270
_____________ Chapter 14 .__________
.'
I' -
1945 Guide-
Table 8. Steam Pipe Capacities for 30 psi Steam. Systems
Capacity Expressed in Pounds per,Hour
(Steam and Condensate Flowing in Same Direction)
Pipe Size Inches
"K l
IK IK 2 2K 3 3K 4 5 6 8 10 12 .
X
15 31 69 107 217 358 651 979 1,386 2,560 4,210 8,750 16,250 25,640
Drop, in Pressure--Pounds per 100 Ft in Length
X
22 46 100 154 313 516 940 .1,414 2,000 3,642 6,030 12,640 23,450 36,930
X
31 63 141 219 444 730 1,330 2,000 2,830 1 5,225 8,590 17,860 33,200 52,320
%
38 77
172 267 543 924 1,628 2,447 3,464 6,402 10,420 21,865 40,625 64,050
i- '
45 89 199 309 627 1,033 1,880 2,825 4,000 7,390 12,140 25,250 46,900 74,000
2
63 125 281 - 437 886 1,460 2,660 4,000 5,660 10,460 17,180 35,100 66,350 104,500
one or more pressure reducing valves, or pressure regulators, as they are sometimes called, are required.
These are used in two classes of service, one where the steam must be shut off tight to prevent the low pressure building up at time of no load, and the other where the low pressure lines will condense enough steam to offset normal leaking through the valve. In the latter case, double seated valves may be used in a manner that reduces the work required of the diaphragm in closing the valve and consequently the size of the dia phragm. These valves also control the low pressures more closely under, conditions of varying high pressures.
Valves that shut off all steam are called dead end type. They are single seated, and some of them have pilot operation that provides close control of the reduced pressure. If a thermostatically controlled valve is installed
Table 9. Steam Pipe Capacities for 150 psi Steam Systems . Capacity Expressed in. Pounds per Hour (Steam and Condensate Flowing in Same Direction)
Pipe Size
M
1
IK
IK . 2 . 2K 3 3K 4 5 6 8 10 12
X
29 58 130 203 412 683 i;237 1,855 2,625 4,858 7,960 16,590 30,820 48,600
Drop in Pressure--Pounds per 100 Ft in Length
X
41 . 82
185 287 583 959 1,750 2,626 3,718 6,875 11,275 23,475 43,430 , 68,750
X
58 117 262 407 825 1,359 2,476 3,715 5,260 9,725 15,950 33,200 61,700 97,250
X
. 82 165 370 575
1,167 1,920 3,500 5,250 7,430 13,750 22,550 46,950 87,250 137,600
.1
116 233 523 813 1,650 2,710 4,940 7,420 10,500 19,450 31,850 66,400 123,400 194,400
2
184 369 827 1,290 2,600 4,290 7,820 11,740 16,620 30,750 . 50,400 105,000 . 195,000 307,400
Steam Heating Systems and Piping
271 .
Table 10. Return Pipe Capacities for 30 psi Steam Systems Capacity Expressed in Pounds-per Hour "
Pipe Size Inches
K
l
IK IK 2 2K 3 3K . .4 5 6
X
115 230 485 790 1,575 2,650 4,850 7,200 10,200 19,000 31,000
Drop in Pressure--Pounds per 100 Ft in Length
X
170 340 710 1,155 2,355 3,900 7,100 10,550 15,000 27,750 45,500
X
245 490 1,025 1,670 3,400 5,600 10,250 15,250 21,600 40,250 65,500
X
308 615 1,285 2,100 4,300 7,100 12,850 19,150 . 27,000 . 55,500 83,000
1
365 730 1,530 2,500 5,050 8,400 15,300 22,750 32,250 60,000 98,000
after, and near, a reducing valve in such a manner as to cut off the passage of steam, the dead end type should be used.
It is common practice when the initial steam pressure is 100 lb or
higher to install two-stage reduction. If the radiation served is cast-iron,
the A.S.M.E. code requires two reducing valves when the inlet pressure
exceeds 50 psi. This makes a quieter condition of steam flow, as it is
apparent that with one reduction, as for example, from 150 to 2 lb, there
is a smaller opening with greater velocity across the reducing valve, and
consequently, more noise. A two-stage reduction also introduces a
source of safety, since if one reducing valve were to build up its discharge
pressure, this excess pressure would not be so great as the case might be
in a one-stage reduction.
,
If an installation requires single seated valves, and the pilot type cannot be Used, it is necessary to use two-stage reduction, as single seated valves require sufficient diaphragm area to overcome the unbalanced pressure underneath the single valve. In many cases the large diameterof diaphragm required would make it impractical in construction. With a two-stage reduction the diaphragm diameter required would be reduced. If a one-stage reduction' is desired, it is necessary to use a pilot controlled pressure reducing valve, where low pressures are to be maintained closely.
Table 11. Return Pipe Capacities for 150 psi Steam Systems
Capacity Expressed in Pounds per Hour
Pipe Size . Inches
K
l
IK IK 2
3 3K 4 5
6
0
X
. 156 313 650
1,070 2,160 3,600 6,500 9,600 13,700 25,600 42,000
Drop in Pressure--Pounds per 100 Ft in Length
X
232 462 960 1,580 3,300 5,350 9,600 14,400 '20,500 38,100 62,500
X
360 690 1,500 2,460 4,950 8,200 15,000 22,300 31,600 58,500 96,000
X
560 1,120 2,330 3,800 7,700 12,800. 23,300 34,500 49,200 91,500 150,000
.
1
890 1,780 3,700 6,100 12,300 20,400 37;200 55,000 78,500 146,000 238,000