurities which would be harmful to the sprayed fireproofing materials.
7. INSTALLATION
a) Application of sprayed fireproofing shall be in ac cordance with the printed instructions of the material manufacturer and the fire test report information.
b) Only experienced applicators, approved by the ma terials manufacturer and Architect shall be allowed to place the materials. Upon request a qualified manufacturer's representative can be present for initial application to guide and assist applicator's personnel.
c) All surfaces to which sprayed fireproofing will be applied shall be thoroughly cleaned of oil, grease, dirt, loose paint, mill scale or any other matter which would impair bond.
d) Temperatures and enclosure conditions shall be as specified by the materials manufacturer.
e) All patching and repairing of sprayed fireproofing, due to cutting by other trades, shall be performed under this section and paid for by the trade(s) that performed the cutting.
8. CLEAN UP
After completion of fireproofing work, equipment shall be removed and all wall and floor areas cleaned of deposits of sprayed fireproofing materials.
9. BID INFORMATION
Each bidder shall submit with his bid:
a) Full report(s) of Underwriters' Laboratories, Inc. fire tests including written material and detailed drawings of the tested assembly.
b) Materials manufacturer's printed instructions for methods and procedures of application.
c) Bond test data for unc.Jted, coated and galvanized steel applications.
d) Results of tests of mate :al performance when sub jected to high velocity ai low.
ZONOLITE DIVISION, W. R: GRACE & CO
ZONOLITE* MONO-KOTE'
(<
DESCRIRTION'FIRE-RESISTANCE RATINGS
(
E-119 by the .Underwriters' Laboratories, Inc. The material.,
beats the U.L. label under a quality control inspection pro
for fast. ipplicatloo; - Wgh'-fir* resistance,-and: tow cost. .The.. gram! Fire-resistance ratings and details for varied structural
.-material Is sprayapplied byany.one of .several postering me- . systems are available on request To insure that architects and
chines. MONO-KOTEis axementitious. mlll'^nixed material re-t - - engineers have the benefits of the most recent ratings. It Is
. , qulring'only.the^dditioriofwater at.;the.'Job.,i-4t:fsapplied' ;
(suggested that they contact the local Zonolite office. Five hour
.ratings are available for steel beams. Ratings are also available
;on cellular, flat or fluted, or blended steel floor systems and columns., (All ratings Underwriters' Laboratories, Inc.)
DESCRIPTION
2 Vi" sand-concrete fill. V." ZONOLITE MONO-KOTE following contour of under side of deck with an additional Vi" across
top of flute.
2Vi* sand-concrete fill.
ZONOLITE
MONO-KOTE following contour of under
side of deck with an additional Vi " across
top of flute.
RATING
SYSTEM
2Vi" sand-concrete fill. ZONOLITE MONOKOTE Vi" thick applied to underside of steel floor as shown.
2V4" sand-concrete fill. ZONOLITE MONOKOTE Vi" thick applied to underside of steel floor with Vi* on top and sides of flute.
Note: 1V4" deep steel floor section.
(C
2Vi" sand-gravel concrete. ZONOLITE MONO-KOTE %" thick applied to under side of steel deck as shown, with addi tional Vi" at top and sides of flutes, l'/i" under trench header ducts.
2V4" sand-concrete fill. ZONOLITE MONOKOTE applied directly to underside of steel floor with %" under flat plate, add Vi" at top and sides of flutes and 1" under filled flutes under 36" trench header duct.
Note: 3" deep steel floor section. Trench header duct not shown.
3 hrs. 2 hrs.
3 hrs. 2 hrs.
r
(
3Vi " sand-concrete fill. ZONOLITE MONOKOTE applied directly to underside of steel
floor Vi " below corrugations.
2Vi" sand-concrete fill. ZONOLITE MONOKOTE V4" thick applied directly to under side of steel floor as shown.
<c
2Vi" sand-concrete fill. ZONOLITE MONOKOTE Vi" below filled flutes to underside of steel floor as shown.
3 hrs. 2 hrs.
i . v , : v: v /
SPRAY-ON FIREPROOFING
tc
2 Vi" sand-gravel concrete slab. ZONOLITE MONO-KOTE %" thick applied di rectly under slab as shown.
2 hrs.
2 Vi" Jr- T" -- _l" T.-r-.-- -T'..--.r~-- --f-- -feSZa:: . ^A-A-rxA-x v v v v v v v Z3^
K5"
ZONOLITE MONO-KOTE applied direct to structural steel beams and girders.
Vi".............................. Vi".............................. Vi"
4 hrs.
3 hrs. 2 hrs.
ZONOLITE MONO-KOTE applied directly to structural steel columns.
l>/"............ 4 hrs. V."............ 3 hrs. Minimum column 14 WF 228.
2V,"........... V/%"...........
l`/j"........... All Columns.
(Additional ratings on other side)
4 hrs. 3 hrs.
2 hrs.
2Vi" sand-gravel concrete. ZONOLITE MONO-KOTE composite floor -- beam de sign applied 3/," on underside of blended, fluted and cellular lVi" steel floor. Vi" of MONO-KOTE on top and sides of flute.
Composite beam -- V," following contour. (Shear strap in composite system may be replaced by shear lugs.)
2 hrs. 4 hrs.
ZONOLITE DIVISION, W. R. GRACE & CO.
5
ZONOLITE VERMICULITE
DESCRIPTION
Zonolite Plaster Aggregate is a specially graded vermiculite produced under rigid quality controls in more than 45 Zonolite
plants in the United States and Canada.
When used with gypsum in plaster, it results in a lightweight, insulating, fire-resistant plaster for either hand or machine application.
