HEATINC VENTILATINC AIK CONDITIONING CUIDE 1944 method of handling this problem is to treat the room as though all the air were being supplied by one supply opening. Thus, if two outlets, each supplying 1000 cfm are used, the value 2000 . cfm should be used with Fig. 5. Although this method may place an unwarranted limit on velocity when'used in a large room, it is seldom that such a room has a.noise level low enough to justify a more complicated though more exact procedure.
In general, return grilles.are selected for velocities about half the supply velocity, and when this is done, they may be neglected in sound computa-
GROSS TRANSMISSION BETWEEN ROOMS Ducts serving more than one room permit cross talk between the rooms and should be lined with acoustical material; Where the rooms aredose together and the ducts short", the ducts should be sub-divided to provide ample acoustical .'treatment. Lagging material similar in character .to acoustical board;'when placed on the outside of'ducts serves to prevent noise originating outside the ducts being carried inside the ducts and into the air stream.
634
CHAPTER 33. SOUND CONTROL
A case where outside lagging is desirable occurs when ducts originate at the fan in the equipment room and pass through this room on the way to the room being conditioned or ventilated. Unless the ducts are lined some of the mechanical noise from the equipment room air may be trans mitted through the wall of the duct, thus reaching the air stream and be carried into the room. In such cases, that portion of the duct which is exposed to the sounds in the equipment room should be lagged with material such as cork, pipe covering or other sound damping material to prevent the sound from entering the duct at this point. Numerical data are not available to permit a simple and practical calculating procedure to determine thickness of covering which should be used for this purpose.
Laboratory measurements have shown that the loss through a sheet of No. 22 gage metal, is 24 db. When a sheet of rock wool insulation 1 in. thick and weighing 1.4 lb per square foot is added to this, the insulation value is increased to 29 db. In general, however, adding a layer of insulation or pipe covering does not materially increase .the sound insula tion value unless the material is dense, or unless it is surfaced with another sound impervious layer such as metal or board. Inside lining material used in the case previously mentioned would serve as an absorber of the sound transmitted through the duct walls, and thus act as a means of preventing the transfer of noise into the air stream.. Inside lining may also be used in ducts to absorb noise which reaches the air stream from equip ment such as fans, sprays and coils; noise due to eddying.currents set up by elbows, dampers and similar obstructions;, and noise transmitted from room to room where there is a common duct system.
NOISE THROUGH BUILDING CONSTRUCTION
It is impossible to select equipment which will operate without pro
ducing some mechanical noise, and since the equipment must be-mounted
in a building, it is probable that a part of this noise will be transmitted
to the building to such a degree as to make noisy-conditions in the rooms
which are to be air- conditioned.
.1
Much of this noise may be transmitted by the duct if it is rigidly con nected to the fan outlet: It is common practice to make the connection between the fan and the duct with a canvas sleeve which effectively restricts noise at this point. Noise may also enter-the building through the mounting of the motor and the fan. Flexible mountings should be provided in all installations but these mountings must be carefully designed so that they will actually reduce the energy transmitted between the machinery and the supporting floor. If a flexible material is used, it
is desirable to investigate the installation so that it is not. short-circuited by through bolts which are improperly insulated and by electrical conduit which is not properly broken and is attached both to the equipment and to the building. The flexible mounting, if improperly engineered, may
actually increase the energy transmitted between the equipment and the floor upon which it is supported.
In the proper isolation of vibration, which is usually in the lower range of frequencies and does not include the air borne vibrations known as sound, there is one basic law which is important iin-the solution of the problem. That is the law of transmissibility as governed by the equation: