Document QX7do6y8bRb2ZegL3xNxBq71R
696
CHAPTER 32
1953 Guide
Fig. 7. Portion op Duct System fob Example 3 '
forms will produce a substantial saving in pressure loss. The addition of vanes or splitters divides an elbow into parallel channels, each having more favorable radius and aspect ratios than the original elbow. Values of addi tional equivalent length L, for elbows of square cross-section having various vane forms and combinations, may be found from Table 3 in which values
of L/W are shown.
LOSSES DUE TO AREA CHANGES
Area changes, in ducts, generally unavoidable, are necessitated frequently by the building construction or changes in the volume of air carried. Ex perimental investigations14'16 of pressure changes, and pressure losses at changes of the area of duct cross-sections, indicate that the excess pres sure loss over the normal friction loss is a dynamic loss due to a faster stream expanding into a slower stream, as determined by the actual areas occupied by the flow rather than the areas of the duct. No perceptible dynamic loss is due to the converging of the air stream itself where the flow
is contracted, but the air stream continues to converge beyond the edge of the contraction and' reaches a minimum at the vend contracta. This con traction of the air stream is shown in Fig. 8. For contraction, therefore,the dynamic loss is caused by expansion from the vena contracta to the full area following the contraction. Enlargement in area may be considered .as a special condition of general expansion following contraction; Fig; 8 illustrates (a) abrupt enlargement and (b) abrupt contraction.
For a sudden symmetrical enlargement, a theoretical expression for the
loss is
.
Fig. 8. Air Flow at 'Abrupt Enlargement or Contraction of Air Stream
Air! DuctDesign or for standard air;
697
(7)
where
h,, = pressure loss due to sudden enlargement, feet of fluid flowing. He *= pressure loss due to sudden enlargement, based on standard air, inches
of water.
Table 3. Pressure Loss in Vaned Elbows of Square Cross-section Expressed in Additional Equivalent Duct Length*- b
Additional Equivalent Length L = Duct Width W, in Feet, Multiplied by L/W \ Values Shown .
* These values are based upon vane test data of Reference 13 which have been modified by the finding
of Reference 9.
-
6Vanes: A - a large number of small arc vanes; B asmall number of largearc vanes;vC = hollow vanes having different outside and inside curvature; D =.four vanes with radius of 0.4 Vi-; E =- single splitter with radius of 0.5 W; F = no vanes or splitters'.
t>i = velocity in the inlet duct, feet per second. vi = velocity in the outlet duct, feet per second. Vi = velocity of standard air-in the inlet'duct, feet per minute. V = velocity of standard air in the outlet duct, feet per minute. Ai = area of the inlet duct, square feet. At = area of the outlet duct, square feet.
The loss for a sudden symmetrical contraction, ho can similarly be ex pressed. as
/_
V AJ