ZONOLITE PLASTER AGGREGATE BASECOAT PROPORTIONS
Base
Gypsum Lath Metal Lath Masonry Monolithic Concrete* *
Ceilings Walls
MIXES
100 lbs. Gypsum
Cu. ft Zonolite
12
12
13
13 13
Thickness including Finish Coat* Vi * min.
min. %" min.
Mi ~ min. %** min.
'Greater thickness may be required for fire retardant ratings. See Vermiculite Institute "hire Resistance Ratings/*
If monolithic concrete ceiling or wall surfaces require more than or Vi*\ respectively, of plaster to produce desired lines or sur
faces. metal lath or wire lath shall be attached thereto. In extreme cases, metal furring may be required.
TECHNICAL DATA
Weight: Approximately IV2 lbs. per sq. ft. at V4 in. thickness.
Gradation: Conforms to ASTM C35. Listed and inspected under Re examination Service of Underwriters' Laboratories, Inc.
Fire Resistance: See partial list of fire resistance ratings below. Consult your local Zonolite office for the most recent rating.
K Factor 0.95 (Sand Plaster, 3.0).
Notes: (1) Zonolite Plaster Aggregate should be used with gypsum plaster that has been especially formulated for lightweight aggregates.
(2) If Zonolite plaster is applied directly to exterior masonry walls, wall design should insure impermeability to wind-driven rain, and an interior surface above the dew point.
FIRE RESISTANCE RATINGS
I3/." ZONOLITE PLASTER over the face of self-furring metal lath wrapped around column.
Same as above except 1 %" ZONOLITE PLASTER over face of self-furring metal lath.
V/2" ZONOLITE PLASTER over the face of metal lath. Lath spaced l1/," from column flanges. Space behind lath on flange faces filledt with plaster, as shown. Same as above except 1" ZONOLITE PLAS TER over face of metal lath.
COLUMNS
2" ZONOLITE-Portland cement PLASTER over paper-backed wire fabric wrapped around column with an additional wire fabric (no paper) over scratch coat.
Column protected with l'h" ZONOLITE PLASTER applied over two layers of V2" thick long length plain gypsum lath wrapped with one layer of hexagonal mesh poultry netting. Same protection as above except 1" ZONO LITE PLASTER applied over gypsum lath. Column protected with 1" ZONOLITE PLAS TER applied over one layer of %" thick per forated gypsum lath.
2'h" sand-concrete fill. 1" ZONOLITE PLAS TER on metal lath or 2'h" sand-concrete fill on formed steel floor. 3/" furring chan nels with V," ZONOLITE PLASTER on metal lath.
2'h" sand-concrete fill. V," ZONOLITE PLASTER on metal lath. 2" sand-concrete fill. y," ZONOLITE PLAS TER on metal lath.
4 hrs.
Paper-Backed Wire Fabric
4 hrs. 3'/2 hrs.
2 hrs.
Gypsum Lath
4 hrs.
3 hrs. 2`/2-hrs.
Steel Joists or Light Steel
Construction
/
>7
PLASTER AGGREGATE
SPECIFICATIONS
MATERIALS -- Gypsum plasters shall conform to ASTM C28. Zonolite ver miculite shall conform to ASTM C35. Metal shall be protected against rusting.
SURFACE PREPARATION All surfaoes to receive plaster shall be carefully inspected and in proper condition prior to plastering. Angles shall be straight and true.
THICKNESS Proper grounds shall provide for minimum thickness of plaster (see table below).
MIXING -- Zonolite vermiculite plaster may be mixed by hand or ma chine. When machine mixed, use following sequence: (1) Charge mixer with water.
(2) Add aggregate.
(3) Add plaster. (4) Mix to desired consistency, adding water as required.
a. Setting Time--Zonolite vermiculite plaster shall set in 2-4 hours.
b. Machine application: Use unfibered gypsum plaster, designated "for Machine Application" by the gypsum manufacturer.
APPLICATION OF BASE COATS --
Use two or three coat work depending on plaster base. For detailed directions on solid plaster partitions, hollow stud partitions and other bases, consult Manufacturer or refer to ASA or Vermiculite Institute Standard Specifications.
APPLICATION OF FINISH COATS-
Gypsum-sand float finish, Keene's Cement-time-sand-float fin ish, machine-applied gypsum vermiculite texture finish, or mill-mixed acoustical plasters (Zonolite Acoustical Plastic) shall be applied following ASA or Vermiculite Institute Stand ard Specifications. Gypsum-lime putty trowel finishes shall in clude approximately Vi cu. ft (50 lbs.) fine silica sand per 100 lbs. gauging piaster.
ZONOLITE FINISH COAT-
Finish Coats are available for application to acoustical plasters or may be applied directly to concrete as a texture coat. When applied to a thickness of X" over acoustical plasters, Zonolite Finish Coat will not adversely affect sound absorption. Zono lite Finish Coat is mill-mixed, requiring only the addition of water at the job. It is applied by any one of several pump type plaster machines or air-spray texture guns. It has a light reflectivity of 65%.
1" of ZONOLITE PLASTER over the face of metal lath. At least 2 Vi" air space between structural members and back of metal lath.
%" of ZONOLITE PLASTER plus Vi" of ZONOLITE ACOUSTICAL PLASTIC over the face of metal lath. At least 2Vi" air space between structural members and back of metal lath.
%" of ZONOLITE PLASTER over the face of metal lath. Ceiling openings for two duct outlets as shown and for two electrical out let boxes; aggregate area of openings not to exceed 100 sq. in. in each 100 sq. ft. of ceiling area. Duct openings protected by dampers.
1* of ZONOLITE PLASTER on metal lath furred or in contact with the lowr- "ange of supporting primary beams
3A` of ZONOLITE PLASTER cn
lath
furred or in contact with the lower flange
of supporting primary beams.
ZONOLITE PLASTER on metal lath -- sup
ported on wire or channel hangers. %" plaster.
