Document OJX8Q2xzNOJOwQKaE5kYQrr1w
INTRODUCTION Polychlorinated biphenyls (PCS) have been used In a vide variety of Industrial and consumer applications over the past 40 years, but It was only recently that evidence began to appear that these materials had been widely dispersed throughout the environ ment, By letter dated February 16, 1970 the Monsanto Company, sole US producer of PCB's, notified all of Its customers of'the potential problem of environmental contamination" by these liquids and recommended "that all possible care should be taken In the application, processing, and effluent disposal of these products to prevent them becoming environmental contaminants." Monsanto has begun a program to discontinue tales of PCB's for'use In paints, plasticizers, specialty Inks, adhesives, paper coatings and all . other open-system applications. The Monsanto Company has declared, however, that It will continue to sell PCB's for closed-system electrical uses. This decision is a tacit recognition of the Important role that PCB's play In the safe, reliable, and efficient delivery of electric power from the generating plant to the user. In the spate of published reports and statements that have appeared In recent years on PCB's there has beon no meaningful exposition of this role of PCB's In electrical equipment ...why, where, and how they are used; what alternatives are available; and what the consequences would be to tho users of such equipment If PCB's were no longer available. We hope that this report will provide such an 4,i
MONS 035134
-4HACKCROltND
PCB's pre used by Che electrical Industry ss components of
certain types of transformers and capacitors. The nature and
function of those devices are described In tho separate sections
of this report devoted to them. At this point It Is sufficient
to say t
1, Transformers are 'devices for converting electrical
power from one- voltage and current level to another,
. and the conducting parts of these devices must be
separated from each other by a suitable Insulating
medium.
.
2, Capacitors are devices for storing electrical energy
through the physical separation of charged metal
surfaces by an Insulating medium.
Prior to 1930 the most commonly used Insulating medium was
mineral oil. The early 1930's saw the commercial development of
Insulating liquids that were mixtures of synthetic chlorinated aro
matic hydrocarbons, principally various polychlorinated biphenyls.
By controlling tho composition of these mixtures, the manufacturer could obtain desired combinations of thermal, chemical and dielectric
properties that resulted In insulating liquids with much greater
oxidation and fire resistance than mineral oils. During the past
40 years these liquids have become widely used in certain types
' ''
,/
of transformers and capacitors and are recognized as a distinct
class of Insulating materials designated by the International
term "askarel". The definition of the term "askarel", the composi
tions- of the liquid that comprise this class of materials, and the
various trademarks by which they, are known commercially are described
In the following section headed "Askarel".'/
HONS 033135
-5-
Tho particular askarels used in transformers end capo,
oro different; so also are the reasons for, and the extent ana
consequences of, their use in these two types of electrical equip,
uient. However, certain general comments can be made at this point
concerning tholr use in both types of equipment:
1, Askarel-insulated transformers and capacitors are
delivered to customers as sealed units from which
thore is no escape of askarel under normal operation
' during their expected lifetimes of 10 to more than 30
' years. However, certain types of equipment failures
can rupture the case and permit the loss of some
askarel to the environment. Such failures occur'
at a rate of about 0,022 of the units in service
per yoar.
2, PCB's can get into the environment during the manu-
facture, delivery, Improper use, maintenance, repair,
and disposal of transformers and capacitors. In
' addition to specific control measures instituted '
by individual manufacturers and recommended by
them to the equipment users, tho American National
Standards Institute has established ANSI Committee
C107 on Use and Disposal of Askarel Vsod in Electrical
Equipment, Its memberships (see Appendix 1) Is
divided Into separate working groups on transformers
and capacitors which will recommend national standards
and procedures necessary to prevent the loss of PCB's
to the environment at all stages from equipment
r
3, .........
manufacture through ultimate disposal. The record of reliable and safe performance that askorcl-lnsulated transformers and capacitors have
.
HONS 0 3 5 1 3 6
\
6
compiled during the past four decades Is reflected
In the various codes, standards, and regulations
th'at now effectively require or encourage the
continued use f.aakerel-insula ted equipment in
many applications,
. "/
I |r i i
L
HONS 035137
ASKAR IS I,
Pnfinitlons'
' '' ,
1, A kynthetlc nonflammable insulating liquid which, vihen
.
decomposed by the electric arc, evolves only nonflammable gaseous
mixtures.
