158 CHAPTER 10
when the outdoor air temperature is zero F. The floors in the three rooms are covered with heavy wall-to-wall carpeting, without a pad. Insulation which has a conductance of 0.4 Btu per (hr) (sq ft) (F deg) is placed along the edge of the slah. and extends downward 2 ft below it.
Step 1. Heat Los*
Calculate the heat loss of
room, following the recom
mendations contained in Chapter 25 of the 1961 Gums And Data
Book, but do not include any heat loss through the area covered
by the paneL
If very targe rooms are involved, the rooms should be sub
divided into areas having somewhat similar heat requirements,
i.e., separate the.interior areas requiring little or no heat
input, from the exterior areas directly influenced by outdoor
weather conditions. Each such area should then be treated as
a separate room for the purpose of design.
Room dimensions, exposure, and calculated heat losses are as follows:
Rook
Dimensions Feet
Exposed Wall Feet
Heat Loss Btu per hr
A* 11 x 12 x 8 23
B
11 x 12 x 8
12
C
15 x 21 x 8
21
3300 2500 8000
* Compare with Room A
i. Tbo rooms are the tame except
that la this "-r*u knrer beat kae b married to permit the room to be
heated by a
> without developing ao i-f
corfmoe temperature (Step 3). Tbe lower heat lam b presumably the result
of to Wwirn A
Step S. Required Panel Output
Divide the beat loss of each room by the maximum floor area in the room which can be used as a heating panel. The result is the minimum heat output per square foot of panel that will satisfy the requirements of the room. The panel that requires the highest output per square foot will generally contra) the design, because the temperature of the water in the system must be high enough to produce the required output from that panel.
Room
A B C
Available Panel Abba
Sq ft
132 127 306
Required Panel Output (9.)
Btu/(hr) (sq ft)
25.0 19.7 26.1
1962 Guide And Data Book
Table 4.... Thermal Resistance of Root Coverings
Description
Besistaac*, (F <4gKAr)fa ft)/BJa
Bare concrete, no covering Asphalt tile Rubber tile
0.00 0.05 0.05
Light carpet .Light carpet with rubber pad Light carpet with light pad Light carpet with heavy pad
0.6 1.0
1-4 1.7
Heavy earpet Heavy carpet with rubber pad Heavy carpet with light pad Heavy carpet with heavy pad
0.8 1.2
1.6 1.9
Step 4. Dotonward and Edgewise Heat Flout
a. Determine the temperature of the surface of the concrete slab (f.) by adding to the panel surface temperature, the tem perature difference caused by the thermal resistance of the floor covering, if any:
f. - t* + (?. X r)
(12)
The value of (rM) for various 'floor coverings is given in Table 4.
Room
t.
9- ft*
(,
A
85.0 F
25.0 0.8
105.0 F
B
82.5 F
19.7 0.8
98.3 F
C
85.3 F
28.1 0.8
106.2 F
b. Determine tbe downward and edgewise heat loss co efficient Ci from Fig. 17 for the insulation to be used. Insula tion with a conductance of 0.4 Btu per (hr) (sq ft) (F deg) ex
tending two feet below the slab results in a slab downward and edgewise heat loss coefficient of 037 Btu per (hr) (ft)
(F deg).
c. Apportion the downward and edgewise heat loss uni formly across the panel as follows:
P X Ci(t -- (m) Qd4 " ----------------------
(13)
Step 3. Panel Surface Temperature
From Fig. 16 find tbe panel surface temperature needed to yield the required beat output to each room, using the output determined in Step 2 and tne design room air temperature.
Floor panel surface temperatures-in excess of about 85 F are not recommended because of the probability of discomfort to the feet. If the required heat output cannot be obtained from an 85 F floor panel, heat losses should be reduced or sup plementary heating should be provided.
Room
A B C
Panel Surface Temperature ({,)
85.0 F 82.5 F 85.3 F
Room
P
-U
A,
9*
A 23 105.0 F 132 17.7
B 12 98.3 F 127 9.0
C
21
106.2 F
306
7.1
Step 6. Upward Panel Resistance
Aavmnf- 4 tentative pipe or tube size and a spacing for each
Enel, choosing closer spacings and larger oipe or tube when gher heat outputs are required. From Tame 3, find the ther mal resistance (r,,) of the slab of each panel, using heat flow ratios (qjqu) calculated from tbe flow rates determined m Steps 2 ana 4, interpolating as.required. To the slab resistance (r,,j, add the resistance of the floor covering (rw, Step 4) to obtain the panel resistance to upward heat flow (r.).