1" of ZONOLITE PLASTER applied to each face of Vi" thick long length plain gypsum lath. No studs. Overall thickness of par tition 2Vi".
V." of ZONOLITE PLASTER applied to each face of Vi" thick long length plain gypsum lath. No studs. Overall thickness of par tition 2".
ZONOLITE PLASTER applied on metal lath fastened to incombustible studs spaced 16" on centers. Overall thickness of par tition 2Vi".
ZONOLITE PLASTER applied on metal lath fastened to incombustible studs spaced 16" on centers. Overall thickness of partition 2".
4 hrs.
BEAMS, GIRDERS & TRUSSES
4 hrs.
\ irrVm
3 hrs. 4 hrs. 3 hrs.
T
" jCONTACT
PRIMARY BEAMS-
Protected with Furred or Contact Ceilings
FURREO
4 hrs.
2 hrs.
SOLID PLASTER PARTITIONS
1 hr.
Individually Protected
1?-T
Gypsum Lath
2 hrs. 1 hr.
ZONOLITE DIVISION, W. R. GRACE & CO.
OTHER ZONOLITE PRODUCTS
ZONOLITE Vermiculite CONCRETE AGGREGATE
For insulating concrete roof deck applications over vented galvanized steel, formboard, structural and pre cast concrete. For current catalog, send for CA-140.
ZONOLITE Vermiculite
Water-repellent insulation for cores and cavities in masonry construction. Doubles thermal insula
MASONRY FILL INSULATION tion in most systems. Full details in catalog MF-83.
ZONOLITE DYFOAM
In roll or board form, for perimeter insulation, cold storage, flotation, innumerable uses. Send for
EXPANDED POLYSTYRENE catalog DF-26.
ZONOLITE DYFOAM NOISE CONTROL BOARD
ZONOLITE Vermiculite ATTIC INSULATION
ZONOLITE Glass Fiber INSULATION
Specially-laminated polystyrene for sound-deadening in wall and ceiling systems. Full details and test data in SC-101.
Free-flowing, permanent, mineral granules for insulation of horizontal spaces. Can be applied di rectly over existing inadequate insulation. Ask for brochure HI-203.
Full range of widths, thicknesses for any R-factor requirement. Foil-faced, kraft-faced or plain. De tails in brochure HI-203.
ZONOLITE SALES OFFICES
ZONOLITE DIVISION W. ft GRACE A CO.
ALABAMA, Birmingham 35205 2800 Fifth Ave.. South
ARIZONA. Phoenix 85031 4220 West Glenrosa
ARKANSAS, North Little Rock
72114 P. O. Box 294
CALIFORNIA Los Angeles 90041 758 Colorado Bivd
Los Angeles 90041 P. O. Box 41077
9 Modesto 95351 416 Hosmer Street P. O. Box 862
Newark 94560 6651 Smith Avenue P. O. Box 217
COLORADO, Denver 111S. Navaio Street
FLORIDA
Boca Raton 33432 P. 0. Box 67
rBoca Raton 15S5 N W. First Avenue
`Hialeah
--
1050 S.E. 5th Street
----- ""
Jacksonville 32202 1530 East Adams St.
Tampa. 35th St. A 3rd Ave. P. O. Box 5047, Ybor Station
GEORGIA, Atlanta 30306
1167 Zonolite Place. N.E P. O. Box 8127. Station F
`GEORGIA, Atlanta 520 Permalume Place N.W.
ILLINOIS. Chicago 60643 12300 South Ashland Avenue
KANSAS, Wichita 67214 1463 Barwise Avenue
KENTUCKY, Wilder. Newport 41070 112 North Street
LOUISIANA, New Orleans 70121 4729 River Road P. O. Box 10262
MARYLAND. Beltsville. 20705 P. O. Box 347
MASSACHUSETTS. Easthampton 01027
P. O. Box 112
MICHIGAN, Dearborn 48120 14300 Henn Avenue
MINNESOTA, Minneapolis 55422 4725 Olson Hwy.
MISSOURI, Kansas City 64105 515 Madison Street
MISSOURI, St. Louis 63110 1705 Sulphur Avenue
MONTANA. Libby 59923 P. O. Box 607
NEBRASKA, Omaha 36th and 1 Street
NEW JERSEY, Trenton 06607 336 Whitehead Road P. O. Box 2124
NEW YORK, Weedsport 13166 P. O. Box 310
NORTH CAROLINA, High Point 27260
1701 Prospect Street. Extension P. O. Box 1308
OHIO, Cr and . .. treet
O.'tL
uland 97227
2303 N. > ding Avenue
PENNSYLVANIA, EMwood City 16117
12th and Factory Streets
PENNSYLVANIA, New Castle 202 East Cherry Street Box 1207
PUERTO RICO, Cupey Bajo. Kn. 0.5
Insular Highway 845
SOUTH CAROLINA, Travelers Rest 29690
P. O. Box 517
TEXAS, Houston 77008 611 West 22nd Street
WASHINGTON, Auburn 98002 P. O. Box A
WASHINGTON, Spokane. 99201 1318 N. Maple Street
WISCONSIN. Milwaukee 900 North 43rd St.
