Document QJDNo9wkM20g8reYr7qE1wLG4
PLAINTIFF'S EXHIBIT
American Water Works Association
September 1974 Part 2
A Study of the Problem ofAsbestos in Water
by
The American Water Works Association Research Foundation
c
l
CAPCO JEN 0020272
A Study of the Problem of Asbestos in Water
by The American Water Works Association
Research Foundation 6666 W. Quincy Ave. Denver, Colorado 80235
AWWA has accepted this report as repre senting the opinion of its authors. The authors have given explicit instructions that the report be published using their exact copy; the JOURNAL'S editors have complied. The summary represents a reasonable distil late of the body, however, the reader is ad vised to read the entire report for a rational understanding of the asbestos-from -asbestos-cement-pipe problem.
CAPCO JEN 0020273
Project History
Research has revealed a recognized occupational health hazard connected with excessive and prolonged inhalation of asbestos dust. A related question has arisen regarding the possible health hazard that may result from the presence of asbestos fibers in water, beverages, food, or fluids used for the administration of drugs. Since considerable amounts of asbestos-cement pipe convey potable water in North America, Europe, and other parts of the world, a question has also been raised with respect to the possible health hazard that may be associated with drinking water which has flowed through asbestos-cement pipe.
The asbestos industry has been investigating the biological effects of asbestos for many years. Additionally, the A/C Pipe Producers Association contracted with the American Water Works Association (AWWA) Research Foundation to study the problem of asbestos in water, and specifically with rela tion to the use of asbestos-cement pipe.
The objectives of the study were to: (1) assemble all perti nent literature on the biological effects of asbestos; (2) have a committee examine the technical literature and on the basis of present knowledge issue a report answering the question: Does asbestos in water constitute a hazard to health by caus ing a greater than normal occurrence of gastrointestinal can cer or malignant mesothelioma of the peritoneum or pleura?; and (3) recommend the research required to finally resolve the matter.
Selection of Study Committee In the formation of the select committee, considerable at
tention was given to keeping the group manageably small but invested with competency in the following specialties:
1. An individual familiar with the asbestos problem in air and water.
2. A representative of the U.S. Environmental Protection Agency (EPA) familiar with the problem.
3. A representative of the water supply industry. 4. An expert in analytical methods. 5. A pathologist. 6. An epidemiologist. 7. An international expert knowledgeable in the water, medical and public health fields, and capable of providing in put and insight from abroad. The fact that the committee members accepted the first in vitation to serve indicates their interest in the subject. The following persons served on the study committee:
Marvin Kuschner, M.D. Dean, School of Medicine State University of New York Stony Brook, New York
Roger Lee Chief, Surveillance & Technical Assistance Section Program Operations Branch Water Supply Division U.S. Environmental Protection Agency
Gordon G. Robeck Director, Water Supply Research Laboratory U.S. Environmental Protection Agency
John R. Rossum
SEPTEMBER 1974
Sanitary Engineer California Water Service Company
Marvin A. Schneiderman, Ph.D. Associate Director for Field Studies and Statistics, DCCP U.S. Department of Health, Education, and Welfare Public Health Service National Cancer Institute
E. Windle Taylor, C.B.E., M.A., M.D., D.P.H., F.R.C. Path. Director of Water Examination (retired March 1974) Metropolitan Water Board London, England
George W. Wright, M.D.
Procedure
Two meetings of two days' duration were held. Prior to the first meeting the AWWA Research Foundation staff gathered and analyzed, to the extent possible, all the pertinent litera ture on the biological effects of asbestos. Copies of papers dealing specifically with asbestos in water, including analyti cal methods, were sent to the committee members for their study prior to the first meeting. Each committee member also received abstracts of the Lyon Conference papers, the full text of which was available for their examination upon re quest. The committee members were also instructed to con duct their own search for additional information.
The Lyon Conference, convened by the International Agency for Research on Cancer, was held in Lyon, France on October 5-6,1972. It involved 137 participants from 20 coun tries and was called to review all evidence relating asbestos with cancer and other biological effects.
Worthy of mention is the fact that in addition to the techni cal papers listed in the bibliography, the conference resulted in the issuance of a report of the advisory committee on asbestos cancers. Panels specializing in epidemiology, patho logy, and physics and chemistry, met in a separate session after the conference and prepared a report which consisted of two sections.
The first section provided a general review in the form of answers to a number of important general questions about the relation of asbestos to cancers of different body sites while the second section offered recommendations for further research. Question seven in the first section was phrased as follows:
"Is there evidence of an increased risk of cancer resulting from asbestos fibres present in water, beverages, food or in the fluids used for the administration of drugs?" The answer was as follows: "Such evidence as there is does not indicate any risk." The panel on pathology and experimental pathology recom mended the following two projects for further experimental study. 1. "The effect of long-term ingestion of fibres of various sizes, shapes, and chemical composition should be studied." 2. "The effects of fibres and associated metals on the me tabolism of target organs should be investigated." Neither of these two projects were rated high in priority. The bibliography lists the material distributed to each member or available for their study. The purpose of the first meeting was to orient the commit tee, exchange information and views, discuss the work re ported in the literature, and assign various tasks to be per formed by the committee members during the three-month
COMMITTEE REPORT 1
CAPCO JEN 0020274.
interim between meetings.
The second committee meeting concentrated on the health
hazards posed by asbestos in water (based on present -knowledge of the subject) and recommendations for research
needed to answer unresolved questions.
Following the second meeting, several committee members collaborated on the development of the statement of the com
mittee's position and recommendation. This was circulated by mail to all members.
Section III (Summary); section IV (Recommendations);
section V (Committee Report); section VI (References); and
section VII (Appendices) comprise the COMMITTEE RE
PORT.
Bibliography
General
Bonser, G. M. & Clayson, D. B. Feeding of Blue Asbestos to Rats. Ann. Rprt. 1967 Brit. Empire Cancer Campaign for Res. p. 242.
Burns, A. F. Chrysolite Fiber Levels in Municipal Water Systems. Johns-Manville Res. Rprt. No. 404-79. (Jun. 4, 1971).
Burns, A. F.; Jaunarajs, K. L.; & Reimschussel, G. P. Method for the Quantitative Determination of Chrysotile Fiber in Samples from Various Sources. Johns-Manville Res. Rprt. No. 404-67. (Aug. 3, 1970).
Carriere, J. E. Behaviour of Asbestos-Cement Pipes in the Soil. Inti. Water Supply Assn. Paper presented at Stockholm, Sweden. (Jun. 15, 1964).
Cunningham, H. M. & Pontefract, R. Asbestos Fibers in Beverages and Drinking Water. Nature, 232:332 (Jul. 30, 1971).
Eick, H. Corrosion in Asbestos Cement and Concrete. Inti. Water Supply Assn. Paper presented at Vienna, Austria (Sep. 1,1969).
Elmes, P. C. & Simpson, M. J. C. Insulation Workers in Belfast. 3. Mor tality 1940-66. Brit. Jour. Indi. Med., 28:226 (1971).
Enterline, P.; Decoufle, P. & Henderson, V. Mortality in Relation to Occupational Exposure in the Asbestos Industry. Jour, of Oc cupational Med., 14:897 (Dec. 1972).
Gould, D. A Dangerous Dust New Scientist, (Mar. 9,1967). p. 453. Harwood, C. F. Asbestos Air Pollution Control. Report prepared for
Illinois Inst, for Environ. Quality. (Nov.-1971). Kiviluoto, R. & Meurman, L. Results of Asbestos Exposure in Fin
land. Proc. Inti. Conf. on Pneumoconiosis, Johannesburg, South Africa. (Apr.-May 1969). Kristiansen, H. Extraction of Calcium by Soft Water from Concrete and Asbestos Cement Pipes. Norwegian Inst, for Water Res. (Mar. 1973). Lewinsohn, H. C. The Medical Surveillance of Asbestos Workers. (Brit.) Roy. Soc. Health. 2:69 (1972). Mancuso, T. F. & Coulter, E. J. Methodology in Industrial Health Studies. Arch, ofEnviron. Health, 6:210 (Feb. 1963). Mancuso, T. F. & El-Attar, A. A. Carcinogenic Risk and Duration of Employment Among Asbestos Workers. Proc. 2nd Inti. Conf. on Biol. Effects of Asbestos. Dresden, Germany. (Apr. 1968). p. 161. Meurman, L. O.; Kivoluoto, R. & Hakama, M. Mortality and Mor bidity of Employees of Anthophyllite Asbestos in Mines in Fin land. Paper presented at Lyon, France conference. (Oct. 2,1972). McDonald, J. C. Cancer in Chrysotile Mines and Mills, Paper pre sented at Lyon, France conference. (Oct. 2,1972). McDonald, J. C., et al. Mortality in the Chrysotile Asbestos Mines and Mills of Quebec. Arch, ofEnviron. Health, 22:677 (Jun. 1971). MCDonald, J. G, ET al. Mortality in Chrysotile Producing Industry of Quebec: A Progress Report Manuscript presented at 4th Pneumo. Conf., Bucharest (1971). Newhouse, M. L. A Study of the Mortality ofWorkers in an Asbestos Factory. Brit. Jour, ofIndl. Med., 26:294 (1969). Newhouse, M. L. Cancer Among Workers in the Asbestos Textile In dustry. Paper presented at Lyon, France conference (Oct. 2, 1972). Oettle, A. G. Tumors of the Alimentary Tract in Mortality from Malignant Neoplasms of the Alimentary Canal in Whites, Col oreds, and Asians in South Africa, 1949-1958. Natl. Cancer InsL Monograph No. 25. (Jul. 1967). Olson, H. L. Does Asbestos in Water Supply Present a Health Hazard? Paper presented at the Conf. ofState San. Engrs. at San Francisco, Olif. (May 7, 1973).
Pontefract, R. D. & Cunningham, H. M. Penetration of Asbestos through the Digestive Tract of Rats. Nature, 243:352 (Jun. 8, 1973).
POOLEY, F. D. Mesotheliomas in Relation to Exposure. Paper pre sented at Lyon, France conference (Oct. 2, 1972).
Quint, S. M. Transite Pipe Test Line--Determination of Asbestos Fiber in Water. Johns-Manville Res. Rprt. No. 425-T-1360. (Sep.
29, 1971). Rickards, A. L. Estimation ofSubmicrogram Quantities of Chrysotile
Asbestos by Electron Microscopy. Anal. Chem., 45:809 (Apr. 1973). Sargent, H. A. Asbestos in Drinking Water. Paper presented at NEWWA Meeting at Northfield, Vt. (May 17, 1973). Selikoff, I. J.; Hammond, E. C. & Seidman, H. Cancer Risk of Insula tion Workers in the United States. Paper presented at Lyon, France conference (Oct. 2, 1972). Speil, S.; & Leineweber, J. P. Asbestos Minerals in Modern Tech nology. Environ. Res. 2:166 (Apr. 1969). Swinburne, L. M. Report on Research at St. James' Hospital, Leeds. Appendix 4. Included in report from Asbestos Res. Council (Oct. 1970-Oct. 1971). Vigliani, E. C.; Ghezzi, I; & Maranzana, P. Epidemiological Study of Asbestos Workers in Northern Italy. Proc. 2nd Inti. Conf. on Biol. Effects of Asbestos. Dresden, Germany. (Apr. 1968). Wagner, J. C. Personal communication to Dr. P. V. Pelnar. (Oct. 27, 1972). Westlake, G. E.; Spjut, H. J. & Smith, M. N. Penetration of Colonic Mucosa by Asbestos Particles. An Electron Microscopic Study in Rats Fed Asbestos Dust. Laboratory Investigation. Ofcl. Jour, of the Inti. Academy ofPathology, 14:2029 (Nov. 1965).
Asbestos-cement water pipe and human health
Cancer Research in 1967. Brit. Med. Jour., 7:73 (Jul. 1968). Does A/C Pipe Constitute a Hazard to Health by Causing an Ex
cessive Occurrence of Gastrointestinal Cancer or Malignant Mesothelioma of the Peritoneum or Pleura? Eliminating the Hazards of Asbestos Waste. Munic. Engrg., (Brit.) (Feb. 13,1970). Exposure to Asbestos. Nature, 234:383 (Dec. 17, 1971). Municipal Water Systems Analysis--Table provided by Johns-Man ville Res. Ctr.
