Document OyXQE3zKRg18n8bjkwkgyKvL
PLAINTIFF'S EXBmrr
Mfg. Dept. Engr. Instruction SF**104
CHV-581
APPENDIX NO.III
SAFETY INSTRUCTION SHEET - FIRED HEATERS
' FORM MFG. 600-3
.............
NO. SUBJECT
DISCUSSION
I to 31
Refer to Appendices I and II for the discussion.
32 TEST APPLIED NEW
The tests applied new for both strength and
leakage may be noted as those specified by the
designing engineer and issued to the con
struction forcer as the required tests. The
strength test is governed by either (a) the cold
test limitations of the terminal fittings or
directly connected piping that can not be
blinded off, or (b) by the stress being limited
to 75# of the proportional limit of the
material, i.e, the test pressure should not
exceed (1.5) x (proportional limit) x (t)/O.D.
The leakage test is usually between 2/3. of the
strength test and a minimum of 1.5 times the
cold equivalent of the safety valve'setting
. . protecting the heater,
.
33 LIMITED BY 34 BANK OR COIL
Note the limitation for the specified test pressure as "tubes," "headers," "flanges," .etc.
Give the location of the tubes and headers in the bank or coil as "convection," "radiant," "roof," "shock," etc. For the terminal fittings note as "inlet," "outlet," "crossover.," etc.
35 HEADER: TYPE
The type of headers should be specifically
designated where possible, for example "Key_____1900," etc. If type is no.t known designate by the general type as "mule ear," "breeck lock," "screw lock," etc.
36 DESIGN PRESSURE
The operating pressure limit should be established as the maximum possible pressure that can be reached by any method of operation. The temperature should be the maximum for safe operation within the limitations of the equip- ment and material.
37 BASED ON
Note the limiting features of the equipment at minimum thickness or other controling factor. The limitation may be the "tubes," "headers," "flange ratings," etc., with temperature limits restricted by "oxidation," "embrittlement,"
"graphitization," etc.
CHEVBB
_ 1? _
0002699
Mfg. Dept. Engr. Instruction SF-104 NO*. SUBJECT 33 TEST PRESSURES
39 PRESSURE
40 TEMPERATURE
FIRED HEATERS (Cont'd)
DISCUSSION
The routine test pressure for strength should - be as close as practicable to the Initial strength test, as these1 tests are applied-to test newly-rolled repair joints. A note should be added stating that the test pressure shall not exceed (l5l x (proportional limit) x (current minimum tube thickness)/o.D. The leakage test is a function of the strength as noted in "32" above,
The pressure for calculating the minimum tube wall thickness should be taken as either of the following:
(a) For low pressure-drop heaters, assume that the entire coil is protected by the safety valve on the top transfer line or on the vessel into which the furnace discharges,
(b) For cracking, reforming, or similar heaters with appreciable coil pressure drop, take a different pressure for each bank or : section of the coil. These pressures are to be determined from the maximum inlet and outlet pressures and either the known or an assumed pressure drop through the coil. In assuming a pressure drop, remember that it will not be a ' straight line function of distance through the' coil, and this will be particularly true in a reformer or other heater where vaporization is appreciable,
The temperatures used for calculating the minimum tube wall thickness should be the maximum allowable operating tube wall temperature. Different temperatures may be in dicated for radiant and convection tubes. Some judgment is required here on the part of the engineer, For example, if the fired heater is to operate with moderate outlet temperatures in the neighborhood of 7OO0F., it is usually a good idea to set the maximum temperature for carbon steel .tubes at about 100F.
- 18 -
CHEVBB 0002700
Mfg. Dept. Engr. Instruction SF-1G4 70. SUBJECT 41 MINIMUM THICKNESS
42 CORROSION ALLOWANCE
FIRED HEATERS (Cont'd)
DISCUSSION
After establishing the pressure and'temperature, the minimum tube wall thickness shall be calculated according to the equation'
tm = PD____ _
2Sxl.33 where P Pressure, lbs. per square inch.
D *= O.D., inches.
S = Stress in lbs. per square inch for 1$ creep in 10,000 hours at the ma-x-tmum operating metal temperature.
1.33 = is a factor applied to get the effect of the two dimensional stress in the tube wall caused by internal pressure. It represents the ratio between two dimensional creep stress and that determined by an ordinary tensile specimen in one direction only, which is the value, appearing in the literature.
