652
CHAPTER 38
1965 Guide And Data-Book
fig. : 17
Required Head vs How for Wafer Chiller ` with Cooling' Tower
requirements of-Fig. 17,-and this is why.it has-been most universally'adopted in recent years.
.Where more stringent requirements for variation must be met, hot gas bypassing is sometimes used. Hot gas bypassing is inefficient, however,' and suitable provisions must be made to desuperheat the bypass gas to prevent excessive discharge temperatures at low loads.'Automatic liquid injection into the bypass gas stream may be provided for this purpose,- or the gas stream may be brought'into contact with cooling refriger ant liquid by'other arrangements. '
In most water-chilling machines, -capacity control is' ob tained by varying the.inlet guide-vane setting in response to a thermostat in the chilled water leaving the evaporator, in order to maintain the temperature of that water as nearly constant as -possible.' In- practice, -the 'temperature of-the chilled water -leaving the evaporator, is allowed to- vary slightly, as a function of the load; in order to obtain a suitable gjgnul to operate the guide ' vanes.- This provides a simple and stable control scheme. Either pneumatic, electro-pneu matic, or electronic controls are available for this purposed and all are widely used. Other methods are'available for auto1-' matically readjusting the set point of the basic capacity con trol in response to load, thereby eliminating drift, and holding the temperature more nearly constant. This feature is1com monly referred to as reset
For further information on automatic controls, see Chapter 13.
Safety Controls
In addition to the basic capacity controls, centrifugal refrigeration machines normally require a number of other controls, which are generally classed as safety controls. Some of these are limiting controls to keep the compressor within bounds during operation, and others are designed to shut down the machine without damage in the event of various possible malfunctions. Typical controls of this type are: (1) a load-limiting control which overrides the capacity control during start-up, during pull-down, or at other times when conditions would overload the motor, (2) a safety relief valve or valves on the condenser or evaporator, (3) a low oil pressure cutout switch for shutting down the unit as a result of lubri cation failure, (4) a high condenser pressure cutout, (5) a low evaporator water (or brine) temperature cutout, (6) a low refrigerenfc-temperature or-pressure cutout, -and. sometimes (7) a chilled\water flow cutout/Still other, oontrola may be provided for special situations.
MULTIPLE MACHINE OPERATION
When more than one machine is installed to chill a common
bad, choices must be made concerning the piping of the chill-1 era and condensers, Le., whether the chilled water should be piped through the multiple evaporators in series.or parallel
and whether the condenser water should be piped through the' multiple condensers in series or parallel. In addition, choices
must be made of the methods of chilled-water temperature control. Each method has advantages and disadvantages, and selections will be based on the best match between the char acteristics of the equipment, the initial cost, and the operating
cost. Sometimes the overall system requirements, including consideration of the air-side equipment,.will dictate the most4 economical arrangement.
Series operation of the chillers is desirable primarily because' one machine can be operated at a higher eraporatortempeni-
ture, with improved cycle efficiency. Water-side pressure drop, is higher if .the same number of;passes are used;as in.parallel operation. Total full-load horsepower, including pump horee-.
power, can be less for series than for parallel arrangement of the chillers. However, this advantage becomes questionable if extensive partial load operation is expected. Much the same trend exists, with regard to series arrangement of ttie' conV. denser. The water-side pressure drop in series operation of.
either the condensers or the evaporators can be minimized by reducing the number of passes. Reduction of the number of passes usually lowers heat transfer performance somewhat'
and tends to cancel the performance gun obtained by series^ operation.
A single-control thermostat may be used to control all machines, or each machine may have'its own thermostat. If
a single-control thermostat is used in parallel operation of-the chillers, overriding thermostats on each machine are usually required to prevent freeze-up.of one operating machine when . the other is shut down at partial load. Controls can be ar ranged to reduce load on all machines simultaneously, or to
reduce load on one machine at .a time, with others remaining' at full load until the unloading machine is shut down. Controls,
are usually arranged to shut down machines as load reduces, in
order to operate.the; .remaining machines at .higher load and better efficiency. Arrangements usually, permit selection of; which machine or machines will remain in operation, so that
machine operating time can be equalized.
SaECTlON OF CENTRIFUGAL. REFRIGERATION
MACHINES
In the design or selection of a centrifugal refrigeration
machine for a given situation, the following minimum infor
mation is required:
1. System Load in Tons of Refrigeration. The system load re quired for selection or specincation is determined by careful con sideration of all the individual or tone loads, and the diversity of factors entering into the summation of these loads. This is dis cussed in Chapter 27 of this volume'and Chapter 19 of the 1964 Guide Ann Data Boos.
2. Design Leaping Chilled-Water Temperature. The Itoving chilled-water temperature is determined by the type of equip ment selected to absorb the system load, balancing adequate humidity control with economical selection of coil surface.' If all other conditions remain constant, a higher leaving chilled-water temperature will result in increased refrigeration unit capacity for a given kilowatt input, and a more economical selection of refrigeration equipment.