Lyon conference papers
Ahlman, K., et al. Anthophyllite Mining and Milling as a Cause of Asbestosis
Akehurst, R. L. The 1969 Asbestos Regulations--Their Economic Appraisal
Allison, A. C. Effects of Asbestos Particles on Macrophages, Mesotheiial Cells and Fibroblasts
Ashcroft, T. & Heppleston, A. G. Quantitation of Asbestos Fibres in Lung Tissue
Becklake, M. R. Assessment of Methods Used in the Studies of the Biological Effects of Asbestos--C. Lung Function
Berry, G. Hygiene Standards--Theory and Application Boersma, A.; Degand, P. & Havez, R. Mesotheliome Diffus. Etapes
Biochmiques du DiagnosUc. Detection et Dosage de L'Acide Hyaluronique Dans Le Liquide Pleural Bohlig, H. & Gilson, J. C. Assessment of Methods Used in the Study of Biological Effects of Asbestos: Radiology Bohlig, H. & Hain, E. Cancers in Relation to Type of Fibre, Dose, Occupation and Duration of Exposure (b) Manufacturing-Ill Environmental Butler, E. B. & Berry, A. V. Diffuse Mesotheliomas Diagnostic Cri teria Using Exfoliative Cytology. Cooper, W. C. & Miedema, J. Asbestos in Relation to the Type of Fibre and Dose in the Insulation Industry Cralley, L. J. & Sunderman, F. W. Interactions of Metals and Minerals in Carcinogenesis. Interim Report of Investigations after 22 months Elmes, P. C. Therapeutic Openings in the Treatment of Mesothelioma Elmes, P. C. The Natural History of Diffuse Mesothelioma Enterline, P. E. & Weill, H. Asbestosis in Asbestos Cement Workers Gibbs, G. W. & DuTorr, R.S. J. Environmental Data in Mining Gilson, J. C. Progress in Epidemiology Greenberg, M. The Value of A Cancer Register in the Study of Asbestos Tumours Hammond, E. C. & Selikoff, I. J. Relation of Ggarette Smoking to Risk of Death of Asbestos-Associated Disease Among Insulation
2 ASBESTOS IN WATER
JOURNAL AWWA
CAPCO JEN 0020275
Workers in the US Harington, J. S. Chemical Factors (Including Trace Elements) as
Aetiological Mechanisms Harries, P. G. Assessment of Methods Used in the Studies of the
Biological Effects of Asbestos Hinson, K. F. W., et al. Criteria for the Diagnosis and Grading of
Asbestosis Holmes, S. Criteria for Environmental Data and Bases of Threshold
Limit Values--Environmental Data in Industry Holmes, S. Sampling Methods Jones, J. S. P. & Sheers, G. Pleural Plaques Kannerstein, M.; Churg, J. & Magner, D. Histochemical Studies in
the Diagnosis of Mesothelioma Langer, A. M. & Pooley, F. D. Identification of Single Asbestos
Fibers in Human Tissue Le Bouffant, L.; Martin, J. C. & Durif, S. Structure Et Composition
Des Plaques Pleurales LtN dell, K. V. Asbestos and the Community--Industrial Uses McCaughey, W. T. E. & Oldham, P. D. Diffuse Mesotheliomas: Mor
bid Anatomical and Histological Diagnostic Criteria, Including Observer Variation in Histological Diagnosis McDonald, J, C. Asbestosis in Chrysotile Mines and Mills McDonald, J. C. Cancer in Chrysotile Mines and Mills Meurman, L. O.; Kiviluoto, R. & Hakama, M. Mortality and Mor bidity of Employees of Antohpyllite Asbestos Mines in Finland Morgan, A. & Cralley, L. J. Chemical Characteristics of Asbestos
and Associated Trace Elements Newhouse, M. L. Cancer Among Workers in the Asbestos Textile In
dustry Nicholson, W.J.& Pundsak.F. L. Asbestos in the Environment Oldham, P. D. Asbestos in Lung Tissue Oldham, P. D. A Trial of Techniques for Counting Asbestos Bodies in
Tissue Pooley, F. D. Mesothelioma in Relation to Exposure Pooley, F. D. Methods for Assessing Asbestos Fibres and Asbestos
Bodies in Tissue by Electron Microscopy Rajan.K. T. Experimental Methods--Organ Culture
Selikoff, I. J.; Hammond, E. C. & Seidman.H. Cancer Risk ofInsula tion Workers in the US
Sluis-Cremer, G. K. & Du Toit, R. S. J. Amosite and Crocidolite Mining and Milling as Causes of Asbestosis
Smither, W. J. & Lewisohn, H. C. Asbestosis in Relation to the Type of Fibre, Dose, Occupation and Duration of Exposure in Textile Manufacturing
Stanton, M. F. Some Aetiologic Considerations of Fiber Car cinogenesis
Suzuki, Y.; Kannerstein, M. & Churg, J. Electron Microscopy of Normal, Hyperplastic and Neoplastic Mesothelium
Timbrell, V. Physical Factors as Aetiological Mechanisms Timbrell, V. Progress in Physics and Chemistry Wagner, J. C. & Berry, G. Considerations of Aetiological Mecha
nisms and Other Factors-Information Obtained from Animal Experiments Wagner, J. C. & Berry, G. Investigations Using Animals Wagner, J. C. Report on Progress Made on the Recommendations of the UICC Working Group on Asbestos and Cancer, 1964. Warwick, M., et al. Immunology andAsbestosis Webster, I. Malignancy in Relation to Crocidolite and Amosite Summary report of the advisory committee on asbestos cancers to the Director of the Inti. Agency for Res. on Cancer, a division of the World Health Org., Lyon, France. (Oct. 5, 1973) Recommendations for further research by epidemiology, pathology and experimental pathology, and physics and chemistry panels Abstracts ofpapers Curry, M. G. & Gigliotti, G. M. Cycling and Control of Metals. Proc. of an Environ. Resources Conf., Columbus, Ohio. Oct. 31-Nov. 2, 1972. Report No. NERC-C-73-1 (Feb. 1973). Smith, R. W., et al. Aqueous Surface Chem. of Asbestos Minerals. Chemical and Metallurgical Engrg. Dept., California State Univ. and Colleges, Univ. of Nevada, School of Mines, Reno, Nev. Smithsonian Science Info. Exchange Notice of Res. Proj. sup ported by HEW, PHS, Health Service Mental Health Admin., Natl. Inst, of Occupational Safety and Health (Sep. 1971-Aug. 1972).
SEPTEMBER 1974
COMMITTEE REPORT 3
CAPCO JEN 0020276
DOES THE USE OF ASBESTOS-CEMENT PIPE
FOR POTABLE WATER SYSTEMS CONSTITUTE
A HEALTH HAZARD?
A Committee Report
by
MARVIN KUSCHNER, M.D. ROGER LEE GORDON G. ROBECK JOHN R. ROSSUM MARVIN A. SCHNEIDERMAN, PH.D. E. WINDLE TAYLOR, C.B.E., M.A., M.D.,
D.P.H., F.R.C. PATH. GEORGE W. WRIGHT, M.D. (CHAIRMAN)
Prepared for
The American Water Works Association Research Foundation
6666 W. Quincy Avenue Denver, Colorado 80235
4 ASBESTOS IN WATER
JOURNAL AWWA
CAPCO JEN 0020277
Summary
Does the use of asbestos-cement pipe for potable water systems constitute a health hazard?
This question has been raised because of the possibility that asbestos fibers might be released by mechanical action during construction or subsequent tapping of the system, or by ero sion or by leaching and thus be ingested directly or indirectly through water drunk or through food prepared from water flowing through such systems. Asbestos-cement pipe has been in use for potable water systems for 50 years in Europe and almost 40 years in the United States of America without overt evidence that it poses a hazard to health. Populations using these systems have not been studied with techniques adequate to reveal small differences of health experience when compared to populations using other water distribution systems. Moreover, the lag time for biological effects such as cancer may be longer than the period spanned by the use of asbestos-cement pipe. For these reasons, a direct evaluation of the question on epidemiologic grounds is not possible at this time. Nevertheless, it is possible to consider the matter in a useful way by exploration of the following questions:
A. Is there valid evidence that ingested asbestos is harmful? Asbestos can cause granulomatous and fibrotic reactions in the lungs but there is no evidence that it does so in the gastrointestinal tract. There is sufficient evidence to support the presumption that occupational exposure to asbestos poses an unusual risk of developing gastro-intestinal cancer. This is assumed to be caused by the asbestos ingested as a result of occupational exposure. An excess occurrence of peritoneal mesothelioma has been reported in most occupational groups exposed to airborne asbestos. Although it may be so, it is not certain that this is caused by ingested asbestos.
B. What is known about the determinants of the biological effects of ingesting asbestos?
There is evidence that whatever gastro-intestinal car cinogenic effect is demonstrable, it is related to dose but is not related to variety of fiber, and whether or not it is related to fiber size is unknown. If ingested asbestos plays a role in the development of mesothelioma of the peritoneum it can be ex pected to be dose related and probably related to the dose of those fibers longer than ten micrometers and thinner than three micrometers. It is unlikely to be related to the chemical make-up of the different varieties of fiber.
C. What is the evidence that asbestos is releasedfrom asbestoscement pipe by mechanical handling during installation, tapping for new users, or by erosion or by leaching as waterflows through the system? Ifthis does occur, what are the amounts ofthe released fiber, its size and pattern of build-up or persistence?
The general prevalence of asbestos in soil results in its pres ence in most waters of lake, river, and well origin, and in dis tribution systems whether fabricated of asbestos-cement or other materials. Additional asbestos fibers may be con tributed to the water flow through transfer from the asbestoscement pipe wall or deposit in the pipe during construction or repair of the distribution system. At present the available data are inadequate to describe the quantitative or qualitative con tribution made by asbestos-cement pipe alone with respect to the amount, size, and persistence of the asbestos fibers found in potable water distribution systems.
D. If there is evidence to indicate that ingested asbestos is harmful, what inferences can be drawn from the circumstances of such exposure that are applicable or meaningful with respect to the
SEPTEMBER 1974
exposure that might be experienced due to the domestic use of asbestos<ement pipe?
The total amount of asbestos ingested by occupational groups spans a range that, even at its lowest level,, is many times that which is likely to be experienced by the public use of water from asbestos-cement pipe systems. Since the oc cupational risk of excess gastro-intestinal cancer is dose-re lated, the slight or perhaps no risk posed by low level occupa tional exposure makes it even less likely that the exposure from ingestion of public water would pose a gastro-intestinal cancer hazard.
Asbestos-cement pipe systems have serviced large popula tions for 40 or more years in Europe and the United States. No apparent increase in peritoneal mesotheliomas among the public has occurred during this period despite the fact that this tumor has been the focus of great interest among pathol ogists for the past ten years.
Asbestos fibers shorter than 20 micrometers in length ap pear to have little or no capacity to induce mesotheliomata in experimental animals. To the degree that fibers longer than this are absent or scant in the water of asbestos-cement pipe systems the likelihood that such systems would pose a mesothelioma risk would be small.
No firm evidence shows that the proper use of asbestos-ce ment pipe poses a hazard to health by reason of ingestion of asbestos fibers. Calculations comparing the probable inges tion exposure in occupational groups to that likely to occur as a result of ingestion of potable water from asbestos-cement pipe systems suggests that the probability of risk to health from the use of such systems is small -- approaching zero. A group of scientists at the Lyon Conference on Biological Effects of Asbestos, who looked at the possible hazard posed by asbestos in potable water, reached a similar conclusion. Additional evidence, currently not available, to show more directly that the use of asbestos-cement pipe is without risk, is desirable. Appendix F lists proposed areas of research directed toward achieving that goal.
Recommendations
Of primary importance is the development of a standard analytical procedure to identify and quantify asbestos fibers by type and size as they actually exist in water. This ability is essential for the equally important study of pipe systems of various materials to determine the effect of the asbestos con tent of the soil in which the pipes are laid and the effect of the pipe itself (asbestos-cement) upon the asbestos content of the water traversing the system.
In addition, necessary research should include epidemio logical studies of human population groups exposed to asbestos-cement pipe systems, and animal studies to examine the health aspects of asbestos fiber and to explore possible carcinogenic effects.
Appendix F provides a more detailed list of suggested research projects.
Committee Report
Introduction. The question we have been asked is: Does the use of asbestos-cement pipe for potable water systems con stitute a health hazard?
