(Source: Amended at IZ 111. Reg. 81S. effective . December 24. 1987)
7) Which 1$ a pressure tank as described In Section 215.121(a).
Section Z1S.I22 loading Operations
a) No person shall cause or allow the discharge
of more than 3.0 kg/hr (8 Ibs/hr) of organic
material Into'the atmosphere during the
loading or any organic,aiaterlal from the
aggregate loading-pipes of any loading
facility haying through-put of greater than
1S1 cubic meters pef day (40.000 gal/day)
Into any railroad tank car. tank truck or
. . trailer unle'ss such loading facility Is
equipped with submerged loading pipes or a
devlce-ttiat Is equally effective In
..
controlling emissions and Is approved by the.
Agency according to the provisions of 3S 111.
Adm. Code 201.
b) No person? shall-cause"oir allow the loading of ..any organic material. Into any stationary tank having a storage,capacity of greater than 946 1 (250 gal), unless such tank Is equipped . with a permanent submerged loading pipe or an equivalent, device approved by the Agency according to the provisions of IS 111. Ada. ,
Code 201, or unless such tank Is a pressure tank as described In Section 215.121(a) or is Mttedwlth a recovery system as described in Section 215.121(b)(2).
c) Exception: if no odor nuisance exists the , limitations of this Sectlog.shall only apply to the loading of volat11e;:organic liquid with a vapor pressure of 17.24 kPa (2.S psla) or greater- at 294.3K (70F).
:b) Subject to subsection (aj no owner or - operator of a stationary storage tank shall cause or allow the storage of any volatile petroleum liquid In the tank.^unless:
1) The tank is equipped with one of the vapor loss control devices specified In Section 215.121(b); '
2) There are no visible holes, tears or other defects In the seal or any seal fabric or material of any floating.roof
3) All ^openings of any floating roof deck, except.stub drains, are equipped with
. covers, lids of; seals, such that:.
. .. A); The cover, lid or seal Is In the closed position at all times except .when^peicaleimL Uqu.tA.ls transferred to or from the tank;
_ -. ,B) .Automatic bleeder vents are closed at ... ; - .all times except when the roof Is ' .. floated off dr landed on the roof leg -supports? and-
C) Rim vents. If provided; are set to open when the roof. is belng floated off. the roof leg supports or at the manufacturer's recommended setting:
;4)., Routine Inspect Ions-Of Moating roof seals are conducted through roof hatches once every six months;
(Source: Amended at 12. 111. Reg. :81S. effective 0ecember>24, 1987)
Section 2)5.123 Petroleum Liquid Storage Tanks a) The requirements dr subsection (b) shall not
apply to any stationary storage tank:
5) A complete inspection of the cover and seal of'any floating roof tank Is made whenever the tank ts emptled for reasons other than the transfer .of petroleum liquid during the normal operation of the tank., or whenever repairs are made as a resuTr of any semt-ahh6aT'fnspectTon or
Incidence of roof damag'd or defect; and
1) Equipped before January 1. 1979 with one of the vapor loss control devices specified In Section 215.121(b). except Section 215.121(b)(1):
2) With a capacity of less than 151.42 cubic meters:
3) With a capacity of less than 1.600 cubic meters (422,400 gallons) and used to store produced crude oil and condensate prior to custody transfer;
'6) A:record of the.results of each ' Inspection conducted under subsection (b)(4) or (b)(S) Is maintained.
c) Owners and-operators'-of petroleum liquid storage tanks were required to have
compliance schedules as summarized In Appendix C.
(Source: Amended at 3 111. Reg. 124. effective July.20. 1979)
4) With a capacity of less than 1.430 cubic meters (378.000 gallons) and.used to store produced oil or condensate.In crude oil gathering;
5) Subject to new source performance standards for storage vessels' of petroleum liquid. 3S 111. Ado. Code 230:
Section 215.124 External Floating Roofs
a) In addition to meeting the requirements of Section 215.123(b). no owner or operator of a stationary storage tank equipped with an
external floating roof shall cause or allow the storage of any volatile petroleum liquid In the tank unless:
6) In which volatile petroleum liquid is not stored: or
1) The tank has been fitted with a' continuous secondary seal extending from
- 93 -