3. Design Ckuled-Water Rate. Since the chilled-water, tem perature drop of the refrigeration unit is normally determined by the adsorbing equipment selection, the chilled-water rate is a function of chilled-water temperature drop and the refrigeration . load (in tons) in accordance with Equation 11..
Compressors'
where tg water Sow rate, gallons per minute. a - load, tons. f , water temperature drop in the chiller, degrees. -
.-
4. Design Temperature of the Cooling Water Entering the Con
denser. The dwign temperature of the cooling water entering the
is dependent primarily on the source of the cooling
water. Became" there are limitations on water usage in most areas,
the K>ling tower has become the most common tource of con
denser
water. Normal tower design can provide Cooling
water at a temperature 7 F deg above the design wet-bulb tem
perature, and, m the case of a 78 F design outdoor wet-bulb tem
perature, the cooling water leaving the. tows and entering the
condenser will be 85T.
; 5 Design Condenser Water Rate. The condenser water rate is
usually specified on the basis of a 10 F deg water temperature
rise the oondenser. The water rate can be related to the
temperature rise by Equation 12.
...
; --,, .
+ 0-212P) . .
'.h;
'WO
653
where
P *= power, required to pump refrigerant through the com
pressor, horsepower.
. . .j
. A4 = water temperature rise in condenser,' degrees.
For water chilling applications, a good approximation is given by Liquation 13.
30q .= (13)
OL
All other conditions remaining constant,' the lower the
leaving condenser water temperature, the higher will-be the
refrigeration unit capacity for a given kilowatt input and the
more economical will be the selection of refrigeration equip
ment. '
.
-.With-this information,-a Erst approximation of-the'con
densing and evaporating temperatures TM be made.*An ap-
proach-oi 7-8 F deg can be assumed-for.the evaporatorpbased
on a water-side-fouling factor of 0.0005, if water or a fluid
having similar'- heat transfer coefficient is used. Approach
refers to the temperature difference between refrigerant and
leaving water.- If a fluid having a low heat transfer coefficient
is to be chilled, a higher approach should be assumed in order
to prevent the evaporator from becoming uneconomicaliy
large. An approach of 7-8 F deg can~also be assumed for the
condenser, based on a fouling factor of 0.0005. If dirty water
is expected, with a still higher .fouling factor,, ARI Standard
555-63 (Application and Ratings of Centrifugal liquid Chill
ing Packages) allows for the selection of.water chilling pack
ages for 2 F deg lower leaving chilled water temperature' for
each increment of 0.0005 fouling allowance in the cooler, and
for 2.5 F deg higher leaving condenser water temperature for
each increment of 0.0005 fouling allowance in the condenser.
Alternately, approaches wu> be calculated yring the-informa-
tion giveh in'Chapters 42 and 43. .
.. .
With these approximate values of evaporating and con
densing temperatures, the flow and head for a given refrigerant
eao .be calculated. In' doing this, it' is usually assumed that
very little subcooling or superheating occurs in the normal
cycle-and that condenser liquid and evaporator vapor can
therefore be assumed to be at saturation.
For a simple single-stage compression cycle, as shown, in
Fig- 9, the flow volume is calculated by the following equation:
where
Q " quantity of refrigerant at compressor intake, cubic feet per minute.
*i ~ specific volume of vapor at the compressor inlet, cubic feet per pound.
. Ai = enthalpy of gas at saturated suction temperature, Btu
, per pound.
, -
ht ** enthalpy of liquid at saturated condensing temperature,
Btu per pound.
'
. Although a polytropic process can be thought of as any
process which is non-iscntropic, as commonly, used with ordi
nary centrifugal refrigeration compressors (where there is little
external-heat*transfer during compression),, the poiytropic
process,is-generally referred to as-an' irreversible adiabatic
process: It-caa.be shown that the polytropic head require
ment for such'a process may be calculated using the following
equation:
; >'
.<.
- U5)
H TM polytropic head requirement,
pi -= pressure at stage inlct/pounds per square inch absolute,
pi -- pressure at stage discharge, pounds per square inch
absolute.
' 1
Pi -- specific volume at stage inlet, cubic feet per pound/
pi * specific volume at stage discharge, cubic feet per pound.
Poiytropic t analysis- is -usually preferred over, isentropic
analysis because it tends to stay invariant over a wider range
of4 compressors, fluids, and operating conditions. The poly-
tropic or hydraulic efficiency is commonly defined as the ratio
of tiie Poiytropic Head to the actual enthalpy, rise of the fluid,
otherwise known as the Input Head:
v - .-
` = '
, -`JL:
(16)
s,".**.poiytropic,efficiency.
HmInput Head, foot pound force per,pound mass. ]
'
"V."* enthalpy at discharge pressure'and temperature^1'Bta
-'-.'.i-- per-pound.
-
.--I'-v.-.l
- enthalpy at suction pressure and temperature, Btu per
.. ..pound..; /,
-i
T-ir.l
"'With'flow'quantity and head-requirement to calculated'in Equations 14-16, the compressor performance characteristic may be used to determine the efficiency and operating speed requirement.