The recommended values of creep stress are'given in the Richmond Materials Laboratory report of \
November 20, 1946 entitled "Recommended Values of Creep and Rupture Strength."
The minimum tube wall thickness in the case of fired heaters subjected to high pressure tests may be determined by the routine test stress in the tube being limited to 75$ of the pro portional limit for the material. When the minimum thickness is so limited, the basis should be clearly stated, in the asterisk note- -- as it may be desirable to reduce test pressures ' at a later date to obtain maximum service life for the tubes.
In the event the calculated minimum thickness is less than 0.10", the minimum shall be established arbitrarily at 0.10".
The above apply except where tube thickness
requirements are mandatory as for power boilers
in which case- the requirements of the State of
California Boiler Safety Orders and the ASME
Boiler Code govern.
The corrosion allowance can now be determined by subtracting the minimum thickness calculated from 1ie tube wall thickness supplied.
- 19 -
CHEV BB 0002701
DATA AND OPERATING LIMITS SHEET.- FIRED HEATERS
EQUIPMENT DATA
SERVICE.
MFR____
TUBE NUMBER IHG DIAGRAM
DRAWINGS_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ TEST APPLIED NEK: STRENGTH LIMITED BY__________________
J2. 33
TUBES: LOCATION, i.e. BANK OR COIL
ORDER NO.
._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
MATERIAL . _________________
SPEC. A GRADE _
HUK3ER _______
O.O.-WALL, AY. OR MIN.-LGTH..
HEADERS 4 FITTINGS: LOCATION ORDER NO. '______ MANUFACTURER. TYPE_______ _ MAT* L-HEADERS 4 PUIGS_________ MAT'L-HOLOIHG MSIBERS A SCREWS.
INLETS,OUTLETS & CROSSOVERS: LOCATION FLANGE SIZE 4 RATING_________ FLANGE FACING _ ___________________ CROSSOVER SIZE 4 HEIGHT.
Jl 34 3V
NO.
.YEAR BUILT.
EXT. HEATING SURFACE
.SQ.FT.
.Pl____ LEAKAGE_____ -.3?
psi__
Eras
j- . /OVALS
ENG. DEPT.
-- ----------- --
OPRfl DEPT.
. OPERATING LIMITS
(CONSULT DESIGNS ENGINEER BEFORE EXCEEDING THESE LIMITS)
DESIGN PRES.: INLET
36.
Pi.
F., OUTLET.
BASED ON
_ _ _ _ _ _ _ _ _ _ _ _ 3L
MAX.ALL0H.TU8E HALL. TEMP.___ PJSJ.TEiCTED BY SAFETY VALVE ON TEST PRESSURES: STRENGTH____
15" 38
psi. LEAKAGE.
KKWE3 Till CNN ESS OF TUBES AND HEADERS AT PRESL 4 METAL TFMP. GIVEN
TU3ES' V
PRES. TPIP.
HEADERS
36 psi 1__ _
- S.Y. SET AT
38_______ _
psi. psi.
PRES. TEMP,
4l 42 32- 4o
DATE
*4n based on:
SAFETY PRECAUTIONS
REFER TO GENERAL SAFETY INSTRUCTION SHEETS ME-5IC2 Sheets I, 2, 3, 6, 7, FOR NOTES OH HAZARDS OF EQUIPMENT FAIL URE, KITH RECOMMENDATIONS FOR THEIR AVOIDANCE AND FOR .INSPECTIONS AMD TESTS.
NOTE SELOU ANY SPECIAL HAZARDS, RECGMrIENDAT IOHS, IHSPECTIOHS, OR TESTS THAT ARE IMPORTANT FOR THE ABOVE EQUI FfttNT:_____________________ !----------------------------------------------------------------------------------------------------- :-----------------------
.______
_____ j?sa.__.
"CHEVBB"0002702
Mfg. Dept. Engr. '
Instr.SS'-ldJiFigure 8 jr
SAFETY INSTRUCTION SHEET FIREO HEATERS
(fif'flr'rv )
-- *- - fn --- " -Tr-L *Hrwm
(Plant I 20
DWG. HO. _
Sheet
of
r, rt it i; u 4 I