Heating Ventiuiting Air Conditioning Guide 1939
and collection of dirt in the coils. These difficulties can be avoided bv
proper design and proper servicing. There are a number of ways in which
coils may be cleaned. A common method is to wash them off with water
They can sometimes be brushed and cleaned with a vacuum cleaner. |[|
bad cases of neglect, especially on restaurant jobs where grease and dirt
have accumulated, it is sometimes necessary to remove the coils and wash
off the accumulation with steam, compressed air and water, or hot water
The most satisfactory solution, however, is to keep the filters serviced'
and thus make the cleaning of the coils unnecessary.
'
The proper selection of coils requires an understanding of the necessities of each case and should be based on an economic analysis of the plant design as a whole: No general rule can, therefore, be laid down for the
selection of heating or cooling coils. It is possible, however, to point out
the limits of usual practice and to indicate the influence of the variables involved in the coil selection.
Heating Coils
Steam and hot water heating coils are usually rated within these limits:
Air Face Velocity--200 to 1200 fpm, sometimes up to 1500 fpm. Steam Pressure--2 to 200 lb, sometimes up to 350 lb per square inch. Hot Water Temperature--150 to 225 F. Water Velocity--2 to 6 fps.
Individual cases may deviate widely, but the tabulation given herewith will serve as a guide to usual heating practice:
Air Face Velocity---500 to 800 fpm face, 500 being a common figure.
Delivered Air Temperature--varies from about 72 F for ventilation only to about 150 F for complete heating.
Steam Pressure--2 to 10 lb, 5 lb being common.
Hot Water Temperature--150 to 225 F.
Water Velocity--2 to 6 fps.
Water Quantity--Based on about 20 F temperature drop through a hot-water coil.
Air Resistance--The total resistance through heating coils is usually limited to from % to % in. of water gage for public buildings, to about 1 in. for factories.
The selection of heating coils is relatively simple as it involves dry-bulb temperatures and sensible heat only, without the complication of simul taneous latent heat loads, as in cooling coils. For a given duty, entering air temperature, and steam pressure'it is possible to select several arrange ments of the same design of coil depending upon the relative importance of space, cross-sectional area, and air resistance. Table 2 shows an example.
__________________ Table 2. Several Heating Coil Arrangements
Selection
123
Temperature of air leaving noil, deg F. Air auantitv. cfm. Coil face area, sq ft. Coil rows deep....................... .......... Face velooitv, fpm.
Air friction, in. water.......................................
5
40 129 10*000
33.3
2
300 0.044
'5
40 129 10,000
12.5 3
.
800 0.396
5
40 129 10,000
7.50 4 1330 1.077
510
Chapter 24. Heat Transfer Surface Coils
Cooling Coils The usual range of ratings for cooling and dehumidifying coils are
enumerated herewith:
Entering Air Dry-Bulb--60 to 100 F. Entering Air Wet-Bulb--50 to 80 F. Air Face Velocities--300 to 800 fpm, (sometimes as low as 200 and as high as 1200). Volatile Refrigerant Temperatures--25 to 55 F, at coil suction outlet. Water Temperatures--40 to 65 F. Water Quantities--2 to 6 gpm per ton, or equivalent to a water temperature range of
from 4 to 12 F. Water Velocity--2 to 6 fps.
The ratio of total to sensible heat removed varies in practice from 1.00 to about 1.65, i.e., sensible heat is from 60 to 100 per cent of total, de pending on the application. (See Chapter 21, Tables 1 and 2). Required ratios may demand wide variations in air velocities, refrigerant tempera tures, and coil depth, so that general rules as to these values may.be misleading. On usual comfort installations air face velocities between 400 and 600 fpm are frequent, 500 being a common value. Refrigerant temperatures will ordinarily vary between 40 and 50 F where cooling is accompanied with dehumidification. Water velocities will range from 2 to about 6 fps.
When no dehumidification is desired, for which condition the dew-point of the entering air will be equal to or lower than the cooling coil tempera^ ture, the coil selection is made on the basis of dry-bulb temperatures and sensible heat transfers only, the same as with heating coils. It is possible also to choose various arrangements of face area, depth, air velocity, etc., for the same duty, as illustrated in Table 2 for a steam coil.
Dehumidifying Coils
The selection of coils for combined cooling arid dehumidifying duty is more involved than for heating or sensible cooling and requires con sideration of both dry- and wet-bulb air temperatures. It is further complicated by the fact that the proportional amount of dehumidification required is also highly variable. The methods outlined previously under Heat Transfer and Resistance may be used to determine whether it is possible for a coil to perform the duty required. If entering and leaving
Table 3. Various Cooling Coil Arrangements
Selection
1
Total cooling capacity, tons........ 100
Sensible cooling capacity, tons...
69
Latent cooling; capacity, tons.
31
Ratio total to sensible heat-......
1.45
Air quantity, cfm....... .................. 47,800
Cfm per total ton........................... 478
Face velocity, fpm.. ................... 325
Resistance, in. water... ..................
0.11
Coil face area, sq ft.. _ _____ ___ 147
Coil rows deep.
... 4
Coil evaporator temp, deg F.......
45
2
100 69 31 1.45
41,700 417 423 0.27 99.0 6 45
3
100 69 31 1.45
37,100 371 500 0.51 74.2 8 45
4
100 69 31 1.45
46,800. 468 600 0.37 78.1 4 38