This question has been raised because of the possibility that asbestos fibers might be released by mechanical action during construction or subsequent tapping of the system, or by ero sion, or by leaching, and thus be ingested directly or indirectly by water drunk, or through food prepared from water flowing
COMMITTEE REPORT 5
CAPCO JEN 0020278
through such systems.* Asbestos-cement pipe has been in use Jor potable water systems for 50 years in Europe and almost 40 years in the United States of America without overt evidence that it poses a hazard to health. Populations using these systems have not been studied with techniques ade quate to reveal small differences of health experience when compared to populations using other water distribution systems. Moreover, the lag time for biological effects such as cancer may be longer than the period spanned by the use of asbestos-cement pipe. For these reasons, a direct evaluation of the question on epidemiologic grounds is not possible at this time. Nevertheless, it is possible to consider the matter in a useful way by exploration of the following questions:
A. Is there valid evidence that ingested asbestos is harmful?
B. What is known about the determinants of the biological effects of ingesting asbestos?
C. What is the evidence that asbestos is released from asbestos-cement pipe by mechanical handling during installa tion, tapping for new users, by erosion, or by leaching as water flows through the system? If this does occur, what amounts of fiber are released and what is their size and pat tern of build-up or persistence?
D. If the evidence indicates that ingested asbestos is harmful, what inferences can be drawn from the circum stances of such exposure that are applicable or meaningful with respect to the exposure that might be experienced due to the domestic use of asbestos-cement pipe? A. Is there valid evidence that ingested asbestos is harmful?
Data relating human exposure to asbestos in the environ ment to subsequent health effects are limited to occupational and para-occupational exposure. Such exposures constitute a combination of inhalation and ingestion, since the bulk of the fibers deposited in the regions distal to the pharynx by inhala tion are cleared from the lungs by being brought up into the back of the throat via the mucous removing apparatus and then swallowed or expectorated. In addition, those fibers deposited in the back of the nose and the pharynx are likewise cleared into the throat and then swallowed or expectorated. Moreover, for most occupationally exposed groups, facilities for eating and washing were not always available, and direct contamination of food consumed on the job was common. Although quantitative aspects of exposure via the ingestion route in man have not been examined, on the basis of studies of pulmonary clearance of particles it is undoubtedly substan tial.
Asbestos can cause granulomatous and fibrotic reactions in the lungs, but there is no evidence that it does so in the gastro-intestinal tract. Therefore this manifestation was not further considered. An excess occurrence of cancer of the lung, pleura and peritoneum, and also the gastro-intestinal tract, has been reported in association with occupational and para-occupational exposure of humans to asbestos. Since it is logical to believe that of these manifestations an excess of gastro-intestinal and peritoneal cancer might be associated with asbestos entering the body via the route of ingestion, these two classes of cancer were considered.
Several recent reports have shown a higher incidence of tumors of the gastro-intestinal tract in populations exposed occupationally to asbestos than in a comparable age group of the general public not thus exposed.1-2-3 Another study, com-
While the use of ubestos-cement pipe for tewije or other witer systems might tlso be considered, it seems logics! to believe thst such systems would htve s lesser tnd more in direct effect snd thst consideration should first be directed to potable water systems.
6 ASBESTOS IN WATER
paring an occupational group heavily exposed to asbestos to several groups who had experienced lesser exposure in the same occupation, has shown a gastro-intestinal tumor inci dence in the most heavily exposed double that of the lesser exposed.4-5 In none ' these studies has the author concluded that the data establish unequivocally that employment in asbestos-producing or -using occupations poses a higher than usual risk of developing gastro-intestinal cancer. Neverthe less, the data, when taken in aggregate, appear to establish the presumption that such a relationship does exist. In each of these occupational groups the exposure has been by both in halation and ingestion, but it would appear reasonable to assume that whatever effect on gastro-intestinal cancer rate exists, it is due to ingestion, since the ingested fibers would have direct access to the cells lining the gastro-intestinal system.
An excess occurrence of peritoneal (abdominal) meso thelioma has been reported in several groups occupationally and para-occupationally exposed to combined inhalation and ingestion of asbestos.3-5-6-7-8-9-10 In contrast to the gastro-in testinal cancers where the ingested fibers come into direct and immediate contact with the inner surface of the gut wall, the route of access of fibers to the mesothelial cells of the peritoneum is not clearly understood. Channels through which fibers could go from the lung to the peritoneum with out entering the gastro-intestinal tract do exist. Moreover, the intestinal wall may provide a barrier to the migration ofasbestos fibers of critical size from the lumen of the gut to the mesothelial cells covering the outer surface of the gastro-in testinal tract. For these reasons, the excess of peritoneal mesotheliomas is less clearly the result of ingestion, and may be the result solely of inhalation.
B. What is known about the determinants of the effects ofingested
asbestos? The biological effect of virtually every agent is related to its
specific nature, dose, and host sensitivity or reactivity. Data relating the effects of asbestos to host sensitivity or reactivity are scant and not applicable to the question being considered. Some data are available relating the dose and specific nature of the fibers to the biological effects of asbestos. With respect to the specific nature of asbestos fibers, one should note that the varieties of asbestos have different chemical composittions and shapes. Some varieties have more iron and less mag nesium than others, and some have straight, stiff fibers in contrast to others that are more flexible and curved or curly. Moreover, the airborne dust to which humans are exposed contains asbestos fibers that vary in length from hundreds to less than one micrometer, and in diameter from ten or more to 0.04 micrometers.
Studies that have examined the relationship between the intensity and duration of occupational exposure to asbestos and the incidence of gastro-intestinal cancer have revealed data that can be interpreted as demonstrating a dose effect, the risk decreasing with diminishing dose.1-5 Also see Appen dix E. There are data1 showing a greater risk of both lung and gastro-intestinal cancer in maintenance than in production workers even though their total exposures were thought to be similar. Among several other possible explanations for this observation, the greater likelihood of high intermittent ex posure of maintenance workers may have played a role. Ap proximately the same order of excess of gastro-intestinal can cer has been reported in those occupations where chrysotile, amosite, or a mixture of chrysotile and crocidolite, have been used.1-2-5-11 Thus, there does not appear to be an effect related
JOURNAL AWWA
CAPCO JEN 0020279
to different chemical compositions or shapes of fibers. Air borne asbestos in all occupational and para-occupational ex posures contains fibers of ail sizes as to diameter and length. This make'' it impossible to study the effect of various sizes of fiber by human epidemiology. Feeding experiments with animals using asbestos fibers of mixed lengths and diameters have not produced a gastro-intestinal carcinogenic response.12-13-14-15-16 Thus, no animal experiments have been conducted thus far to examine the effects of various sizes of fiber on gastro-intestinal carcinogenesis.
To summarize, there is evidence that whatever gastro-in testinal carcinogenic effect is demonstrable, it is related to dose and perhaps to pattern of dose, but is not related to variety of fiber used in asbestos-cement pipe. Whether or not it is related to fiber size is unknown.
With respect to mesothelioma, the only studies relating dose or severity of occupational exposure to occurrence of mesothelioma are those of Newhouse. They show a dose rela tionship with the risk lessening as the dose decreases.8-21 Animal experiments support the dose relationship pre mise.22-23 Unfortunately, the studies by Newhouse do not ex press exposure in numerical terms. Available evidence also suggests that an excess of mesothelioma occurs in occupa tionally exposed groups at doses below those that produce pulmonary fibrosis and probably below that necessary to cause an excess of bronchogenic cancer.3-5-8-10 Evidence of an excess of mesothelioma resulting from para-occupational ex posure has been presented with the assumption that in some instances these exposures have been extremely slight. The numerical intensity of exposure in these non-occupational cases has not been demonstrated. However, on the basis of available information, it appears that many of these exposures have been substantial, though perhaps brief.10-11-17-18-20 It is difficult to evaluate the validity of a cause-and-effect relation ship between casual and presumably slight exposures of the general public to inhaled asbestos and the development of mesothelioma. Such a relationship has been sought by look ing for exposure to asbestos in the life experience of cases of mesothelioma collected from hospital or non-occupationally derived records.6-7-9-10-19 In view of the wide-spread use of asbestos, or asbestos-containing products, now and during the past 50 years, frequent slight exposure of the general public must be common. The importance of these casual exposures should be evaluated with caution.
The two asbestos components of asbestos-cement pipe, chrysotile and crocidolite, have been shown to be associated with excess development of peritoneal mesothelioma. The ex perience in pure chrysotile exposure appears to be less severe than that of mixed varieties.4-18 Unfortunately, there are no numerical dose data for the latter exposures. Therefore, it is unsafe to conclude that this difference is a true varietal effect in terms of chemical or physical character. Both varieties of asbestos produce tumors of the pleura in the experimental animal model.
Since humans are exposed to all sizes of asbestos fiber, it is not possible to examine the effect of varying fiber size by human epidemiologic studies. Several investigators have pro duced cancer of the pleura by introducing asbestos, glass, or aluminum-oxide fibers directly into the pleura or peritoneal space of experimental animals. Some disagreement exists as to whether these tumors are the specific counterpart of meso thelioma in humans. Chrysotile, amosite, and crocidolite, as well as glass and aluminum-oxide fibers will produce these experimental tumors. This suggests that the tumorogenic
SEPTEMBER 1974
effect is not related specifically to the chemical composition of the fibers.22-24-25 These animal studies have indicated a striking effect of size of fiber on this type of carcinogenesis. One can conclude from such studies that fibers thinner than three and longer than 20 micrometers are more carcinogenic than fibers of greater diameter, irrespective of length, or those shorter than 20 micrometers, irrespective of diameter.26 Whether these findings are applicable to the effects of ingested asbestos has not been demonstrated by animal experimentation, but they do suggest that if ingestion of asbestos plays a role in the development of peritoneal mesothelioma, it might be ex pected that the size of the fibers capable of penetrating the gut wall and reaching the mesothelial cells would be of impor tance.
To summarize, if ingested asbestos plays a role in the devel opment of mesothelioma of the peritoneum, it can be ex pected to be dose related, and, on a conservative basis; proba bly related to the dose of those fibers longer than'ten micro meters and thinner than three micrometers. It is unlikely to be related to the chemical make-up of the different varieties of fibers. C. Is asbestos released from asbestos<ement pipe during proper
use? Ifit is, what are the amounts and sizes of the fibers and what
are the patterns of build-up and persistence? Answers to these questions are dependent on methods for
collecting samples, identifying the specific variety of asbestos in the pipe as distinct from other kinds of co-existing fibers, and measuring the asbestos fiber size and amount without altering the original state of the fibers. This task, even on a research basis, is extremely difficult and has been ac complished only in some respects to date (see Appendix B). There are no data delineating temporal variations such as might result from repair or tapping of new lines or services.
There are scant quantitative data for chrysotile asbestos in water expressed in micrograms per unit of volume. Fibers identified as asbestos are found in the primary water source (lake, river or well) of most systems thus far examined. See Appendix D-1,3. This is not surprising in view of the ubiquity of asbestos of one or another variety in the soil of the United States through which source waters flow, or in which they lie; and the consequent opportunity for leaching of fibers from the soil into these waters. Appendix C shows the distribution of asbestos on or close to the surface throughout the United States. There is also the opportunity for some of the asbestos fibers freed into the atmosphere by wind erosion, by earth disturbance, and by escape of fibers from the use of commer cial articles containing asbestos to be washed by surfacewater drainage into the primary sources. Thus, one can antici pate that appreciable amounts of asbestos fiber exist in the water as it enters the distribution system.
It is necessary to determine the amount of asbestos in pot able water and the increment added by the distribution system. It is also necessary to know whether an observed in crement is caused by fibers being removed from asbestos-ce ment pipe, or by contamination from the soil surrounding the pipe, or left in the pipe during construction or repair of the system. Limited studies of water circulated through a closed loop of asbestos-cement pipe, not buried in the soil, reveal that asbestos fibers can be transferred from the pipe wall to the water. See Appendix D-2. The mechanisms governing this release and its persistence have not been established.
Three asbestos-cement pipe systems in use for a substantial period of time have been sampled for their asbestos fiber con tent. The data on asbestos content of the water from the
COMMITTEE REPORT 7
system reported by Sargent were obtained by examining the samples with a light microscope only.27 Subsequent examina tion of these samples using the electron microscope, which permits recognition of chrysotile asbestos, revealed that a large proportion of the fibers originally reported as being asbestos were in fact not.28 This experience exemplifies the difficulties inherent in measuring the asbestos content of water.
The other two asbestos-cement pipe systems were analyzed by a technique (See Appendix B and D) permitting electron microscope recognition and quantification of chrysotile asbestos. In one of these the source and pipe system lay in serpentine soil. Preliminary data place the quantity of asbestos in tap water in this system at 0.119 microgram per liter. The source water contained 0.045 microgram per liter. The increment amounted to 0.074 microgram per liter.
In the second system the well and asbestos-cement pipe lay in soil comparatively free from serpentine rock. The tap water contained 0.01 microgram per liter and the source water 0.0061. The increment amounted to 0.0040 microgram per liter.