PROCESSING DISTRIBUTORS
HAWAII, Honolulu (17) Vermiculite Of Hawaii 842-A Mapunapuna Street
MONTANA. Great Falls 59401 Robinson Insulation Co. 1226 North River Drive P. O. Box 1419
NEW MEXICO, Albuquerque 87107 Southwest Vermiculite Co. 5119 Edith Boulevard. N.E. P. 0. Box 6302
NORTH OAKOTA, Minot 58702 Robinson Insulation Co. P. O. Box 1782
OKLAHOMA, Oklahoma City 73111 Texas Vermiculite Co. 201 North Eastern P. O. Box 11402
TENNESSEE. Nashville 37204 Tennessee Zonolrte Co. 4061 Powell Avenue
TEXAS
Dallas 75222 Texas Vermiculite Co. 2651 Manila Road P. O. Box 6306
Houston 77008 Vermiculite Products. Inc. P. O. Box 7327
Lubbock Southwest Vermiculite Co Route 3. Box 191B
San Antonio Texas Vermiculite Co P. O. Box 9114
UTAH, Sait Lake City 84110 Vermiculite-lntermountam. Inc 333 W. First South P. O. Box 2398
CANADA
ALBERTA Calgary Grant Industries A division of Eddy Match
Company. Limited 4030 8th St.. S. E Box 69. Postal Station "A"
Polystyrene Perlite
Edmonton Grant Industries A Division of Eddy Match
Company. Limited 8602-106A Avenue P. O. Box 174
Lethbridge Grant Industries A Division of Eddy Match
Company, Limited 3003 Leaside Avenue P. O. Box 1104
BRITISH COLUMBIA Vancouver(4) Grant Industries A Division of Eddy Match
Company. Limited 476 Industrial Avenue
Vancouver(5) Grant Industries A Division of Eddy Match
Company. Limited 1075 Melville Street
MANITOBA Winnipeg (10) Grant Industries A Division of Eddy Match
Company. Limited 760 Wall Street
ONTARIO St. Thomas F. Hyde A Company. Ltd 94 Woodward Avenue
Toronto (18) F. Hyde A Company. Ltd 3349A Bloor Street. West
Toronto. (9) F. Hyde A Company. Ltd. 3540 Dundas Street. West
P.Q.. Montreal (9) F. Hyde & Company, Ltd 2315 Cote de Liesse Road
SASK., Regina Grant Industries A Division of Eddy Match
Company, Limited 1035 Angus Street P. O. Box 1213
SASK., Saskatoon Grant Industries A Division of Eddy Match
Company, Limited 733-- 1st Ave. North P. O. Box 1040
/ / \
l
GRACE
PA-99 Copyright 1966. Zonolite. Mono Kote. and Dyfoam are registered trade names of Zonolite Division. W. R. Grace A Co. Since methods end conditions of application and use are beyond our control, the Zonolite Division. W. R. Grace A Co., will not be responsible for failure of its products when not used according to directions and specifications.
Q
A.IA No. 21-A-5
`iLlA.No. 21-A-5&
VERMICUL1TE PLASTER AGGREGATE AND
sf RAY-ON FIREPROOFING
y * r- >
ZONOLITE DIVISION, W. R. GRACE & CO.
- ' A * ..IT *',
OL1TE* MONO-KOTE*
EFINITION
Mono-Kota It the trad* hmn lor a Hr* protaction material developed by Zonolita Diviaion, W. R. Grata 4 Co. specifically for fast application, higti fire resistance, and low cost The matsrial is spray applied by any one of several plastering machines. Mono-Kota is a cementitious, mill-mixed material re quiring only the addition of water at the job. It Is applied directly to steal, concrete and other surfaces requiring fire protection.
TECHNICAL DATA
APPLIED DRY DENSITY: 1.5 lbs. par bd. ft (* 15%).
^
BONO STRENGTH TO STEEL: More than 500 lb. per sq. ft when set and dry.
BONO STRENGTH TO CONCRETE: More than 500 lb. per sq. ft when set and dry.
SOUND ATTENUATION:
The combination of beams and ceiling when fireproofed with Mono-Kote
gives sound absorption of .50 to .85 depending upon the ratio of beam area
to flat area. This is of value to the designer in accomplishing attenuation
objectives, especially when the fireproofed area Is part of a planum above a
finished ceiling.
>
COMPRESSIVE STRENGTH: * (2 In. cubes): More than 70 psi.
AIR EROSION RESISTANCE:
Independent laboratory test subjected standard, maehine-applled Mono-Kote surface to winds exceeding hurricane velocity . . . over 100 M.P.H. for 87 hours ... with no erosion. Copies of test description available.
FIRE RESISTANCE:
Mono-Kote has been tested and rated according to ASTM E-119 by the Under writers' Laboratories, Inc. The material bears the ULL. label under a quality control inspection program. Fire resistance ratings and details for varied structural systems are available on request To Insure that architects and engineers have the benefit of the most recent ratings, it Is suggested that they contact the local Zonolita office. Up to five hour ratings are available for steel beams. Ratings are also available on cellular, flat or fluted, or blended steel floor systems and columns.
%PEftnCATMN:lSHORr:FORMn
^Flre protection material shail be Morio-Kote as manufactured by the Zonolita^ .Division. W. R. Grace A Co. or Its processing Distributors, applied by machine*) to the thickness and In the areas shown on the drawings. The method'dr .mixing and application shall conform to the manufacturer's recommendatiorin Sea page 3 tor tong Form Specification. ^
PWml Office Building. Jacksonville. Ftoftoi Architect* and Engineers: Reynold*, Smith and HR)*,
Jacksonville, Florida Qenerel Contractor: Warrior Conatructton Ce,,
Houiton. Texas Plastering Contractor E. L. Thompaon Flattering Ce,,
Jackaonvllle, Florida ZonoIHe Mono-Kote fireproofing
Niagara International Center end Skylon Architect*: Bragman and Hamann. Toronto. Ontario Canavitlng Engineer*: Farkta. Barren. JaWonaky, -
Terr tie. Ont General Contractor: FIgot: Construction Co.. Ud..
Hamilton. Ont. Fireproofing Applicator: Gtorp* Htnnalord A Sen. Lid
Hamilton. Ontario Zonolita Mono-Kola fireproofing.
SPRAY-ON FIREPROOFING
SJgCl HGA'WONS^
1. GENERAL CONUTIONS All applicable revisions of the General Conditions and Spe cial Conditions Shall form a part of this Specification Sec tion, except as may be modified herein.