Panel Heating
159
Pipe ob Tube
Room
Spacing
9-/9*
rM r.
A
9 in.
17.7
0.47 0.8 1.27
B 12 in.
9.0 -318 0.55 0.8 1.35
26 1
O 9 in- tT"*-* 0.40 0.8 1.20
All toasts: H4n. P*P* er H-W- tabe; 44s. eoseieto slab.
Step 8. Mean Water Temperature
For the required panel output (qm) found in Step 2, the panel resistance (r%) found in Step 5, and the room air temperature .), find the mean water temperature (U from Fig. 16.
Room
A B C
Urn,
116.5 109.0 116.5
Step 7. Design Mean Water Temperature
Select a ningle design mean water temperature (4*_.) for each group of rooms which is to comprise a zone, choosing the highest mean water temperature (Cm) of the group. In the example, 116.5 F is chosen. -
Step 8. Design Panel Output
From Fig. 16 find tbe panel output ($.) for design mean water temperature (t*), room air temperature (O, and panel resistance (rm). Also from Fig. 16 find the design panel surface temperature. If it exceeds 85 F (see Step 3) in a room, go back to Step 5 and choose a wider spacing or smaller pipe or tube for that room.
Room
A B C
(9.)
25.0 24.0 26.1
85.0 (unchanged) 84.5 85.3 (unchanged)
Step 9. Design Panel Area
Divide the room heat loss found in Step 1 by the design panel output found in Step 8.
Room
A B C
A,
132 (unchanged) 104 306 (unchanged)
Step to. Total Panel Output
Add the apportioned downward and edgewise heat flow (9b) to the design panel output (9.) and multiply by the design panel area to obtain the total panel output. If the design panel *pui is appreciably different from the panel output (9.) Qsed m Steps 3 and 4, the apportioned downward and edgewise heat flow (j*,) should be redetermined.
Room
+ 9* A, A,(q. + Q*)
A
25.0* 17.7*
42.7 132
5636
B
24.0
11.6**
35.6
104
3702
C
26.1*
7.1*
33.2
306
10159
* Uachsngod. Redetermined.
Step tl. Fluid Circuit
Design the fluid circuit (panel piping and mains) for a tem perature drop of 10 to 20 F deg between the water inlet (q) npd outlet (t*) of the panel (see Chapter 8, Hot Water Heating Systems).
Step It. Boiler Size
the size of the boiler according to method contained in 43 of tbe 1961 Guide And Data Book. The net Btu rating of the boiler should equal or exceed the total output of all
plus any other loads on the boiler.
Procedure for Hot Water Concrete Floor Panels (Intermediate Slab)1*
The procedure for designing a hot water concrete floor
pflnpl of intermediate
type is given in the following 12
steps.
Step t. Heat Loss Follow the procedure for slab-on-grade construction, Step 1.
Step 8. Required Panel Output Follow the procedure for slab-on-grade construction, Step 2.
Step 8. Panel Surface Temperature Follow the procedure for slab-on-grade construction, Step 3.
Step 4- Downward Heat Flow Ettimate
A. Follow the procedure for slab-on-grade construction. Step 4, part 1.
B. Estimate the heat flow downward as follows:
1. If the underside of the concrete slab is exposed to form a ceiling, find tbe heat output downward (04) from Fig. 15, using the slab surface temperature (t,) found in Step 3 aa the panel surface temperature (t,), and tbe air temperature of the space below.
2. If the underside of the concrete slab is not exposed, use the equation:
94 - Ci(t. - ri)
(14)
Step 8. Upward and Downward Panel Resistance
Follow the procedure for slab-on-grade construction, Step 5, using Table 3 to find both resistances (r, and rj,).
Step 6. Mean Water Temperature and Downward Heat Flow
a. Follow the procedure for slab-os-grade construction,
Step 6.
b. Dae Fig. 15 to find tbe downward heat flow (94). Add to the slab resistance to downward heat flow, fa,), the resistance to beat flow, fa), of any material between the underside of the .Uh and the ceiling surface, to find the total resistance to down ward beat flow fa) to be used in Fig. 15. Tbe water temperature (t_) found above and the air temperature (U) of the space below the ceiling are the other two factors to be used.
If the heat flow downward (94) differs appreciably from the timi*A maWo in Step 4, repeat Steps 5 ana 6 using the calcu
lated value.
Step 7. Design Mean Water Temperature Follow the procedure for slab-on-grade construction. Step 7.
Step 8. Design Panel Output Follow the procedure for slab-on-grade construction, Step 8.