Several points should be made with regard to these studies. Appendix B indicates the major difficulties posed by the methodology used. The quantitative aspects are expressed for chrysotile only. Chrysotile usually comprises 80% or more of the asbestos used in asbestos-cement pipe. The confidence limits with present techniques at these minute amounts may be as much as one order of magnitude. Since the original size of the fibers is altered by the "rub-out technique" we have no knowledge of the amount of fiber in the water as it is ingested by humans according to length and diameter.
Multiple high-volume sampling also creates some diffi culties, and good data with respect to the effect of length of pipe traversed, velocity of flow, and temporal effects do not exist. Nevertheless, these studies afford a preliminary esti mate of the likely exposure by way of ingestion of tap water for comparison with the exposure by ingestion experienced by occupational groups. They do not provide information on the amount of fibers of various sizes. One should also note that if it could be established that the make-up of the pipe, the aggressiveness of the water, and factors such as velocity of flow and age of pipe were essentially the same in the two systems examined, then other explanations for the difference in asbestos content of the water must be found. Serpentine soil contains asbestos fibers. Particles of such soil entering the pipe during construction, especially those lodging in the cre vices of joints, could slowly and over a long period of time contaminate the water. At present there are not adequate data for a description of the quantitative or qualitative role of asbestos-cement pipe as a contributor to asbestos fiber found in potable water distribution systems. However, the available data do indicate what additional studies need to be made and also afford a first approximation of the magnitude of the possi ble health hazard. D. Ifthe evidence indicates that ingested asbestos is harmful, what
inferences can be drawn from the circumstances ofsuch exposure
that are applicable or meaningful with respect to the exposure that
might be experienced due to the domestic use of asbestos-cement
pipe? With respect to an excess of gastro-intestinal cancer, such
evidence as there is does not suggest that the variety of asbestos plays a role and thus the kinds of asbestos used in asbestos-cement pipe might be implicated. There is no evi dence in man or animals about the influence of the size of
8 ASBESTOS IN WATER
fibers ingested on the development of gastro-intestinal car
cinogenesis. Hence, until additional information is available,
it must be assumed that the size of fibers existing in potable
water could play a role.
-
Evidence derived from occupational groups indicates a
direct dose relationship between environmental exposure and
the risk of excess gastro-intestinal cancer. The amount in
gested can be expected to be di/ectly related to the environ
mental exposure. The amount of asbestos in water delivered
through asbestos-cement pipe and other pipe systems is ex
pressed in terms of micrograms per liter. Using this kind of
data, one can compare the quantity of asbestos likely to be in
gested from water to those ingested by the occupationally-ex
posed populations experiencing an excess of gastro-intestinal
cancer, thus placing these two categories of populations in
perspective.
As shown in Appendix A, one can calculate the approxi
mate amounts of asbestos ingested by the occupationally-ex
posed populations of the two groups where an excess of
gastro-intestinal cancer and exposure data have been re
ported. In the McDonald group this ranged from 2.1 to 168.0
grams, and in the Enterline group from 42 to 336 grams dur
ing the working lifetime of the men studied. For comparison,
based upon a water consumption of two liters per day, one can
calculate that the total amount ingested in 60 years from the
water system with the highest concentration of fibers would
be 0.07 gram (See Appendix D-3, Memphis, not asbestos-ce
ment pipe, filtered). The higher of the two asbestos-cement
pipe systems studied (See Appendix D,Malvern) would pro
vide a total of 0.005 gram ingested in 60 years. That the
amount of asbestos ingested from asbestos-cement pipe sys
tems over a 60-year period would approach the least of the oc
cupational exposures is unlikely. Moreover, the dose response
observed in the occupationally-exposed populations suggests
that at the lower levels of exposure there was slight or perhaps
no risk of excess gastro-intestinal cancer.1'4-5- Also seeAppen-
dix E. Thus, there appears to be even less probability that the
ingestion of asbestos from the higher of the two potable
asbestos-cement pipe systems would reach the risk level for
gastro-intestinal cancer of the occupationally-exposed groups.
With respect to mesothelioma of the peritoneum, the oc
cupational and para-occupational exposure is by both inhala
tion and ingestion. Neither route provides direct exposure of
the target cells. The fibers reaching the pleura or peritoneum
do so by indirect routes. It is possible, therefore, that
peritoneal mesothelioma is not caused by ingestion of fibers
and thus not a matter for our consideration. Both chrysotile
and crocidolite are associated with an excess of peritoneal
mesothelioma in occupationally-exposed populations. Hence,
fibers released from asbestos-cement pipe would have this
potential. Mesothelioma is dose related in occupational ex
posures and also the animal model. There are no numerical
data defining the hazardous level of this dose relationship in
humans. As Appendix A shows, the range of exposure by in
gestion in those occupationally exposed is higher than that
which is apt to be provided by potable water. Since animal
studies indicate that the longer fibers are the potent initiators
of mesothelioma, the dose should be looked at in terms of
categories as to length of fibers in potable water. We do not
know the proportion of long to short fibers in their natural
state in potable water and therefore cannot make the desired
comparison at this time. If all or most of the fibers released by
asbestos-cement pipe are less than ten micrometers long, es
pecially if the quantity of those that are longer is small, the
JOURNAL AWWA
CAPCO JEN 0020281
likelihood that asbestos-cement pipe poses a mesothelioma risk would be small. As stated at the outset, asbestos-cement pipe systems have serviced large populations for 40 or more years in Europe and the United States. No apparent increase in peritoneal mesotheliomas among the public has occurred during this period despite the fact that this tumor has been the focus of great interest among pathologists for the past ten years.
Conclusions. No firm evidence shows that the proper use of asbestos-cement pipe poses a hazard to health by reason of in gestion of asbestos fibers. Calculations comparing the proba ble ingestion exposure in occupational groups to that likely to occur as a result of ingestion of potable water from asbestoscement pipe systems suggests that the probability of risk to_ health from the use of such systems is small - approaching zero. A group of scientists at the Lyon Conference on Biologi cal Effects of Asbestos, who looked at the possible hazard posed by asbestos in potable water, reached a similar conclu sion.32 Additional evidence, currently not available, to show more directly that the use of asbestos-cement pipe is without risk, is desirable. Appendix F lists proposed areas of research directed toward achieving that goal. Most will require several years time and the commitment of substantial money and manpower. Some require techniques not currently developed.
References
1. Enterline, P., et al. Mortality in Relation to Occupational Ex posure in the Asbestos Industry. Jour. Occupational Med., 14:12:897 (Dec. 1972).
2. Elmes, P. C. & Simpson, M. G. Insulation Workers in Belfast. 3. Mortality 1940-66. Brit. Jour. Indi. Med., 28:226 (1971).
3. Selikoff, I. J., et al. Cancer Risk of Insulation Workers in the United States, Paper No. 35. Conf. on the Biol. Effects of Asbestos, Inti. Agency for Res. on Cancer, Lyon, France (Oct. 1972).
4. McDonald, J. C., et al. Mortality in the Chrysotile Asbestos Mines and Mills of Quebec. Arch. Environ. Health, 22:677 (1971).
5. McDonald, J. C. Cancer in Chrysotile Mines and Mills, Paper No. 29. Conf. on the Biol. Effects of Asbestos, Inti. Agency for Res. on Cancer, Lyon, France (Oct. 1972).
6. Webster, I. Malignancy in Relation to Crocidolite and Amosite, Paper No. 30. Conf. on the Biol. Effects of Asbestos, Inti. Agency for Res. on Cancer, Lyon, France (Oct. 1972).
7. Webster, I. Asbestos artd Malignancy. South African Med. Jour., 47:165 (1973).
8. Newhouse, M. L. Cancer Among Workers in the Asbestos Textile Industry, Paper No. 32. Conf. on the Biol. Effects of Asbestos, Inti. Agency for Res. on Cancer, Lyon, France (Oct. 1972).
9. McDonald, A. & McDonald, J. C. Epidemiologic Surveillance of
Mesothelioma in Canada. CMA Jour., 109:359 (1973).
10. Wagner, J. C., et al. Epidemiology of Asbestos Cancers. Brit.
Med. Bull., 19:71 (1971).
11. Selikoff, I. J., et al. Carcinogenicity of Amosite Asbestos. Arch.
Environ. Health, 25:183 (1972).
^
12. Smith, W. E. L., et al. Tests for Carcinogenicity of Asbestos, Ann.
N.Y. Acad. Sci., 132:456 (1965).
13. Smith, W. E. Asbestos, Talc and Nitrites in Relation to Gastric
Cancer. Amer, Indi. Hyg. Assoc. Jour., 34:227 (1973).
14. Bonser, G. M. & Clayson, D. B. Feeding of Blue Asbestos to
Rats, 45th Ann. Rprt., Brit. Empire Cancer Campaign for
Res.-1967.U968) p.242.
15. Swinburne, L. M. The Ingestion of Asbestos by Rats. Personal
communication to Bu. ofFood, FDA. Reported in the Fed. Rgtr.,
38:188:27077 (Sep. 1973).
16. Gross, P. Personal communications to J. F. Knox and G. W.
Wright
17. Wright, G. W. Personal observations of environmental.condi-
tions in paraoccupational exposures.
18. Gilson, J. C. Asbestos Cancer: Past and Future Hazards. Proc.
Roy. Soc. Med., 66:395 (1973).
19. Newhouse, M. L. & Thompson, H. Mesdthelioma of Pleura and
Peritoneum Following Exposure to Asbestos in the London
Area. Brit. Jour. Indi. Med, 22:261 (1965).
20. Wagner, J. C., et al. Diffuse Pleural Mesothelioma and Asbestos
Exposure in the Northwest Cape Province. Brit. Jour. Indi. Medn
17:260(1960).
21. Newhouse, M. L. Asbestos in the Workplace and the Community.
Ann. Occupational Hyg., 16:97 (1973).
22. Wagner, J. C., et al. Mesotheliomata in Rats after Innoculation
with Asbestos and Other Materials. Brit. Jour. Cancer, 28:173
(1973).
23. Smith, W. E., et al. Tests for Threshold Levels ofCarcinogenicity
of Asbestos, Internationale Konferenz ueber die Biologischen
Wirkungen des Asbestos. Dresden, E. Germany (1968) p. 240.
24. Stanton, M. F. & Wrench, C. Mechanisms of Mesothelioma In
duction With Asbestos and Fibrous Glass. Jour. Natl. Cancer Inst.,
48:797 (1972).
25. Stanton, M. F. Some Aetiologic Considerations of Fiber Car
cinogenesis, Paper No. 43A. Conf. on the Biol. Effects of
Asbestos, Inti. Agency for Res. on Cancer, Lyon, France (Oct.
1972).
26. Stanton, M. F. Fiber Carcinogenesis: Is Asbestos the Only
Hazard? editorial. Jour. Natl. Cancer Inst^ 52:633 (1974).
27. Sargent, H. E. Asbestos in Drinking Water. Presented NEWWA
Meeting, Northfield, Vl (May 17, 1973).
28. Robeck, G. G. Personal communication.
29. Lynch, J. R., ET al. The Interrelationship of Selected Asbestos
Exposure Indices. Amer. Ind. Hyg. Assn. Jour., 31:598:604 (1970).
30. Gibbs, G. W. Personal communication.
31. McDonald, J. C. Asbestos in Chrysotile Mines and Mills, Paper
No. 23. Conf. on the Biol. Effects of Asbestos, Inti. Agency for
Res. on Cancer, Lyon, France (Oct. 1972).
32. Report of the advisory committee on asbestos cancers to the Inti.
Agency for Res. on Cancer. Ann. Occupational Hyg., 16:9 (1973).
SEPTEMBER 1974
COMMITTEE REPORT 9
CAPCO JEN 0020282
Appendix A
The approximote amount of fiber ingested by reason of in halation in occupational settings can be estimated retro spectively if the intensity and duration ofairborne exposure is known. The occupational group reported by McDonald et al. had an airborne exposure spanning the range of 10 to 800 million particles per cubic foot (mppcf) years.4,5 Assuming a duration of exposure of 40 years for a person acquiring a total of ten mppcf years, his exposure would have been to an en vironment containing 0.24 mppcf each day. McDonald esti mates that in the general exposures of his study population one mppcf of airborne dust was equivalent to two asbestos fibers per cubic centimeter (cc) large enough to be seen by the light microscope.51 Thus, the exposure at ten mppcf years was 0.5 fiber per cc for 40 years. It is reasonable to estimate that during work in the occupations of his study group, the respiratory volume, averaged during a seven-hour period of work per day, would be at the rate of 16 liters per minute. Doing this seven hours a day, five days a week, 50 weeks a year for 40 years would produce a total inhaled volume of 6.72 x 10locc. If each two cc contained one fiber, this would amount to 3.36 x 10' fibers being inhaled in 40 years.In oc cupational circumstances the fibers that are counted by the light microscope can be estimated to average 1 x 20 micrometers. Based on the weight of this size of fiber, it is estimated that 1.35 grams of asbestos fiber would be inhaled as the equivalent of an exposure of ten mppcf years. Further, estimating that 80% of this size of fiber is deposited and subsequently cleared from the respiratory system to be swallowed, a total of 1.1 grams might be ingested at this level of exposure.