2. SCOPE a) Work included -- The work required under this sec tion consists of furnishing all labor, materials and equipment necessary for sprayed fireproofing of structural steel members and metal decking, as In dicated In the drawings and as specified herein, and ciean-up subsequent to that application.
b) Work not Included -- 1) Structural steel encased. In concrete.
2) Trowelled plaster fireproofing Is specified under the Plastering Section.
3) The cleaning of the surfaces to receive sprayed fireproofing.
4) In the event of sprayed fireproofing application in cold weather, the supply of temporary heat shall be by others, as defined in Section of the specifications.
3. EXAMINATION & COORDINATION
a) The contractor shall study the contract drawings and specifications with respect to the work, as shown and specified hereinafter, to assure its complete ness. Supplementary items necessary to complete the work, though not definitely shown or specified, shall be brought to the architect's attention, and shall be included. The contractor's attention is di rected to the drawings and specifications for both structural steel and metal decking, so that he may properly determine the exact scope of the work required.
b) The contractor shall examine all surfaces to which the sprayed fireproofing is to be applied, and shall notify the General Contractor, In writing, if any con ditions exist which would be detrimental to the proper and expeditious Installation of the work. Starting of work, within an area, will be construed as acceptance of the conditions of that area.
c> All dips, hangers, supports, sleeves and other at tachments to the fireproofing bases, as covered under other sections of the specifications, are to be placed by others prior to the application of the fire proofing material, where these materials can be antidpated in advance.
d) Ducts, piping or conduit or other suspended equip ment that could Interfere with the uniform applica tion of the fireproofing material are to be positioned after the application of tha sprayed fireproofing. >
e) The contractor shall cooperate In the coordination and scheduling of the work of this section to avoid delays in tha fob prograss.
4. SAMPLES
Samples of sprayed fireproofing shall be submitted for ap proval in accordance with the applicable provisions of the Special Conditions. These samples shall be representative of the material as applied in accordance with Acceptance A Performance Criteria as stated below.
5. ACCEPTANCE A PERFORMANCE CRITERIA
a) The sprayed fireproofing shall have been tested by Underwriters' Laboratories, Inc. in accordance with the procedures of A. S. T. M. El 19. The structural steel members shall be protected with adequate fire proofing thicknesses and densities to provide the fol lowing fire resistance ratings: Steel Columns..............................................-Hours Primary steel members (Girders) -Hours Secondary steel members (Beams)..-Hours
(Note: Secondary steel members are those which support only the floor system, and are spaced at V4 tha column spacing or less.)
b) The sprayed fireproofing beneath the deck assembly together with adequately propori.taned concrete fill above the metal decking, shall provide a
Hour fire resistant deck assembly as substantiated
by a lira test In accordance with the procedures of
A. S. T. M. El 19. and performed by Underwriters'
Laboratories. Inc.
c) Minimum bond strength between the fireproofing material and the structural steel or galvanised deck
ing shall be --
P. S. F.
d) The fireproofing material shall not be subject to
losses from the finished application by sifting, flak
ing or dusting. This .performance shall be measured
by tha results of a test for erosion resistance when
subjected to high velocity air flow across the sur
face of dried samples. The samples thus tested must
be representative of machine applied material simi lar to that which can be expected on the project. The air velocity shall be not lass than------------ feet per
minute, and the duration of tha test shall be at
leasthours.
-a) Documentation of the above performance shall be submitted with the bid. In order that ail parties will
fully understand the Intantlon of application per formance at that time.
6. MATERIALS
a) The sprayed fireproofing shall be cementitious setting-type, and shall be Mono-Kote as manufac tured by Zonolite Division -- W. R. Grace A Co., or its processing distributors.
All manufactured materials shall be mill-mixed and shall be delivered In original, unopened packages bearing the name of the product the manufacturer's name and the Underwriters* Laboratories. Inc. Label.
The materials shall ba stored off the ground, under cover, and away from damp surfaces. Materials shall be kept dry until ready for use. Materials that have been exposed to water before actual use shall be discarded.
b) Water shall be dean, fresh and free from organic and mineral Impurities which would be harmful to the sprayed fireproofing materials.
7. INSTALLATION a) Application of sprayed fireproofing shall be In ac cordance with the printed instructions of the material manufacturer and the fire test report Information.
b) Only experienced applicators, approved by the ma terials manufacturer and Architect shall be allowed to place the materials. Upon request a qualified manufacturer's representative can be present for Initial application to guide and assist applicator's personnel.
c) All surfaces to which sprayed fireproofing will be applied shall be thoroughly cleaned of oil, grease, dirt loose paint mill scale or any other matter which would impair bond.
d) Temperatures and enclosure conditions shall be as specified by the materials manufacturer.
a) All patching and repairing of sprayed fireproofing, due to cutting by other trades, shall be performed under this section and paid for by the trade(s) that performed the cutting.
8. CLEAN-UP After completion of fireproofing work, equipment shall be removed and all wall and floor areas cleaned of deposits of sprayed fireproofing materials.
9. BID INFORMATION Each bidder shall submit with his bid: a) Full report(s) of Underwriters' Laboratories. Inc. fire tests including written material and detailed drawings of the tested assembly. b) Materials manufacturers printed instructions for methods and procedures of application. e) Bond test data for uncoated, coated and galvanized steel applications. d) Results of tests of material performance when sub jected to high velocity air flow.
ZONOLITE DIVISION, W. R. GRACE & CO
DESCRIPTION *
2V4* sand-concrete Ml. H' ZONOLITE MONO-KOTE following contour of underside of deck with an additional V4" across top of flute.
2Vi* sand concrete fill.
ZONOLITE
MONO-KOTE following contour of under
side of deck with an additional Vi" across
top of flute.