' .. . '
(From the .National Electrical Code 1971 and the
American National Standards Institute C-42 series,
"Definitions of Electrical terms.")
2. Tho term aekarel generally describes a widely used,
broad class of nonflammable synthetic halogenoted hydrocarbon
insulating liquids used as electrical insulating media.
Askarols of various compositional types are used. Under
arcing conditions the gases produced, while consisting of predomi
nantly non-combustible hydrogen chloride, can yield varying amounts
of combustible gases depending upon the askarel type.
Insulation systems incorporating these askarels and
cellulosic or other organic materials may, when arced, produce
gaseous mixture's which are moderately flammable..
, ; (/ '
.
(From ASTM (American Society for Testing and
Materials) Method D 2283-71, Fart 29, 1971 issue; -
will also appear in the 1972 issue of the IEEE
(Institute of Electronic and Electrical Engineers)
"Guide for Acceptance and Maintenance of Transformer
' . ..
o
Askarels in Equipment."; Adoption was also recommended
to tho International Electrotechnical. Commission by
its Subcommittee 10U (Insulating Liquids Other than
Hydrocarbon Oils) of Committee 10 (Liquid and Gaseous
- Dielectrics) as reported in item number 9 of minutes
___________ . M Ilfil/SC 10B. March 1971.) ... 1
MONS 035138
Compositions
Polychlorinated biphenyls are derivatives of the hydrocarbon,
biphenyl, which has the chemical formula C}2H10' From one to ten
of the hydrogen atoms In a molecule of biphonyl can be replaced
by chlorine atoms', and the chemical identity of the resulting
chlorinatod compound depends both on the number of chlorine atoms
that have been introduced into the molecule and on the specific
sites in tho molecular structure at which they are introduced.
The commercial material manufactured by Monsanto under its
registered trademark Aroclor consists of mixtures of these specific
chlorinated compounds. They are usually identified by the weight
percent of chlorino in tho total mixtures, e.g. Aroclor 1254 con
tains 54% chlorine. The Aroclors commonly used in the electrical
Industry are Aroclors' 1260, 1254, and 1242, .i
Aroclor 1242, used primarily in capacitors, contains about
7% of pentachloroblphenyls and higher. In September 1971 Monsanto
Introduced a new capacitor-grade askarel, Aroclor MCS-1016, which
is essentially Aroclor 1242 that has been specially processed to
reduce the content of pentachloroblphenyls and higher to less than
0.4%. \
.'
'
'
As a general rule, the nonflammability of liquid PCB's, their
vapors, and their arc-formed gaseous products is greater the higher
the degree of chlorination of the liquid. Studies by Monsanto
suggest that the resistance' of PCB's to degradation in the environ-
.
I
ment may also Increase with increasing chlorine content. Analytical
methods for low levels of PCB's (reported in parts per million or
parts per billion) in marine, aquatic, and wildlife environments
do not always idontlfy the specific compounds that are present,
but in its letter of February 19, 1970 to its customers, Monsanto
stated that "PCB's. with a chlorine content of less than 54% have
HONS 035139
not been found in tho environment and appear to proeent no potential
problem to the environment,"
Trademarks
'
Tho following trademarks are ueed by electrical manufacturer*
to doeignato the askarele u*od in their product*t
Manufacturer
..
Trademark
, Aerovox ..
-.*"Y .
Hyvol
1
Allis-Chalmers .
Chlorextol
American Corp, Cornell Dublller Genera], Electric
Abectol Dykenol Pyranol
Kuhlman Electric ItcgM-us Has ON Jr* I' ''`m*1'1
, Sangamo Electric . " :
Saf-T-Kuhl Elernex Diaclor
Wagner Electric
Noflamol
Wostlnghouse Electric
Inerteen
Toxic and Biological Effects of PCB'a
Systematic investigations of. the toxic and biological effect*
of PCB1* have been undertaken only within the past few yeara, and
the description and evaluation of the results is beyond the scope
of this report. Some investigators suggest that reports of certain
toxic reactions may be caused by highly poisonous compounds (e.g.
chlorinated dlbentofurans) found to be contaminants in some PCB
preparations. In the United Statas, medical records show that
over a nearly 40,-year period the only adverse health effect*
experienced by US workers exposed' to PCB's,either during the
manufacture of these liquids or of electrical equipment containing
these liquids ,have beon limited to occasional cases of non>chronlc
chloracne or other temporary skin lesions or Irritation*.