Lynch has shown that in manufacturing operations there are 25 to 100 times as many thin fibers requiring the electron mi croscope for recognition as there are of those large enough to
be seen by the light microscope.29 Gibbs reports similar cir cumstances for the type ofexposure reported by McDonald et al. Using the lower value of 25, and assuming a-fiber of 0.5 x 5.0 micrometers, a lung deposition of 50% of this size fiber, and clearance with subsequent swallowing of 90%, calculations show that the ingestion by this occupational group at the ten mppcf level was an additional 1.0 gram of asbestos fiber. Thus, a total of 2.1 grams of asbestos would be ingested at this level of exposure.
Since the group under study by McDonald et al covered an exposure range of 10 to 800 mppcf years, the range of inges tion during their working life was approximately 2.1 to 168 grams of asbestos of all sizes, and 1 to 80 grams for the size of fiber measuring 0.5 x 5.0 micrometers.
Based on Lynch's studies, the group examined by Enterline can be expected to have had a fiber to particle ratio of be tween two and six fibers per cc for each one mppcf. Choosing four fibers per cc for the conversion ratio, and using the same calculations as above for McDonald's study group, the num bers are simply doubled in order to arrive at the ingestion ex posure for the Enterline group. The range of exposure for this group was 100 to 800 mppcf years. Therefore, the ingestionexposure for the Enterline group ranged between 42 and 336 grams for both the light-microscope and electron-microscope sizes of asbestos fiber over the 40-year period of work, and from 20 to 160 grams for the fibers 0.5 x 5.0 micrometers which would be seen only by using an electron microscope.
A precise estimate of the ingestion exposure is not possible in these retrospective studies. The estimates arrived at are meant only to provide a frame of reference for comparison of the occupational exposure to that which might occur in the general public by reason of ingestion from potable water sup plies.
10 ASBESTOS IN WATER
JOURNAL AWWA
CAPCO JEN 0020283
Appendix B
The determination of the asbestos fiber concentration in water supplies is a very difficult task. Some of the reasons for this are:
1. The concentration of asbestos fiber in water is generally very low, i.e. in the parts-per-billion range.
2. There is no convenient chemical method which can be considered because the elements present in all forms of asbestos fiber are common to all rock-forming minerals.
3. There are no reliable methods to concentrate or separate the asbestos fiber from the other inorganic solids present in the water.
4. The size of the fiber is, in most instances, below the limits of resolution of the optical microscope.
Faced with these limitations, the analyst must resort to electron microscopic techniques for the identification and quantification of the asbestos fiber in water.
The exact details of the electron microscopic methods which are used for the analysis of asbestos fiber will depend to a great extent on the nature of the information desired. Basi cally there are three major steps involved:
1. Removal of the solids from the water by filtration on a membrane filter.
2. Transfer of the captured solids to a suitable mount for ex amination with the electron microscope.
3. Examination of the sample, including counting and measuring the asbestos fibers which are found.
The majority of information which has been obtained on the asbestos-fiber content of waters was gathered by a meth od designed to determine the mass (or weight) of chrysotile present. This method was developed to ascertain the levels of chrysotile fibers in source waters, and also to obtain informa tion on the possible addition of fiber by asbestos-cement pipe. In somewhat more detail, this method involves a considerable degree of mechanical work on the sample prior to examina tion by the electron microscope.
After the suspended solids are collected on the membrane filter, the entire sample is ashed (at 400 C) to destroy the filter and any organic solids present in the water. An aliquot of the ashed inorganic solids is then rubbed out, or ground, in a dilute solution of nitrocellulose. This latter step reduces the size of the particles of residue which might hide extremely small asbestos fibers. The final result is an even dispersion of the inorganic residue in a film which is suitable for transfer to a standard electron-microscope grid.
The sample is examined under the electron microscope, and photographs taken of representative areas. Under these conditions it is possible to recognize chrysotile fibers by their characteristic hollow-tube structure. Quantification is ac complished by measuring the length and diameter of each fiber, calculating the total mass, and finally relating this mass to the original amount of water sampled.
This technique, which many investigators agree is the best available for the purpose, has several shortcomings. First, because of the extremely small fraction of the sample which can be examined under the electron microscope, and because of the small amounts of asbestos present, the accuracy and precision of the analysis is very poor. Under the best condi
tions duplicate determinations on the same sample cannot be reproduced by better than a factor of three. Although there are insufficient data available to estimate the accuracy, most agree that the true value is at least within a factor of ten of the measured value. From these values, it is obvious that the re ported values can only be used as an index of the relative amount of fiber present, and no great significance should be placed on small differences.
A second limitation of this method is the destruction of the original form of the fibers by the rub-out procedure. There is increasing pressure from medical and biological researchers to have information on the exact size and shape of the fibers as they may be ingested. It is necessary, therefore, that meth ods be devised to obtain this information.
Finally, the method is specific for chrysotile and cannot be used for the determination of amphibofe fibers. This point is important since many varieties of asbestiform minerals can occur in water, and crocidolite is a common ingredient of asbestos-cement pipe.
There are several possible variations of the above technique which might be used to obtain information about the original size and shape of the fibers, and the various types of fiber present. With the transmission electron microscope, it is possible to identify a mineral variety by means of selected area electron diffraction. This method is also limited in that it cannot be used reliably to distinguish between the different types of amphiboles, i.e., crocidolite, amosite, anthophyllite, etc. Thus, one can only be certain that an amphibole mineral is present.
In order to obtain more information about the variety of amphibole fiber, it is necessary to use an electron-probe ap proach to determine the chemical composition of each fiber in question. This type of analysis can be accomplished in a scan ning-electron microscope with the proper accessories, or in the more sophisticated transmission-electron microscope now available, e.g. EMMA IV. These techniques require more time per sample and more sophisticated instrumentation, and are, therefore, much more expensive.
In order to obtain the desired information on the original size and shape of the fibers, it is necessary to explore new sample preparation techniques. Obviously, the technique can not involve any excessive amount of physical work in the sample. The most promising approach appears to be the direct-transfer method. In this method the solids are collected on a membrane filter. Using a special extraction apparatus, it is then possible to dissolve the filter and deposit the residue on a carbon-coated electron-microscope grid. The sample can then be examined by either transmission or scanning electron microscopy and the actual dimensions of the fibers deter mined along with the other essential information. This meth od might suffer from even poorer precision and accuracy than the rub-out technique, but it will yield the information most
urgently needed. Finally, it should be pointed out that the various modifica
tions of the analytical method which have been discussed are only now being explored in various laboratories. Although they do show considerable promise, more work is required to establish their validity and applicability to this problem.
SEPTEMBER 1974
COMMITTEE REPORT 11
CAPCO JEN 0020284
Appendix C
aoto. .n*c<kaCnoio>.rO
<0 W
-- !c
CO -
So
wt og
31 sJ?
11
(o0 <50 fl
.52.<0
*; 0>. to
o o
V)
!
2-o r<~0 3O
o5:
CO
kco.
~cwo
o5 5w2 _*>=
IS * C o x ;C cO ^c CO. .c ^. jdw
e nn }+ u
1 2 ASBESTOS IN WATER
JOURNAL AWWA
CAPCO JEN 0020285
Appendix D-1*
Introduction
This project was conducted to investigate the removal of chrysotile fiber from the inner walls of asbestos cement pipe by potable water in municipal water systems. Two municipal systems were selected: Malvern, Pennsylvania and Glendale, Arizona. Both systems utilize well water sources. The Malvern well is drilled in a serpentine rock belt (known to contain chrysotile fiber intermixed with the rock), while the Glendale system is outside any serpentine-bearing area.
Experimental Pertinent features of the two municipal systems and water
properties are given in Table 3 of Appendix D-l-2. Sampling was conducted at the well site and at a location down-line, re ferred to as the domestic site. The objective was to obtain weekly samples at both sites in both systems; however, man power and equipment problems caused occasional sampling interruptions. Sampling was initiated at Glendale during Sep tember 1969 and continued through December 1970. Sam pling at the Malvern well site was initiated in June 1969, but the domestic filtration site was not placed in operation until December 1969 so that comparative well and domestic site data at Malvern was not available as early as Glendale. The sampling sites were not changed throughout the program, with the exception of the Malvern well site where a new well as drilled on the original site in October 1970.
The sampling equipment and procedures are described in Appendix D-l-1. Sample analysis for fiber content, including ashing, rubout and counting, is described in Report No. E404-37 and 404-67. Analysis was conducted at the J-M Research & Engineering Center.
Analytical results for the Malvern and Glendale municipal water systems are presented in Tables 1 and 2 of Appendix D-l-2. Table 3 of Appendix D-l-2, in tabulating the water properties at the well and outlining the pipe systems, provides a basis for interpreting the fiber level data. These fiber level data were analyzed statistically and the results are outlined below.
There is a greater than 99 per cent probability that the ini tial fiber level (at the well site) is higher at Malvern than at
Glendale. Table 3 of Appendix D-l-2 shows the average of all well site samples for Malvern (0.17 /ig/gal) and for Glendale (0.023 /ig/gal). As stated in the introduction, the Malvern well is drilled in an area of serpentine rock, which contains chrysotile fiber, while the Glendale well is not in such an area. It is, therefore, not unexpected that well water from Malvern contains more fiber.
Statistical analysis of the data yields a 90 per cent probabili ty that there was an increase in fiber level between the well site and the domestic site at both Malvern and Glendale. In addition, it was shown that at both Malvern and Glendale (within each system) there is no significant correlation be tween the initial fiber level and the amount of increase. It thus appears that the water is picking up fiber from the pipe walls, but the amount of pick-up is not significantly influenced by the existing fiber level in the water. Also, this lack of correla tion between initial fiber level and amount of increase indi cates that the fiber quantification procedure can define changes in fiber level unaffected by the initial level.
Table 3 of Appendix D-l-2 shows that the average fiber level increase at Malvern is 0.28 /xg/gal, while at Glendale the average increase is 0.015 /xg/gal. Statistical analysis yields a 90 per cent probability that Malvern had a greater fiber level in crease between the well site and the domestic site than did Glendale. Among the factors that could influence removal of fiber from pipe by water are the water properties, the length of exposure time of the pipe to the water, the flow rate of the water through the pipe and the pipe surface area exposed per unit volume of water.
Table 3 of Appendix D-l-2 shows that there is not a large difference in pipe area exposed per gallon of water between the Malvern (0.80 sq ft/gal) and Glendale (0.96 sq ft/gal) pipe systems. The flow rate through about 90 per cent of the length of the Glendale system was 54 ft/min., similar to the 48 ft/ min. through the Malvern system. The first 10 per cent of the Glendale system had a flow'rate of 138 ft/min., so that the overall potential for erosion of the pipe was somewhat greater in the Glendale system. The length of exposure time of the pipe to the water could be an influencing factor, but has not been systematically evaluated.
`Abstract from Johns-Mmville Research and Engineering Center Report No. E404*79. SEPTEMBER 1974
COMMITTEE REPORT 13
CAPCO JEN 0020286
Appendix D-1-1
Sampling Municipal Water Systems
Apparatus Description. The filter assembly consists of a top and bottom section. The
bottom section (on four legs) contains a coarse stainless steel mesh and sintered stainlesssteel filter-support disc.The thicker top section is held in place by stainless steel wing-nuts and is fitted with a small bleed valve. The whole assembly is sealed with twoO rings. Both top and bottom sections are center-drilled and tapped to receive 1/2-in. pipe.
Apparatus Hook-up. 1. To the top section, connect a 4-in. nipple, an elbow, and
another nipple to which a plastic pipe or hose may be clamped. The plastic pipe is connected to a cut-off valve tap ped into the system.
2. To the bottom section, connect a short nipple, an elbow, and another nipple to connect the water meter. The outflow is run ofT into a convenient drain. (Note -All fittings should be brass or stainless steel. Ribbon dope is used as pipe dope could foul the filters.)
Collacting Sampla
1. Remove the top section of the assembly.
2. On the sinte-d filter-support, lay (a) a Whatman 541 filter paper which nas been cut to size, (b) a 0.8 /xm pore size Millipore filter sheet, and (c) another Whatman 541 filter paper. The filter sheets are all 293 mm diameter.