RATING
3 hrs. **
2 hrs.
2% * sand-concrete fllF. ZONOLITE MONOKOTE %" thick applied to undaraida of steel floor a* shown.
2V4 * aand-concrata fill. ZONOLITE MONu- . KOTE K* thick applied to underside of steel floor with '6" on top and sides of flute.
Note: 1 '6 * deep steel floor section.
3 hn. 2 hr*.
2'6" sand-gravel concrete. ZONOLITE MONO--KOTE 'K" thick applied to under side of steel deck as shown, with addi tional Vi " at top and sides of flutes, 1V4" | under trench header duCts.
2Vi * sand-concrete fill. ZONOLITE MONOKOTE applied directly to underside of steel floor with Jf,* under flat plate, add Vi" at top and sides of flutes and 1* under filled flutes under 36* trend' header duct
Note: 3" deep steel floor section. Trench header duct not shown.
3 hrs. 2 hrs.
2V4*
i 3 VS * sand-concrete fill. ZONOLITE MONO-
KOTE applied directly to underside of steel floor l/4* below corrugations.
4 hrs.
SYSTEM
^5S2Zi'
i--:---------ir*
216' sand-concrete fill. ZONOLITE MONOKOTE Vi" thick applied directly to under
side of steel floor as shown.
_ilVV i"
r
3 hrs. 14>44 '.>-.&: - 7: *. U *:.
216" sand-concrete All. ZONOLITE MONOKOTE V* ' below filled flutes to underside of steel floor as shown.
4
2 hrs.
SPRAY-ON FIREPROOFING
2V4 ' sandgravel concrete slab. ZONO-
UTE MONO-KOTE %' thick applied dlractly under slab as shown.
2 hrs.
l | ZONOLITE MONO-KOTE applied direct to '
structural steal beams and girders.
' *-v ir-
4 hrs.
3 hrs. 2 hrs.
h I
ZONOLITE MONO-KOTE applied directly to structural steal columns.
ll/*............. 4 hrs.
%*............. 3 hrs. Minimum column
14 WF 228.
2V4*____
1%'.............. 1V4 ".............. All Columns.
(Additionalratings on other side)
4 hrs. 3 hrs. 2 hrs.
-- -------- 30'
2xh" sand-gravel concrete. ZONOLITE MONO-KOTE composite floor -- beam de sign appiiad H" on underside of blended, fluted and cellular 1V4" steel floor. V4* of MONO-KOTE on top and sides of flute.
Composite beam -- following contour. (Shear strap in composite system may be replaced by shear lugs.)
i
iI
\
i
\
I 1
ZONOLITE DIVISION, W. R. GRACE & CO.
Nolite* vermiculite
aBBsase'*''*
iCRlPTiiOOMM. *'.'-TECHNICAL DATA
,*!.- w-fhbAppn-B>ily IVi IbS. per 8*.$
i in norethav45Zonollte;,,*wb*i
^
r, K results Hi a gghtwalgM, plaster tor lth hand or machina
' Conforms to ASTM 05. Urtodand^ axamination Sarvica of Undarwrtterr
gagfjgcggteark,' - .--h :-------
uMBtiftm ?MetoiLaMt
mm
100 to*. areswe*
i
tomato '
a
ia
l a^
FMaacmt*
H'mto. H'-mhv H'wUn.
jManeMMe Cencrete** CareeUaisnae
X
X
aa
te'mtn. 4b* min.
ITtltoeter thklMMi may be nrM tor lira (MitoM raUflC*. Baa ^.'VanwttMlWa toeiMuto Tin ReeisMnca Rallno-
W mnatotoc eancraia celMnc ar wad aurfacaa require non' than tH* ar H". reepecttoebr. af Master to pteduce desired lines or sur. toss*. malal lath ar atlro lath sbsli ba ` i ,--aaa. malal tarrtoc may ba required.
FIRE RESISTANCE RATINGS
IVi* ZONOLITE PLASTER over the face of self-lurring metal lath wrapped around column.
Same as above except IVi' ZONOLITE PLASTER over face of self-furring metal lath.
IVi' ZONOLITE PLASTER over the face of metal lath. Lath spaced IVi' from column flanges. Space behind lath on flange faces filled with plaster, as shown.
Same as above except 1" ZONOLITE PLAS TER over face of metal lath.
4 hrs. 3 hrs.
4 hrs. 3 hrs.
Hr* Easistenca: Soo partial Hat of lira losittonc* ratings local Zonollte offlca for tha most racant rating,)
K Factor; 0.99 (Sand Plaster. 3.0).
' >Mai;fiw<
..
(1) Zonollta Plaster Aggregate should be used with gypsum?''
plaster , that has boon especially formulated for lightweight'.
aggregates.
y#\>s
(2) If ZonoUte plaster Is applied directly to exterior masonry
walls, wall design should Insure Impermeability to wind-driven
rain, and an Interior surface above the dew point
. >2
"y
COLUMNS
Metal Lath
<
>
I
f
1I
2' ZONOLITE-portland cement PLASTER over paper-backed wire fabric wrapped around column with an additional wire fabric (no paper) over scratch coat
/
Column protected with IVi' ZONOLITE PLASTER applied over two layers of Vi* thick long length plain gypsum lath wrapped with one layer of hexagonal mesh poultry netting. Same protection es above except 1* ZONO LITE PLASTER applied over gypsum lath. Column protected with I* ZONOLITE PLAS* TER applied over one layer of Vi* thick per* forated gypsum lath.
2Vi" sand-concrete fill. 1" ZONOLITE PLAS* TER on metal lath or 2Vi" sand-concrete fill on formed steel floor. Vi' furring chan nels with Vi' ZONOLITE PLASTER on metal lath. 2Vi" sand-concrete fill. Vi' ZONOLITE PLASTER on metal lath. 2' sand-concrete fill. Vi' ZONOLITE PLAS TER on metal lath.