MOMS 035140
TRANSFORMERS
Definition ,
A trantformer it a devlco for transferring electrical energy from one
alternating current circuit, to another by electromagnetic meant. It hat no
moving parta and performs its function by linking two electric current
carrying circuits (the colls, usually copper wire) via a common magnetic
flux cnrrylng-clrcult (the core, usually a special grade of iron). A
transformer may be designed to effect a change In voltage or current from
one circuit to the other or simply to obtain electrical energy from one
electrical circuit without making a conductive connection between It and a
second electrical circuit.
'
The transmission of electrical energy from one point to another la
essentially the transmission of a required number of kilovolt-amperes (kva).
By means of transformers the kva's may be generated at a low voltage suitable
for the windings of generators, stepped up to higher voltages and lower
currents suitable for transmission of electricity over long distance wires,
and then at the desired destination stepped down to a lower voltage and
larger current suitable for utilisation by elactrlcally powered equipment.
The almost universal use of the alternating current system for the trans
mission and distribution of electrical energy Is largely due to this ability
of transformers to link up circuits of different voltages and currents. Thus
the generator, the transmission lines, the secondary distribution system, and
finally the great variety of ultimate loads can each be operated at the vol
tage most suitable .to it* particular function. Without this unique ability
of the transformer to adapt the circuit voltage to the Individual require
ments of the different parts of the system, the enormous development and
progress In the transmission and distribution of electrical energy during
the past 80 years would nAt have been possible.
MONS 035141
!!L
-11Why Askarels are Used in Transformers
Tho colli end coro of most transformers are enclosed In sealed metal
tanks that arc filled with an insulating liquid, usually mineral oil. Under
certain conditions of sudden power surges high-current electric arcs are
producod inside the transformer which can generate and ignite damnable and
explosive gas mixtures formed from the mineral oil and other cellulosic in sulating components in the transformer,
because of the nonflammability of liquid askarels, their vapors, and
their arc-formed gaseous products, transformers filled with askarels are
free of these fire end explosion hazards and may be used in locations where
failures of oil-insulated transformers would present a potential danger to
life and`property. This safety factor is the only advantage that askarelinsulated transformers have over oll-lnsulatcd transformers of the same else
and rating. The density of askarels is about 1,7 times that of mineral oil,
so askarcl-lnsulated transformers are heavier than their oil-filled counter
parts, Askarels themselves are more expensive than mineral oils, and their
solvent characteristics require tho use of more expensive insulation compo
nents on the Internal parts of the transformer, so the complete units are
more expensive. As a consequence, askarcl-lnsulated transformers have captured only
those market applications (less than 5%, but growing) where considerations .
of safety and reliability are paramount. Their use in such applications is
usually required or encouraged by the provisions of electrical codes, flro
underwriting policies, or governmental regulations,
jjotc: Prior to tho mld-1950's the liquid used In askarel-lnsulated
transformers was a SO-SO weight mixture of Aroclor 1260 (60% chlorine) with
trichlorobenzcnes; then the benzene component was changed to a mixture of
trl- and tetrachlorbenzenes; and In 1971 the Aroclor component was changed
to Aroclor 1254 (567. chlorine).
.
HONS 035142
Typos anti Applicat ions of Askarel-Insulated Transformer*
Thoto arc two broad classifications Of transformers: powor transformers, which era used to step up voltages; and distribution
transformers, which are used to step down voltogoe. The many typos of transformers that are Included within these two classifications
ero listed in Appendix 2, The applications that accompany the
listing apply only to those units of a given type that are manu
factured with askarel as the insulating liquid. Host units ofthe typos listed are still oll-lnsulatad.
We estimate that the total number of askarel-lnsulated units
that have been put Into service in the United States since 1932 is
125,000, and virtually all of these units are still In service.
The lifetime-before-fallure is often longer than 30 years, and
almost all units that do fail are rebuilt and returned to service.
The current production rate of new askarel-lnsulated transformers
unite is about 5,000 per year.
.
Host of these transformers are located Inside public, commer
cial, or industrial buildings; on the roof tops of such buildings;
or in close proximity to such buildings, and require no special
enclosures other than what are necessary to prevent accidental hazardous mechanical or electrical contact of persons with the
equipment, Howevor, the National Electrical Code does specify vaults for the Indoor installation of askarel-lnsulated transformers rated moro than 35,000 volts. Askarel-lnsulated transformers are,
limited by the clectrlal properties of these liquids to ratings
below 69,000 volts.