3. Wet the filter papers from the center outwards, and smooth out the ripples.
4. Replace the top and spin on the wing nuts finger tight.
5. Open the water valve slowly with the bleed valve open. When the test chamber is filled, close the bleed valve.
6. Run approximately 300 -400 gallons through the filter, or until the outflow slows to a trickle.
7. Shut off" the water. Note the initial and final meter read ings, and record volume, data, location, and any other perti nent data or observations.
8. Open the assembly and remove the top Whatman 541 filter paper plus the Millipore filter sheet. Leave the bottom Whatman filter paper in place for the next test. This bottom filter paper is only used to protect the Millipore from possible damage due to direct contact with the sintered metal support.
9. Fold the filter sheets together into a petri dish for ship ment to be analyzed.
Appendix D-1-2
JOHNS-MANVILLE RESEARCH AND ENGINEERING CENTER*
Report No. E404-79
TABLE 1 Fiber Level and Ash Content in Municipal Water Samples from Malvern
Ash Content (mg/gal)
Sample Number
Sampling Date
Well Domestic Site Site
M-18 M-19 M-20 M-21 M-22 M-23 M-24 M`25 M-26 M-27 M-28 M-29 M-30 M-31 M-32 M-33 M-34 M-3S M-36 M-37
M-38" M-39M.40" M-41M-42" M*43"
12/19/69 1/02/70 1/16/70 1/30/70 2/06/7G 2/13/70 2/24/70 3/04/70 3/24/70 4/15/70 5/08/70 7/23/70 8/07/70 8/15/70 8/29/70 9/05/70 9/12/70 9/19/70 10/03/70 10/10/70 10/20/70 10/26/70 11/03/70 11/12/70 12/12/70 12/19/70
1.93 1.84 1.90 2.73 1.98 1.94 6 46 1.62 5.35 1.21 126 1.66 128 1.61 1.16 1.19 121 1.46 0.48 0.29 960 15.80 122 10.40 2.22 164
167
_
--
212
2.06 1.94 5.70 1.78 5.83 1.47 129
116
1.14 7.19
MS us 130
1.35 0.60 022 10.70 1.43 061 865 3.45 1.90
Facsimile of Johns-Manville report. tValues in parentheses 0 indicate a decrease. New well, drilled at the same location.
14 ASBESTOS IN WATER
Fiber Level (^g/ga!)
Well Domestic Site Site Increase!
0.183 0.152 0.083 0.210 0126 0.450 0.593 0014 0.591 0.040 0.022 0.019 0006 0020 0017 0.028 0.173 0.093 0X122 0.001 0208 0202 0 0.473 0017 0.472
0.985
_
0.160 3.700 0803 1.910 0.436 0.684 0233 0261 0230 0.115 0.097 0.084 0.002 0.075 0.161 0.072 0.074 0.013 0.034 0.006 0270 0.032 0258
0802
_
(0.050) 3.474 0253 1217 0.422 0.093 0.193 0239 0.311 0.109 0.077 0067 (0026) (0098) 0.068 0.050 0.073 (0.195) (0.168) 0.006 (0203) 0.015 UM)
JOURNAL AWWA
CAPCO JEN 0020287
JOHNS-MANVILLE RESEARCH AND ENGINEERING CENTER*
Report No. E404-79
TABLE 2 Fiber Level and Ash Content in Municipal Water Samples From Glendale
Ash Content (mg/gal)
Fiber Level (;*g/ga])
Sample Number
G`l G-2 G`3 G-4 G-5 G`6 G-7 G-8 G-9 GOO G-ll G-12 G03 G-I4 G05 GO 6 G07 GO 8 G09 GOO G-21 G-22 G-23 G*24 G-25 G-26 G-27 G-28 G-29 0-30 G-31 G-32 G-33
G-34
G*35
Sampling Date
9/10/69 9/17/69 9/23/69 10/01/69 10/07/69 10/20/69 11/04/69 11/09/69 1/23/70 3/06/70 3/22/70 4/03/70 4/10/70 4/11/70 4/24/70 5/03/70 5/12/70 5/15/70 5/21/70 5/28/70 6/09/70 6/17/70 8/27/70 9/12/70 9/19/70 9/26/70 10/03/70 10/10/70 10/17/70 10/24/70 10/31/70 11/15/70 11/22/70 11/29/70 12/06/70
Well Domestic Well Domestic Site Site Site Site Increaset
0--.13
1.68 0.10
0.0--880
02140 0.0089
0.1--260
0.08
0.67
0.0073
00760
0.0687
0.09
0.06
0.0021
0.0058
0.0037
0.06
0.30
0.0042
00200
00158
0.11
022
0.0046
02850
02804
0.32
020
0.0075
0.0110
0 0035
0.20
0.18
0.0041
0.0600
0.0559
0.58
109
0.0077
00330
0.0253
033
0.32
0.0140
00730
0.0590
1.34 034 0
00020
0.0020
1.49
032
0.0110
0.0280
0.0170
1.72
0.09
0.0930
0.0006
(00924)
0.22
0.18
0.0190
0.0310
0.0120
006
008
0.0003
0.0017
00014
0.07
021
0.0039
0.0041
0.0002
0.09
0.13
0.0300
0.0046
(0.0254)
0.10
0.14
0.0019
0.0013
(0.0006)
008 0.19
1.79 0.25
0.1090 00006
00.00905100
(00140) 0.0004
029
0.79
0.1300
0.1010
(00260)
007
0.43
0.0016
00305
0.0289
3.45
0.51
0.1030
0.0080
(0.0950)
0.26
0.24
0.0520
0.0860
0.0340
024
0.55
0.0110
00380
00270
0.11
041
0.0226
00003
00223
0.14 008 0
0.0001
0.0001
009
009
00007
0.0005
(0.0002)
007
007
0.0008
0.0005
(0 0003)
009
0.06
0.0060
0.0004
(0 0056)
0.07
0.06
00002
00004
0.0002
004 0.09 0
00004
0.0004
0.06 0.07 not not
--
analyzed
analyzed
0.07 0.07
not 0.0118
analyzed
004
0.07
0.0028
00045
0.0017
'Facsimile of Johns-Manville Report. tValues in parentheses 0 indicate a decrease.
SEPTEMBER 1974
TABLE 3 Municipal System Characteristics and Data Summary
Malvern
Glendale*
Pipe System Diamater (in.) Length (ft) Area exposed to water (sq ft) Water volume (low rate (gal/min3 Water linear (low rate (ft/min.) Pipe area exposed (sq ft/gal) Water volume in pipe
Water properties (well site) Total hardness (mg/lCaCOj) Calcium hardness (mg/lCaCOJ Alkalinity (mg/lCaCOJ Dissolved solids (mg/1) pH
Average initial fiber level (jig/gal) (well site)
Average fiber level increase (/ig/gal)
8 2800 5860 125
48 0.80
49 27 110 106
IS
0.17
028
12 6 1300 12,000. 4150 18.700 800 80 138 54 034 1.06
0.96"
94 61 114 328 8.0 0023
0.015
The first 1300 ft ofthe Glendale system utilized I2-in. diameter pipe, followed by 12.000 ft
of 6-in diameter pipe.
"Overall system
.
COMMITTEE REPORT 15
CAPCO JEN 0020288
Appendix D-2*
Introduction
During 1968. a TRANSITE pipe test line was installed in a building situated adjacent to the Research Filtration plant. The purpose of this installation was to determine the amount of asbestos fibers entering a potable water supply after pass ing through TRANSITE water pipe.
Procedure
Originally, the system was constructed for 175 GPM to pass through the installation on a once-through basis. Trial runs revealed that a once-through system was not feasible due to almost immediate plugging of filters. Consequently, the system was converted to a semi-closed recirculating system with a small amount of filtered fresh water continuously en tering the system, and an equal amount of system water dis charged to the sewer, in order to prevent dissolved solids buildup. (See Figure 1 of appendix for schematic and equip ment list). (Refer also to Research Report No. 425-T-1345).
The most critical portion of the test involved two Millipore filters, one before the TRANSITE line and one after the
TRANSITE line. The TRANSITE line was 30 feet of Class 200 RTPP from Waukegan Plant. The pre-TRANSITE filter was a 40 plate Millipore containing 40 sheets (293 mm diameter) of 0.8 micrometer filter paper. Before entering the TRANSITE line, all water passed through this filter. The 0.8 micrometer size was chosen based on chem lab tests showing that 0.8 micrometer filter paper would retain 100 percent of the asbestos. (See Research Report No. 425-Int-1301). After leaving the TRANSITE line, ten percent of the water was sampled by a ten plate Millipore filter also containing 0.8 micrometer filter paper. Thus, all of the asbestos fiber found on this filter can be considered to have come from the pipe wall. Hardness of the water was controlled by a water softener and pH was controlled by a chemical injection pump using dilute sulfuric acid. Water volume was about 150 GPM and flow rate was 6 -8 FPS. A series consisted of a minimum of ten weekly runs at a chosen pH and hardness level. At the end of each weekly run, the ten papers from the sampling Millipore were delivered to the chemistry lab for fiber analysis. A fresh TRANSITE line was installed at the start of each series of runs.
Fiber analysis was originally intended to be based on the
"From Johns-MtnviUe Restirch and Engineering Center, Report No.425-T*136Q. 16 ASBESTOS IN WATER
Fig. 1. Schematic Diagram of Test Line Installation
Inlet water Flowmeter-Fischer & Porter No. 10A3535SY-9.5 GPM max. Inlet Water Filter - Pall Trinity Micro Corp. filter housing No. MCS1002UX16 utilizing two pleatedpaper filter cartridges No. MCYlOOHJXrated for 100percent removal of 0.8 micrometer. Chemical Pump on Inlet Water - Chemcon Pump - Mode! No. L24 "Raider" Diatomite Fitter - BIF Mode! No. 1865-03 vacuum diatomite filter, 240 square feet, flow rate 175 GPM at five psig. Oper ated with leafs removed and no diatomite in system. Pump - Weinman Model 2KB (Centrifugal) capacity 175 GPM at 220 feet TDH, 2-inch discharge, 3-inch suction flanged, 20 HP 3500 RPM motor 460-3-60. Cuno Filter - "Micro-Wynd" cartridge type filter, type CG 40 S-4 for 175 GPM at 1.0 micrometer Filter density, 95 psig inlet -five psig pressure drop. Cartridges used are 160 each of JM 2E7P or equivalent. Large Millipore - Millipore 20 set multi plate Alter unit com plete in 30 set plate capacity bell housing. 0.8 micrometer filter papers. Sample Millipore - Millipore five set multi-plate filter unit com plete in five set capacity bell housing. 0.8 micrometer filter papers. Sampling Flowmeter - Schutte & Koerting Figure No. 18410 size 6HCF6 type SK W/S.S. fittings, 17.5 GPM at 65 psig oneinch connections. Sampling Orifice & Recorder - Beckman model No. 153062, capacity 17.5 GPM with one pair 1-1/2 inch PVC orifice flanges. pH Meters - Beckman Model No. 900. Water Softener - Sears Roebuck Model No. 625.3474 capacity 8.5 GPM. Total Flow Orifice & Display -Foxboro, serial No. 423484, capacity300 GPM (modelNo. unknown). Water Testing - Hach portable engineers kit - Model No. DR 1834B.
JOURNAL AWWA
CAPCO JEN 0020289
magnesium content found on the sampling Millipore. How ever, due to the extremely small amounts of fiber and because of traces of magnesium from cement in the pipe and mag nesium in the water, this approach was abandoned. The results from the first few runs were, therefore, considered in valid and are not reported. Runs "C" through "G" results were considered to be as accurate as possible and are reported as valid runs. (See Tables 1-11). Fiber analysis was performed by the chemistry lab using particle and fiber counts of mag nified electron microscope photographs combined with a radi oactive tracer technique. Observation of the data showed that
in all series of runs, the amount of fiber in the water is ex
tremely small. For instance, calculating the numbers of
gallons needed to produce one gram of fiber results in the following:
No. Gallons Required Run for 1.0 e Fiber
C 5,950,000,000 D 8,130,000,000 E 12,800,000,000 F 71,400,000,000 G 11,200,000,000
JOHNS-MANVILLE RESEARCH AND ENGINEERING CENTER**
Report No. 425-T-1360
Hours Run of No. Test
] 99.0 2 93.5 3 96.0 4 95.0 5 72.0 6 96 3 7 * 96.0 8 96.0 9 96 0 10 95.0 11 96 3 12 75.0 13 960 14 72.0 15 960 16 96.3 17 72.0 18 96.3 19 97.0 20 96.0
TABLE 1 "C" Series of Runs-Test Line Data (See Research Report So. 404-56) Water Not Treated During This Series
Water Row (gal.)