4 hrs.
Paper-Sacked Wire Fabric
4 hrs. 3 Vi hrs.
2 hrs.
OypMim Lath
4 hrs.
3 hrs.
2Vi nrv,
StMi Jotttl UfM 8lt(
ConttrvctloA
11*
r
r v1-
-i .1 i i
>i .1f
* r
PLASTER AGGREGATE
to ASTM C28. Zonoltta verC39. Metal shaU be pratactad
shaft ba carefully Inspected and taring. Angles shall ba straight ftopwggb^^^^^^ljrffor minimum thickness of piaatar
*--may ba mixed by hand or machinar-Wheartiachlheintaad. uaa feflowing sequence: (1> ChargiinbmWhto'i
(4) \Mlr todeslred pbruUstency. adding water as required. .~?&&Settfng Tlmo', Zbnollta aarmlcuBte plaster shall sat
*'
b. Machine application: Um onffbered gypsum designated "for MacMm AppticatkxT by the manufactum.
APPLICATION OP BASE COATSUm two or ttnao coat work dapending on piaatar____ detailed directions on solid plaster partitions, hoUowr__ partitions and other bases, consult Manufacturer or referit ASA or Vermicuilte Institute Standard Specifications.
APPLICATION OF FINISH COATS--
Gypsum-sand float finish, Kaam's Camem-flme-Mnd-floatftflg
ish. machine-applied gypsum vermiculits texture flnlshfV.br.
mill-mixed acoustical plasters (Zonollte Acoustical Plastfct
ahait ba applied following ASA or Vermicullta Institute Stan ard Specifications. Qypsum-Ume putty trowel finishes shalhljk
elude approximately ft cu. ft (50 lbs.) fine silica mnd'.per
100 lbs. gauging plaster. .. ...
-
ZONOUTE FINISH COAT-
Finish Coats are available for application to acoustical piasters!
or. may ba applied directly to concrete as a texture coat. When
applied to a thickness of Htm over acoustical plasters, Zonollte
Finish Coat will not adversely affect sound absorption. ZonoV
Kte Finish Coat is mill-mixed, requiring only the addition of
water at the fob. It Is applied by any one of several pump type
plaster machines or sir-spray texture guns. It has a light
reflectivity of 65%.
. ..j.-fc
1* of ZONOLITE PLASTER over the face of metal lath. At leatt 2V4* air space between structural members and back of metal lath.
4 hrs.
BEAMS. GIRDERS A TRUSSES
%* of ZONOLITE PIASTER plus V4* of ZONOLITE ACOUS TCAL PLASTIC over the face of metal lath. At least 2V4" air space between structural members and back of metal lath.
4 hrs.
%* of ZONOLITE PLASTER over the face of
metal lath. Calling openings for two duct
outlets as shown and for two electrical out
let boxes; aggregate area of openings not to
exceed 100 sq. in. In each 100 sq. ft. of
Ii
ceiling area. Duct openings protected by dampers.
3 hrs.
gueMwded fI*rWaUIRlwlwgSo
I1 1* of ZONOUTE PLASTER on metal lath
I furred or In contact with the lower flange
of supporting primary beams.
4 hrs.
y~ of ZONOLITE PLASTER on metal lath furred or in contact with the lower flange of supporting primary beams.
3 hrs.
ZONOUTE PLASTER on metal lath --sup ported on wire or channel hangars. %'
piaster.
4 hrs.
MMduaay Protected
1* of ZONOUTE PLASTER applied to each ' face of V4" thick long length plein gypsum - lath. No studs. Overall thickness of par
tition 2V4".
*/4" of ZONOLITE PLASTER applied to each face of V4" thick long length plein gypsum lath. No studs. Overall thickness of pari tition 2*.
2 hrs.
SOUD PLASTER PARTITIONS
1 hr.
OypMn Lath
\ ZONOUTE PLASTER applied on metal lath \ fastened to Incombustible studs spaced ! 16* on centers. Overall thickness of par-
1 tition 2%*.
2 hrs.
I l
ZONOLITE PLASTER applied on metal lath ; fastened to Incombustible studs spaced 16*
i i on centers. Overall thickness of partition 2*. 1 hr. ZONOLITE DIVISION, W. R. GRACE & C
&R ZONOLITE PRODUCTS
%
ZONOUTE* VormicuVts CONCRETE AGGREGATE
For insulating concrete roof deck applications over vented galvanized steel, fomtboard, structural and pre-cast concrete. For currant catalog, sand for CA-140.
ZONOUTE VermicuVte
Water-repellent Insulation for cores and cavities In masonry construction. Doubles thermal insula*
MASONRY FILL INSULATION tion In most systems. Futt details in catalog MF-83.
ZONOUTE DYFOAM*
In roll or board form, for perimeter Insulation, cold storage, flotation, innumerable uses. Send for
EXPANDED POLYSTYRENE catalog DF-26.
ZONOUTE DYFOAM* NOISE CONTROL BOARD
Specially-laminated polystyrene for. sound-deadening in wall and celling-systems. Full details and tes^data In SC-101.
ZONOUTE Vermiculfte ATTIC INSULATION
Free-flowing, permanent mineral granules for Insulation of horlxontaripices. Can be applied di rectly over existing Inadequate insulation. Ask for brochure HI-203.____
ZONOUTE Glass Fiber INSULATION
Full range of widths, thicknesses for any R-factor requirement Foil-faced, kreft-faced or plain. De tails in brochure HI-203.
(' t
*ZONOLITE,SALES' OFFICES
ZONOUTE DIVISION W.R. BRACE ACO.
