Document Q3rGm0gEyZdn63XM8Bp70Z9k
468
CHAPTER 24
1948 Guide
EXPANSION TANKS
Water heated from 40 F to 200 F expands about 0.04 of the original volume. The expansion tank permits the change in volume of the water in the heating system to'take place.without producing undesirable stresses due to pressure in any part of the system. Expansion tanks may be open, as illustrated in Fig. 15, or closed as shown in Fig. 16. An open expansion tank has free vent to the atmosphere and consequently the pressure on the surface of the water is always that of one atmosphere. The minimum contents of an open tank should be 0.06 of the volume of the water in the system including that in the boiler, heat transmitters, pipes, etc. This : capacity is 50 per cent in excess of the actual increase in volume of water
Fig. 15. An Open Expansion Tank
Fig. 16. A Closed Expansion Tank
due to increase in temperature from 40 F to 200 F. The tank should.be
located at least 3 ft. above the highest radiator. Provision must be
made to prevent freezing of the water in .the tank as. well as in. the pipe
leading to the, tank.
. " :
When the vent from an open expansion tank is extended, through the roof, it should be not less than '4 in. in diameter from a point below the roof, through and beyond the roof line; This will prevent vapor,-Which sometimes rises from an expansion'tank, from closing the vent during outside freezing temperatures.
In a gravity circulation system, the pipe to the open expansion tank should be connected to the supply riser from the boiler, so that'the air liberated from the water in the boiler will enter the expansion tank.
In a' forced circulation system, the pipe to an open expansion1 tank should be connected on the suction side of the circulating pump.
A closed expansion tank is sealed against free venting to the atmos phere.' The tank may be above the highest-radiator, or heat transmitter, or may be below the lowest one. The minimum contents of a closed expansion tank must be such that the expansion of the water due to increase in temperature will be cushioned against a reservoir of compressed air above" the water level in the expansion tank. The tank must provide
Hot Water Heating Systems and Piping , '
469
space hot only for the change in water volume, but also for variations in air volume within the tank due to changes in air pressure; If the closed expansion tank is below the heat transmitters, the tank should be. larger than if it is above them, and the higher the building, under such circum stances, the larger should be the air capacity in excess of that required for increase in water volume due to temperature rise.
The size of an expansion tank for installation in a.closed system may be determined by the following, formula: .
--*
(3)
Pi + 0.434 H
Pi
where
''
V = required tank capacity, gallons. E = expansion of water from cold system to flow riser temperature, gallons.
Pi = atmospheric pressure, psia. Pi = maximum tank pressure specified for heated system, psia.
H = height of top of filled system above tank, feet. (Note- Top of system open to atmosphere when system is filled.)
Example 7. Select a closed expansion tank for basement installation on a system containing 5000 gal arid operating at 200 F flow temperature. The static head due to the height of the system is 70 ft. The maximum pressure should not exceed 100 psig.
Solution. Assume that the system is filled at 40 F. Then
E = 0.04 X 5000 = 200 gal Pi -- 14.7 psia P, = 100 + 14.7 = 114.7 psia.
Substituting these values in Equation 3:
~ 14.7 14.7 + 0.434 (70)
14,7 114.7
200: 0.327 - 0.128
=
1000 gal.
The size of a basement-located closed expansion tank should be at least equal to the following:
One story buildings: x = 0.10 'V . Two story buildings: x = 0.13 V
Three stray buildings: x = 0.17 V Four story buildings:. X = 0.23 V
where. x = expansion tank size in gallons. V = water" voiume.in. heating system in gallons.
"This condition favors, especially in talFbuildings, the placing of the
closed expansion tank above the highest heat transmitter.
... - . .. .
It is common practice to make multiple tank; installations on large
systems iir lieu of having a tank made where the capacity required is
beyond commercially manufactured-sizes. .
"
t
Any closed expansion tank located above the heat transmitters of,a hot water heating system should be, connected by a direct pipe with; the flow main leaving the boiler, in order to enable the air to pass easily to. the expansion tank. In a closed hot water heating system the water under pressure tends to absorb air at a rate increasing with pressure increase and decreasing with temperature increase.
Means must be provided to adjust and to observe the proportion;of air within any closed expansion tank. This involves the provision of. an air