Total x 103
Sample* x 103
1031 106.1 996 97.5 965 91.4 941 89.8 737 65.3 1004 103.3 821 74.2 979 89.9 914 82.1 714 62 2 953 89,5 745 700 893 74 9 698 61.2 850 75.6 938 81.4 706 61.2 852 74.1 945 902 857 82.1
Avg. Rate (GPM)
174 178 168 165 168 175 140 170 159 125 165 110 155 160 148 163 163 148 163 150
Facsimile of Johns-Manville report. tAsmg/1 CaC03
Run Dates - January 6,1969 July 25,1969
Avg. pH
7.5 7.3 7.2 6.8 7.3 7.3 6.9 7.0 7.2 7.3 7.1 6.8 7.0 7.3 7.5 7.1 7.5 7.6 7.0 69
avg. 7,2
Avg Total Hardness*
120 125 109 101 105 HI 95 102 103 76 78 95 100 102 113 123 122 119 108 102
avg.10$
TABLE 2 "C"Series of Runs-Fiber Data (See Research Report No. 404-56)
Water Run Sampled No. (gal) * 103
1 106.1 2 97.5 3 91.4 4 898 5 65.3 6 1033 7 743 8 89.9 9 82.1 10 623 II 89.5 12 700 13 74.9 14 61.2 15 75.6 16 81.4 17 613 18 74.1 19 902 20 82.1
Ashed Solids (mg)
21.4 41.5 510 47.2 118.5 53.6 228.5 130.0 152.5 106.3 47.6 32.0 116.1 38.6 70.3 260 83.5 27.2 27.S 17.7
Fiber in Ashed Solids
(%)
00337 00140 0.135 00506 0.0112 0.0040 00168 0.0001 00061 00030 00025 0.0242 0.0075 0.0043 0.0115 0.0251 0.0061 0.0648 0.162 00138
SEPTEMBER 1974
'Facsimile of Johns*Manvi!le report tMicrograms/gal (1 microgram - 1 millionth ora gram)
See Research Report No. E404-37 for method
Fiber in Water
(Mg/gal )*
6 8 xlO-5 6.0 xl0-5 75 0 x 10-5 270 x 10-5 200 x 10--5 2.1 xl0-5 52.0 xl0-5 0.14 x 10-5 11.0 xlO-5 5.1 x 10-5 1.3 x 10--5 11.0 x 10 5 12.0 xl0-5 2.7 x 10 5 11.0 x I0"5 80 xl0-5 8.4 x 10"5 240 x I0"5 49.0 x I0~5 30 xlO-5 avg. 168 x 10 5
COMMITTEE REPORT 17
CAPCO JEN 0020290
o
Z
cd
w
czd
3
z
Cd
0
*Cd *77 cd a
H1 Zl
vId z i.
(d
d d
M >
Z
<
S
zC/3 5o5
"5
.5 * .U a.
O<xeixV<6axMJxi^srx->t'(xO'>x'oOoxvs'exmK'i1
s ~f
o5 '? fc ^
UJ a S a.
" a; os
<^ f-- $5
<S --W /loOi, mow f-M~*_ n (S n ^ <t
$
Co Q
O re
re 60 j ^
cje- 'T--O'of' -- --- Oc ' OO ^ c>
0,-3
Si
(d*
* c* v *n o p
Cz5
M
Cd Cd Cd
Z
M
O
Z
w
Qz
Co
55* 22
UOd 5 2w a "b"
w.z
e
2
c/d
Cd Cd I
cd
v OS
Cd
dl
d
M
> Z
*<
S
cA
Z 55
O
l_5
ooeooeeeoooooo
XXXXXXXXXXXXXX
S* & *g
OS
O -- o\mNMO -- <r n ys "> -* < p i*-,e o--
5 8" 8 5p 5
5 8 88
oo
>OO
\ 5 w
0 CO
<
H
*
ft:
**} P ee ao v0 m r o IO
1 V fO fO fO
O O' r* -
<Z> >
o" <"o r> w oo r- o> 9> 9> eo ao >o
5q
-NIOiOO
Facsimile of Johns-Mcnville report`
o
Z
i--i
? =
Cd
Cd
Cd
Z
3 Z
<S?55=
Cd
ZQ O I
< Q <a>o o2d 2co.
!^3
55 ;*
U e* K "5 ^
cd UJ I J to
<d S Cd P
ao ^.07^.i'
C/3
Cd
cd
Cd
Sef--it*og-ts-n--*r-e- rOioONa*iNo**O&V*
'OO'
^
d
d
N*
>
Z <
S'Si oO oO*^o1 copOoOe^o*po doV*J
%
zcA NniO'Of'o9iO
55
O
18 ASBESTOS IN WATER
ozM
Cd
Cd
Cd
Z
3z
Cd
Q
Z
<
W* U cd 2 Cd "z
CdZ 73W CdU
cd
Cd d s Sd O^
Z
o' ^
sS
- 1
Jw o
z
55
O *9
* t e < s ro -- r~t Mm
s, o Cj ,~- t^I0:,
M 2
<s
u) t
-j
H< SC. ft:
<'Xr-erHeocOoocp'Oa'pOoo'Op^^p^aOsvSoff
CH'lO'^OpiOOO'OppOp 0id`9io>iQa'^ra,9'f'i0O--'>f'9o>hC."'0f'i0o'Cio'iCoi'O0>
-NOTIOOf
cd 21 JOURNAL AWWA
"Facsimile of Johnj-Manville report tAs mg/I OCOj Run Dates April 6, 1970 November 6,1970
CAPCO JEN 0020291
JOHNS-MANVILLE RESEARCH AND ENGINEERING CENTER*
Report No. 425-T-1360
E$ OoI oOI oO( oOI oO( oOI vSWoiOo1Oe(- ^
i* OxOxTD xt'o>xIOrtxvtxOoCxatNox--O>`
5?
sN
t? :i sm ac ^
>QS *2
Sco 5*^ * 6^
-- gri> ; iL -g ^o8SSO ivwVOwOuO
<2.55 t^pNhrtot'-t'rft'tfiiwrrtO>rrB.rI/t^Mr-toN>o'OnfrHtVN*>l
" OO l-r~\e- > <0>rtNO{M^ OOOQOOOOOOOaOQO
*2 -<NntvttOhn0
o C4
td
tzd zo
td
Qz
<o
52* $7
Sws 5h' 2zi
u| P<
tdd
d
> Z
s<3
GzO ao*-5
bi |S} 2 `T ^ si| c-oJ C? f>t1; < ^-s
C <U ?|
b s*
J*Oo>
Fiber in W.ter
3 b. <=
i
o *o"_* <E05?5'6-
ToVToToToToToo'T? Vo Oxwxxq xTM xOx,x,xxPixQ
-- -- 0f-%O --
OP4<rNHomiPVN>> oSo8oe3oe
O d> >J m eg
.9 3
o <3
to f
3O3
#-
e.us
c
I Q
3m 'Sa S8
4.8 {a0t>5
<g
= 5a |
8
Cu >2
!i
^ &
'.E2
.6E
as. .-
i> *.*g2 I^ ^E-.
^P` 'O'jOocjP--r>'iaOcooNron o--odr"d'OOwwrtiP0
Otf2| r m p- o ;
*g *s 3
>< afe> hcSr>
CO *j
o^
* g
a
s
JC
SO
s s
g i g-s:
OOOTjC cccg`
sssi;
a & b-o <<<"
HggE
5E 0u 5g 1*S> O2v3
JOHNS-MANVILLE RESEARCH AND ENGINEERING CENTER*
Report No. 42S-T-1360
<NDfiNlP^orjOtep-vy`tt^oS^lOMnOn-'CnorOpsNO5
u> --. <
--S 0 N rs & t>-) ^I
m
.5 tA, ,2 *4 ej 5:
JO , '
f~ -S 4. UJ I < "S J sC r
5 = S.'s
e-- =e f-S S o -g
:i-t*SS '
> s s&. <ctfc>
O' -- -- --- r n pm
*% oe oo oo oe o
s O' r o oo as
2tt -
Oc
20'^0'9'0>0>0'0'0>
SEPTEMBER 1974
2 NntmiOhBO'O
C5 Z--cd ttdd Zh--I u ztd
Q Z C os f.USf.Bit*dJ T*S*r>
wZr| tdU g.
r 2 tddd} > Z <
iI S S8^ cc
IfS uI.<a: O
?5 = -- C4 *
5 ^
<> n 5&o. OOOOOOOwtwiO
"-5 . K ^ -S .
jatS:
c. < o; &-i
H <--0B; tS I t:o o2; ^s ?
Soo^or-vfPNN...W...M...r.t
eo'OW'On--co*rt-O'OrctoO
'o0O'ppM-o'0Oo'0vio''0Oo'0'Oo'<'Oo>'eD'0'>O'0cP'r
edZ MNrti'tVtOP'tOO'O
--O 3c
IS
s
!<?=
i"f3*S
COMMITTEE REPORT 19
CAPCO JEN 0020292
Appendix D-3
Municipal Water Systems Analysis
Sample
Fiber in
Filtered
PerCent Original
Quantity Ash Fiber in
*er
(Gals)
mg
Ash
1 l Globe source 12 Globe disL system 13 San Diego source 14 San Diego dist system IS Long Beach source 16 Long Beach dist system 17 Providence source 18 Providence disL system 19 Providence dist system 20 Providence source 21 Providence dist. system 22 Wichita dist. system 23 Wichita source 24 Wichita dist system 25 Memphis dist system 46 Saginaw source 47 Saginaw dist. system 48 Winnepeg source 49 Winnepeg dist system
5
3.0 0.043
026
5 40.4 0.0053 0.43
5
2.0 0.067
027
4-1/3
10.0 0.137
3.16
S
20.9 0.060
2il
4*1/3
10.3 0.098
2J4
4
2.7 0.141
0.95
4
3.6 0.161
1.45
4
2S 0.351
2.19
4
1.0 0.302
0.76
4
0.7 0.574
1.01
2
21.1 0.015
1.58
4
S.6 0.084
1.18
1
27.4 0.022
6.03
5
16 0.422
6.42
4
180
0.00026
0.012
4
4.3
0.00045
00048
5
11.0 0.026
0.57
5
6.9 0.034
0.47
Phenolphthalein Alkalinity + Methyl Orange Alkalinity (Total Alkalinity in mg/I CaCt^)
pH
8.1 8.0
.
8.0
.
8.0 9.4 10.5 102 9.8 9.8 9.0 8.4 8.9 8J 8.0 9.0 7.8 8.0
Total Solids mg/I
479 614
.
753
.
409 63 86 82 62 61 359 355 380 59 138 113 137 129
Total Hardness
mg/I
156 163
.
324
.
104 29 56 45 31 30 113 72 105 28 106 80 97 98
Calcium Hardness
mg/I
124 118
.
204
.
76 25 55 44 25 25 61 49 52 16 75 54 69 68
Total i Alkalinity* Iron
mg/I mg/I
214 0.02 228 0.10
114
.
134 5+1005) 35+15(50) 20+15(35) 10+5(15) 5+10(15) 13+82(95) 2+84(86) 9+80(89)
36 82 68 87 * 87
0.07 0.05 0.02 0.05 0.04 0.01 0.03 0.01 0.35 r.5 0.08 - 0.026 0.011 0.068 0.088
Juniata River
Breetewood, PA. Newton.Hamilton Lewistown Amity Hall
Connecticut River
Canaan, Vt. Littleton, N.H. Lebanon, N.H. Greenfield, Mass. Middletown, Conn.
Chrysotile Asbestos Content of River Water 3/71 4/71 5/71 6/71 7/71 8/71 9/71 10/71 11/71 12/71 1/72 2/72
0.0 00 Ul 0.0 0.0 0.0 2.96 2.89 2.36 6.06 6.30 2.96
2.75 0.0 0.0 0.0 3.35 . 0.0 *
4.06 9.20 0.6
2.37 00
0.0
10.79 0.0
0.0
2.02 0.0
0.0
0.19 2.92
1.81 5.61
121
1.09 2.36
6.18
SSI
0.0
5.48 14.96 14.83
4._16
_
48.05 13.93
1.48
1.25 0.0
6.74 1.83 2.95 0.43 1.58 0.0 0.48
2.61 0.0 2.81 2.77 5.08 0.0 13.79 0.83 1.25 0.0
1.96 1.86
2.43 0.0 0.0
3.13 2.64
1.92 0.0
1.66 1.70 1.15
1.39 1.03
6.39 23.48
3.41
0.0
0.67
407 2.98 4.44 168 103 12.08 4.59
6.33 11J9 4.61 10.10 6.75 14.48 00
088 0.48
--
3.02 4.32
Note: All numbers in mierograms per gallon. 0 -- no fibers detected or fewer fibers than considered reliable Ail values determined by ektron microscope observation. No fibers were visible in any (he samples under optical microscopic observation at 4S0X magnification.