MASSACHUSETTS, Easthampton 01027
R. O. Box 112
WISCONSIN, Mltwoukae 900 North 43rd SL
ALABAMA. Birmingham 35205 2BOO Filth Ave- South ARIZONA. Phoenix 15031 4220 Wnt Glsnrasa
ARKANSAS, North Uttlo Rock 72114
R. O. Box 294
CALIFORNIA 'Lot Angelos 90041
756 Colorado Bird. Los Angslos 90041 R. O. Box 41077 Modto 95351 416 Hosmor Strsot R. O. Box SCZ Newark 94560 6651 Smith Avenue R. O. Box 217 COLORADO. Denver 11IS. Novalo Street
FLORIDA Boca Retan 33432 R. O. Box 67 *Boea Reton 1555 N.W. First Avenue `Hialeah 1050 S.E. 5th Street Jacksonville 32202 1530 East Adams SL Tampa. 35th St A 3rd Ave. R. O. Box 5047, Ybor Station
GEORGIA, Atlanta 3Q30S 1167 Zonolite Place. NX. R O. Box 6127. Station F -OEORQIA. Atlanta 520 Rermalums Rlaco N.W. ILLINOIS, Chicago 60643 12300 South Ashlar
KANSAS. Wichita 67214 1463 Berertso Avenue
KENTUCKY.-WIMer, Newport 41070 112 North Street LOUISIANA. Now Ortoens 70121 4729 River Road R. O. Sox 10262
MARYLAND. Belttvlllo. 20705 R. O. Box 347
MICHIQAN. Dearborn 4S120 14300 Ham Avenue MINNESOTA. Minneapolis 55422 4725 Olson Hwy.
GTsawsa*"1'*
MISSOURI, SL Louis 63110 1705 Sulphur Avenue MONTANA. Libby 59923 R. O. Box 607 NEBRASKA. Omaha 36th and 1 Street NEW JERSEY, Trenton 08607 336 Whitehead Reed R. O. Box 2124 NEW YORK, Weedsport 13164 R. O. Box 310 NORTH CAROLINA, High Rolnt
27260 1701 Prospect Street Extenetor R. O. Box 1300 OHIO. Cleveland 1123 W. Uth Street OREOON, Portland 97227 2303 N. Harding Avenue PENNSYLVANIA. Eltwood aty
16117 12th and Factory Streets PENNSYLVANIA, Now Cottle 202 East Cherry Street Sox 1207 PUERTO RICO. Cupey Bale.
Kn. OJ Insular Highway 045 SOUTH CAROLINA. Travelers Rest
29690 R. O. Box 517 TEXAS, Houston 7700S 611 Woet 22nd Street WASHINGTON, Auburn 9MT2 P. O. Box A WASHINGTON. Spokane. 9S201 1318 N. Maple Street
RROCESSUM DISTRIBUTORS
HAWAII, Honolulu (17) VermleuIHe Of Hawaii 42-A Mepunepune Street
MONTANA. Great Falls 59401 Roblnsan insulation Co. 122S North Rhror Orhra R. O. Box 1419
NEW MEXICO, Albuduarquo (7107 Southwest Vormlculltt Co. 5119 Edith Boulevard. NX. R. a Boa 4302
NORTH DAKOTA. Minot 56702 Robinson Insulation Co. R.O. Box I7B2
OKLAHOMA, Oklahoma CMy 73111 Texas VomdeuIRo Co. 201 North Eastern R.O. Boa 11402
TENNESSEE, Nashville 37204
Tennessee Zonolite Co.
4061
Avenue
TEXAS Dallas 7S222 Texas Vermicuttta Co. 2051 Manila Road R. O. Box 6306 Houston 77006 VermlcuMo Products. Inc. R. O. Boa 7327
Southwest VormlctilRo Co. Routs 3. Boa 191B San Antonio Texas Varmlculito Co. R. O. Box 9114 UTAH. Salt Lafca aty 94110 VorwUcullto intormountoln. Inc. 333 W. First South R.O. Boa 2390
CANADA ALBERTA Caleaty Grant Industries A Division o Eddy Match
Company. Limited 4030 6th SL. S. E. Boa 69. Postal Station "A"
Polystyrene Fertile
Edmonton Grant Industrie* A Olvislan of Eddy Match
Company. Limited B602-106A Avenue R. O. Box 174 LothbHdgo Brant Industries . A Division of Eddy Match
Company. Limited 3003 Laasids Averted R. O. Bee 1104
BRITISH COLUMBIA Vancouver(4) Grant Industries A Division of Eddy Match
Company, Limited 476 Industrial Avenue Vancouver (S) Grant Industries A Division of Eddy Match
Company. Limaad 107S MatvUe Street
MANITOBA Wlnnloed (101 Grant Industrial A Division of Eddy Match
Company. limited 760 Wad Street
ONTARIO SL Thomas F. Hyde * Company. Ltd. 94 Woodward Avenue Taranto (IS) F. Hyde A Company, Ltd. 3349A Bloor StraaL Wast
___ Id (91 F. Hyde 1 Company, Ltd. 1540 Dundat StrooL West R.Q,, Montreal (9) F. Hyde 6 Company, Ltd. 2115 Cotae da UI snsa ~
BASIL, Ragkro Grant tndustrios A GMsIon of Eddy Match
Company, limited 1015 Angus Street R. O. Boa 1213
SASH. Saskatoon Grant Industries A Ohrlsion el Eddy Match
Company. Limited 733--1st Ave. North R. O. Box 1040
:v
'RM9 Copyright 1966.' Zonollta. Mono4(ote. end Dyfoam era registered trade nomas of Zonalho Ohrlsion. w. R. Greco 6 Co. Sinca
n *"!nj iTjImilrvTiT?uTfini n'"r
th* Zo"om
"- 6, l^wj^^Jra^wpMilM-f^JtaNure of ha