B.T.U. PER LINEAR FOOT PER HOUR PER DEG FAHRTEMPERATURE DIFFERENCE
HEATINC VENTILATING AIR CONDITIONING GUIDE 1941
Fig. 2. Heat Loss Through 1 In. Thick 85 per cent Magnesia Type Covering
CHAPTER 42. PIPE AND DUCT INSULATION
Table 12. Areas of Flanged Fittings, Square Feet
Nominal Pips Size (Inches)
i
IK IK 2 2K 3 3K 4 4K 5 6 8 10 12
Flanged Coupling
90 Deg Ell
Long Radius Ri.t.
Tie
CB08S
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
Standard
Extra Heavy
0.320 0.383 0.477 0.672 0.841 0.945 1.122 1.344 1.474 1.622 1.82 2.41 3.43 4.41
0.438 0.795 1.015 0.892 1.083 1.235 1.575 1.622 2.07
0.510 0.957 1.098 1.084 1.340 1.481 1.925 1.943 2.53 0.727 1.174 1.332 1.337 1.874 1.815 2.68 2.38 3.54 0.848 1.65 2.01 1.84 2.16 2.54 3.09 3.32 4.06 1.107 2.09 2.57 2.32 2.76 3.21 4.05 4.19 5.17 1.484 2.38 3.49 2.68 3.74 3.66 5.33 4.77 6.95 1.644 2.98 3.96 3.28 4.28 4.48 6.04 5.83 7.89 1.914 3.53 4.64 3.96 4.99 5.41 7.07 7.03 9.24 2.04 3.95 5.02 4.43 5.46 6.07 7.72 7.87 10.07 2.18 4.44 5.47 5.00 6.02 6.81 8.52 8.82 10.97
2.78 5.13 6.99 5.99 7.76 7.84 10.64 10.08 13.75 3.77 6.98 9.76 8.56 11.09 10.55 14.74 13.44 18.97 5.20 10.18 13.58 12.35 15.60 15.41 20.41 19.58 26.26
6.71 13.08 17.73 16.35 18.76 19.67 26.65 24.87 34.11
`Including areas of accompanying flanges bolted to the fitting.
Example 1. Compute the total annual heat loss from 165 ft of 2 in. bare pipe in service 4000 hours per year. The pipe is carrying steam at 10 lb pressure and is exposed to an average air temperature of 70 F.
Solution. The pipe temperature is taken as the steam temperature, which is 239.4 F, obtained by interpolation from Table 8 Chapter 1. The temperature difference between the pipe and air = 239.4 -- 70 = 169.4 F. By interpolation of Table 6 between tem perature differences of 157.1 and 227.7 F, the heat loss from a 2 in. pipe at a temperature difference of 169.4 F is found to be 1.624 Btu per hour per linear foot per degree tem perature difference. The total annual heat loss from the entire line = 1.624 X 169.4 X 165 (linear feet) X 4000 (hours) -- 181,600 Mb.
Example 2. Coal costing $11.50 per ton and having a calorific value of 13,000 Btu per pound is being burned in the furnace supplying steam to the pipe line given in the previous example. If the system is operating at an overall efficiency of 55 per cent, determine the monetary value of the annual heat loss from the line.
Solution. The cost of heat per 1000 Mb supplied to the system = 1,000,000 X 11.5
Table 13. Conductivity (k) of Various Types of Insulating Materials for Medium and High Temperature Pipes1
Types of Insulating Materials
(4 Piles per 1 in. thick) (8 Plies per 1 in. thick) (30-40 Laminations per 1 in. thick) (14-20 Laminations per 1 in. thick) (Diatomaceous Earth and Asbestos) (Felted Fiber)
Mean Temperature, Deg F
100
0.359 0.495
0.505
0.326
0.374
0.350 0.576
0.338
200
0.403 0.618
0.598
0.380
0.445
0.410 0.614
0.396
300
0.448 0.741
0.692
0.434
0.518
0.470 0.652
0.453
400
0.493 0.864
0.786
0.488
0.589
0.530 0.689
0.510
500
0.539
0.543 0.662
0.59a
0.726 0.568
`From tests conducted at Melton Institute.
735