3/72 0.0
8._66
_
0.0 0.0 0.0 1,95 8.68
20 ASBESTOS IN WATER
JOURNAL AWWA
CAPCO JEN 0020293
Appendix E
Dose-Response Relationship
CIn persons occupationally exposed to asbestos (McDonald and Enterline) most of the cancers reported are of the respiratory system. However, some of the asbestos is in gested, and excesses of digestive system cancers are also re ported. The figure compares the rates of digestive system can cers following exposure of two groups of asbestos workers: McDonald - miners; Enterline - retired industrial workers. Since McDonald and Enterline measure their responses on different scales, an attempt was made to equate these scales using the bronchus and lung data. This led to an "equivalent average death rate" (EADR) of ten being roughly compara ble to a "standard mortality ratio" (SMR) of 100, an EADR of 20 = SMR of 400, EADR of 30 = SMR of 600, etc. as shown on the figure.
It also led to a dose response relationship as shown by the line of triangles. This dose response relationship is not ap propriate for the digestive system. In fact, there appear to be two dose response relationships in these data with the one for the miners at a higher risk than the industrial workers for the same exposure in mppcf years.
Because of the paucity of data, some dose groups for both the McDonald series and for the Enterline series were com bined. McDonald originally reported six dose groups col lapsed here into four. Enterline first reported seven dose groups. In one publication, he collapsed these into five, and in this figure they are further collapsed into three. Both the McDonald data and the Enterline data show positive dose response relationships. The Enterline data are possibly con sistent with a threshold somewhere above ten mppcf years. The McDonald data show no evidence of a threshold.
i
i
i
(
SEPTEMBER 1974
O P
600 a<:
500
_i
<h*
oCtL
400 5
ao' < O
z 200 t<I/--1
100
National Cancer Institute, 9000 Rockville Pike, Betnesda,MD, 20014 USA
Fig. 2. Dose vs Death Rate
COMMITTEE REPORT 21
CAPCO JEN 0020294-
Appendix F
Research suggested for further elucidation of the primary question "Does the use of asbestos-cement pipe in the pota ble water systems constitute a health hazard?" Not arranged in priorities.
1. Develop a standard method for determining asbestos in water according to needs for item 2.
2. Determine the quantity of asbestos by categories of size (length and diameter) as it actually exists during variations that might be introduced over time, installation, tapping, etc. in potable water supplies distributed in asbestos-cement, metal and plastic pipe.
3. Determine the increment of asbestos fibers added to the water as it traverses asbestos-cement, metal and plastic pipe systems under varying circumstances of installation and operation.
4. Determine the contribution that the asbestos content of soil, in which pipe of the three kinds is imbedded, makes to the asbestos content of the water traversing the pipe.
5. Determine the effect of water flow in an asbestos-cement pipe loop (not installed in soil) under varying conditions of velocity and aggressiveness, and also with respect to distance and temporal influences.
6. Examine the use of crocidolite content of water as a "marker" of fiber migration from the asbestos-cement pipe wall to water in operating systems. (Pipe loop and in situ).
7. Conduct animal studies both by inhalation and direct im^r
gestion to examine the quantitative aspects (total and for various kinds, sizes and shapes of fiber) of fiber entry into and its fate in the gastro-intestinal system and migration from the system. Clearance and migration studies.
8. Conduct animal inhalation and feeding studies to explore possible carcinogenic effects (gastro-intestinal, peritoneal and others). Perhaps combine this with #7.
9. Conduct studies to ascertain whether or not fibers migrating from either lung or gastro-intestinal tract might reach the peritoneum. Perhaps as part of #7.
10. Conduct a direct study of human population groups ex posed to asbestos-cement pipe distribution systems in con trast to distribution systems of other materials in terms of cancer experience--especially gastro-intestinal and peritoneal mesothelioma.
11. Conduct studies to develop better dose relationships in volving occupational exposure to asbestos and gastro-in testinal and mesothelial cancer experiences.
22 ASBESTOS IN WATER
JOURNAL AWWA
CAPCO JEN 0020295
r, stress at zero pressure with external load only. Calculations showed that the
larger of the two thicknesses obtained by designing separately for (1) external
"load with no internal pressure and (2) internal pressure with no external load
is greater than the thickness calculated by the appropriate Spangler equation for
combined external load and internal pressure. Therefore, the separate stress
design detailed in the standard was selected.
6. Design jor internal pressure. Results of a large number of wall tensile
tests conducted in conjunction with full-length bursting tests of ductile-iron pipe *
of various sizes and thicknesses showed that a design hoop stress of 16,800 psi
for internal pressure is appropriate and conservative. This stress is 40 per cent
of the minimum yield strength of 42,000 psi based on a longitudinal wall tensile
specimen as specified in the pipe standards ASA A21.51 (AVVWA 051) and
ASA A21.52. Internal pressures used for calculation of the thicknesses in ASA
A21.51 (AVVWA 051) included an allowance of 100 psi for surges.
7. Earth loads. As stated previously, the deflection of a flexible pipe reduces '
the earth load to less than that imposed on a more rigid pipe in the same condi
tion, because the sidefills carry a part of the trench load transferred to them
by the deflection of the pipe. When the sidefill soil and the pipe have the same
degree of rigidity and the pipe is installed in a wide trench, the earth load on the
pipe is the weight of the prism of soil directly above the pipe. In narrow
trenches the load may be less than the prism load due to the influence of friction
forces on the trench walls. In the standard the prism load is used for 18-in. and
_, larger pipe laid in trenches of any width. As the reduction in earth load due to
transfer of load to the sidefills is dependent on pipe deflection, it is evident that
the deflection and, therefore, the reduction in earth load of the smaller diameter
pipe would be less than for larger-diameter pipe. From a study of the relative"*
rigidity of the sidefill soil and pipe of various sizes and thicknesses, it was con
sidered that the prism load is applicable to lS-in. and larger ductile-iron pipe.
It was also considered that the deflection of S-in. and smaller pipe would have
no effect on the earth load. Therefore, Marston earth loads for relatively rigid
pipe are used for S-in. and smaller pipe. It was further considered that 10-in.
through 16-in. pipe sizes are intermediate between these extremes, and for these
sizes the earth load is prorated between the Marston load and the prism load.
In the calculations for earth loads, the unit weight of 120 lb per cubic foot for
backfill soil is used. Soil weights generally vary from 110 to 130 lb per cubic
foot. Experience has shown that 120 lb per cubic foot is commonly considered
to be a conservative value for most installations.
_
8. Allowance jor truck sttpcrload. In computing ductile-iron pipe thicknesses,
truck loads are added to earth loads. The truck superload allowances in ASA
A21.1 (AVVWA HI) were adopted. These loads in most cases equal or exceed
the static load from a single AASHO H-20 truck with 16.000 lb on each rear
wheel. These truck superloads arc based on having the design depth of cover
over the pipe. Consideration should he given to the loads that may be trans-
^^mitted to the pipe if either truck supcrloads or heavy construction equipment
is permitted to pass over the pipe at less than the design depth of cover.
o
CAPCO JEN 0020296
TIIICKNICSS DKSIGN OK l>tCTII.K-M)N IMPK
11
^^Frism:
II'. = llwis,.
(5)
Symbols in these equations arc ex plained in Table 7.
a. For 3-in. through 8-in. pipe, the earth load is computed by Marston's method for a trench width equal to nominal pipe diameter plus 2 ft, using E() 2 or 3, whichever gives the smaller load.
b. For 10-in. through 16-in. pipe, the earth load is computed by Eq 4, prorating between the Marston load for S-in. pipe, described above, and the prism load for 18-in. pipe, described below.
c. For lS-in. and larger pipe, the earth load is the weight of the prism of soil directly above the pipe computed by Eq 5.
50-4.2. Truck superloads (IVt) : The truck superloads shown in Table 1 are computed by the procedure in Sec. 1-10 of ASA A21.1 (AWWAHl) for two passing trucks with adjacent wheels 3 ft apart and with 9.000 lb on each rear wheel. To the load thus ob tained, 50 per cent is added for im pact of the trucks moving over a road way assumed to be unpaved and rough.
50-4.3. Net thickness required for
trench load: The net design thickness
required for trench load is determined
from Table 2. The trench load-
..
. /irc\.
.D
diameter ratios ! -- for various --
\p )
t
ratios shown in Table 2 were com
puted from Eq C, which is the formula
for the bending stress at the bottom
of the pipe:
f Wei
Kt
4/s
Kh SEl1
^ + -732
(6)
in Eq 6, / is design bending stress at bottom
of pipe (36,000 psi). Wc is trench load in pounds per
linear foot of pipe (earth load plus truck superload).
d is mean diameter of pipe in inches (D-t).*
D is outside diameter of pipe in inches.*
t is net thickness of pipe in inches. E is modulus of elasticity of pipe metal (24,000,000 psi). E' is modulus of soil reaction in pounds per square inch (from Table
8)\ .
K>, is bending moment coefficient de pendent on bedding angle (from Table S).
Kx is deflection coefficient dependent on bedding angle (from Table 8).
Tables similar to Table 2 may be compiled for laying conditions other than A or B by assuming a series of diameters and thicknesses and calcu lating the matching trench loads using Eq 6 with values of Kh. Kr. and E' appropriate to the bedding and back fill conditions.
Sec. 50-5--Optional Calculation of Pipe Deflection
The maximum strain in cement lin ings is limited to a uniform safe value by the 36.000-psi design bending stress. Deflections calculated for 3-in. through 48-in. pipe with thicknesses designed by the above procedure for standard conditions do not exceed 2 per cent of the out<ide diameter of the pipe, which is well below the deflection that might damage the cement linings. Therefore, it is not usually necessary to calcu late deflection as part of the design pro cedure. If it is desired to calculate the deflection, Eq 7 is used with the
See Xote in Sec. 50-2.1 -
i cr ri nnonooT
10 AMERICAN STANDAR11
cover for a working pressure of 150
psi. 50-3.1--Step 1--Design for Trench
Load for Water or Gas Pipe:
Earth load from Table 1 = 1,290 Ib.'lin fl 'i'ruclc load from Table 1 = 769 Ib/lin ft
Trench load,
li t = 2,059 Ib/lin ft.
Divide trench load by outside diam eter of pipe:
IK 2,059 = 80 lb/ft/in. D 25.80
Find -- = 80 in Table 2 for Laying D
Condition B, and read the required
TABLE 8 Design Values of the Beading Coefficients and
Modulus of Soil Reaction
Laving Condition
Bedding Backfill Bedding
angle--deg A' K, E`--psi
A it
fiat bottom fiat bottom
untamped
tamped
30 0.235 0.108
150
30 0.235 0.108
300
value of the diameter-thickness ratio, D = 112. l
Divide this ratio into the outside di ameter of die pipe to obtain net thickness:
25.80 t -- ------- = 0.23 in.
112
50-3.2--Step 2--Design for Internal Pressure:
a. Water pipe:
Working pressure = 150 psi Surge pressure = 100 psi
Design pressure = 250 psi.
Then,
250 X 25.SO 0.19 in. 2 X 16,800
/~\
b. Gas pipe: Working pressure = 150 psi.
'Then,
150 X 25,80 0.12 in. 2 X 16,800
50-3.3. Step 3--Selection of net thickness and addition of allowances: The larger of the thicknesses is given l>y the design for trench load, Step 1, and therefore 0.23 in. is selected as the net thickness for water or gas pipe.
Met thickness = 0.2.5 in. Corrosion allowance = 0.08 in.
Minimum manufacturing thickness = 0..51 in. Casting tolerance = 0.07 in.
Total calculated thickness = 0..58 in.
50-3.4. Step 4--Selection of stand ard thickness: The total calculated thickness of 0.38 in. is less than the smallest standard thickness shown in Table 6. Therefore, the smallest stand ard thickness, 0.41 in., Class 1, is se lected for specifying and ordering either water or gas pipe.
Sec. 50-4--Design Theory
--'
This section illustrates determination of earth load (W,.), truck superload (Il't), and net thickness required for trench load (Wc) (see Sec. 50-2.1).
50-4.1. Earth loads (fFf) : The earth loads shown in Table 1 are com puted by Eq 2, 3, 4. and 5 below:
Marston, projection condition:
IF, = OIL*
(2)
Marston, ditch condition:
IF, = 0/5 A
(3)
Prorated between Marston and prism : IF, = IF, + 0.1 (/V - 8) (1 I'm - IF.) (4) /*
CAPCO JEN 0020298