Document OzmJ7MJearrYZMMwezbYgZO7e

HEATINC VENTILATING AIR CONDITIONING GUIDE 1944 a wet-bulb temperature down to 20 per cent moisture, where w = 0.25, the corresponding humidity can be computed by the use of Equation 4 or by reading directly from the diagram, the value being 0.0392. Fig. 6 shows that the corresponding wet-bulb temperature is 105 F. Any intermediate '{joint on the wet-bulb temperature curve can be calculatedsimilarly. The points for w = 0.5 are shown in Fig. 7. Below the point, w = 0.25, the temperature of the stock begins to rise appreciably above the wet-bulb temperature. Its temperature at any given-point in this range, for example at w = 0.15, may be computed as follows: At this point, H -- 0.0234 (from Equation 4) and from Fig. 6, Ira = 95 F. Hence the wet-bulb depression, I -- I* = 150 -- 95 = 55 F. The assumption made regarding the relation between stock temperature and moisture content in this range may be formulated: A tx vj % -- Us ~ 0.25 At the point w .= 0.15, At' = 33 F, I1 = 117 F. The temperature of the stock leaving the dryer, similarly computed, is 136 F. Fig. 7 thus computed gives in graphical form the-information as to the temperature humidity relationships in the dryer. The air requirements can be computed by Equation .4. Thus, per 100 lb of dry stock, it is necessary to supply 633 lb of dry air. . Furthermore, since from Fig.; 6 it is seen that the volume of 50 per cent-saturated air at 70 F, k 13.55 cu ft per.pound; 8580 cu.ft of room air must be supplied per 100 lb dry stock. Similarly, since the volume of 50 per cent saturated air at 150 F is"'18.0 cu ft per pound, the volume of hot wet air discharged from the dryer is 11,400 cu ft per 100 lb of dry stock. Finally, the heat necessary, to supply to>the dryer, as a whole, or to any section of it, may be. computed from Equation 5. High Temperature Dryer In the design of a high temperature dryer unit a method- of approach to the necessary calculations involved is outlined as follows: Example S. Cores 4 and 5 in. thick are to be dried by heating to a temperature at' 400 F. An intermittent type box oven is to be used, size 12 x 14 x 10 ft with 856 sq ft surface haying an average heat transfer of 0.3 Btu per square foot per degree per hour. Drying time as determined by test is 2 hr (Fig. 8). Cores weighing 6 tons, and 15-ton steel plates, trucks etc. are delivered to the dryer at 70 F. The oven is heated by an 746 ' - CHAPTER 41. DRYING SYSTEMS Vent 33J per cert at 422 f . / Recirculation 66 per cent 1 . at 422 F*Y lb r Oven 825 F D-- IS 0) product of perfect combustion per pound fuel Fig. 9. atr for combustion X lb at 70 F Core Drying Diagram of Combustion Products and Air external heater; the products of combustion and 66% per cent recirculated air will be delivered to the oven at 825 F. Fuel oil of 19,980 Btu gross and 18,830 Btu per pound net heating value, weighing 6.75 lb per gallon and having 15 lb product per pound fuel for perfect combustion. Cores consist of 91 per cent sand, 3 per cent oil binder, and 6 per cent water. Solution. Heat required per ton of cores: Lb Material X Temp. Rise X Sp. Ht. = Sand 0.91 X 2,000 X (400 .- 70) X 0.2 = Binder. 0.03 X 2,000 X (400 - 70) X 0.4 = Water heating___________ 0.06 X 2,000 X (212 - 70) X 1.0 = Water evaporation______ __ 0.06 X 2,000 X 970 (Fig. 6) = Water superheating (approx. 50 per c--e----nxt.--r-e---a---c--1h---e---s-e577c5T?F\ ) = 0.5 X 0.06 X 2,000 X (575 -- 212) X 0.45 = Btu 120,120 7,920 17,040 116,520 9,800 Total HeatV_____________________________________ _ 271,400 Btu Heat in 1 lb fuel oil Heater Loss (10 per cent) Duct Loss (5 per cent) => = 1883 = 942 18,830Btu 2,825Btu Btu available to heat oven 16,005 Btu Heat content of gases in 1 lb fuel oil at 825 F is 205 Btu Sensible heat in products ofperfect combustion =(15 lb + 205) = 3,075 Btu Btu to heat air X and Y (Fig.9). = 12,930Btu Y {Sta - Srn) + X (SW - 5,o) = 12,930 F = 2 (X -f 15) for 66.7 per cent recirculation (6) where S = heat content of air at temperature noted taken from Fig. 6. (Recirculation and exhaust contains water vapor, products of combustion, and a greater portion of air. Heat capacities of all vary so little that they have all been assumed to be air). Sat -- Sea = 190 -- 91 =99 - Sn = 190 - 8.6 = 181.4 Substituting values of Y, H, etc. in Equation 6, (2 X + 30) 99 + 181.4 X = 12,930 X = 26.3 lb excess air. Y = 82.6 lb recirculating air. Total = 26.3 + 82.6 + 15 = 123.9 lb air and products of combustion circulated per pound fuel burned. 747