The amount of askarel used In various types of transformers
ranges from A0 to 500 gals. (516 to 6,A50 lbs.) with an average
of about 235 gals. (3,032 lbs.). During 1968, the last complete "normal" year for the electrical industry, the total amount of
MONS 036143
I'Cll's used in transformers was approximately 1.3 million gallons
(6.V thousand tons).
Prose nI A1 t.crna t ivcr. to Asharo 1-T.nsula tad Trans formers
If l'CU's wore to be no longer available for c losed-system
eloctrieal uses -- as they are no longer available from Monsanto for
open-system applications.-- what alternatives to askarcl-inculntcd
transformers could now bo supplied by the electrical industry, and
what would be the effect upon the user should askarel-insulated
transformers no longer be available either as new er replacement
units)
.
The only present alternatives to askoral-insulated transformers
aro oll-insnlatett transformers or dry-typo transformers (either
those open to the atmosphere or those that arc gas-filled and sealed)
' -i
'
'
A. Oil-insulated transformers
'
' 1. If one disregards safety considerations, there are
no technical reasons why oil-i.neuletod transformers
could, not be directly substituted for askarol'-insulatod
transformers. The size of the unit'would be unchanged;
, _ the weight and cost would be lesst
2. There arc legal restrictions' to such o diroct
substitution.
t . a. Some local regulations (e.g. Chicago) prohibit
the use of oll-inculuCed units in certain ioea-
. tlons whore askare1-insulated units are allowed,
b. Where ell-insulated transformers would not bo
specifically prohibited as^on-sltc replacements
for asharel-insulated units, the National ,
.Electrical Code imposes special restriction*
upon their mode of installation. Although
HONS 035m
14-
35,000 volt* mutt bo Installed In vaults,
oil oi1-Insula ted transformers require vaults,
' except that alternative fire protection arrange ments are permitted lor units rated not over .
. 600 volts. Assuming that space were available
Inside an existing building to accommodate theso special auxiliary safety provisions, the coat of their construction could range
from $5,000 to $50,000 per transformer, c, Oll-lnsulated units can be Installed outdoor*
. If they are suitably Isolated from flammable
structures or If these structures are suitably
safeguarded against fires originating in the
. transformers. The power output must then
be brought to the point of use Inside the
building via cables or Insulated buses, and
the cost of cable and bus Installation could
' also range from $5,000 to $50,000 per trans
former, The outdoor transformer would have to be of a higher rating than the Indoor one ' It would replace because of voltage drop and
- consequent power losses In the cable or bus
rune,
HOIS 035145
Dry-type transformers .
,
In most locations, dry-type transformers (either those
, 't,'
.
open to the atmosphero or.those that are gas-filled
and saeled) could not be directly substituted for askarel-insulated transformers. There ere several
restrictions to such a direct substitution:
-15-
I The provision!! oC tho National Electrical Code
'
are more stringent for certain classes of dry-
type transformers than for comparable askarel-
Insulated units.
1.
Present technology is not available for design
ing and manufacturing reliable dry-type trans formers above -MiSSiciS' KVA and/or 15 KV.
The reliability of dry-type transformers it less
than that of cpmparably rated liquid-insulated
transformers. Oil- and askarol-lnsulated units
show much greater resistance to switching and
lightning surges than do dry-type units. An EEI
survey of failures In network transformer banks
showed a 77. per year failure rate for dry-type
units compered to 0.27. for liquid-insulated
units. Furthermore, liquid-insulated transformers
have a much greater overload capability. Many
liquid-insulated units can sustain a 100% over
load for 8 hours and a 2007, overload for 2 hours.
These transformers are able to maintain continuity
of electrical service during periods of temporary
outage of related equipment. .
Some dry-type transformers are larger by 10 to 30%
than comparably rated liquid-insulated units, and
most are more expensive.
-
Dry-type transformers are noisier by 5-10 dB than
are liquid-insulated `transformers.
Becauso their insides require regular cleaning,
the malntonanco costs for opon dry-typo transformers
are higher than those f.or sealed dry-type transformers
HONS 0 3 5 1 4 6
-16-
or for liquid-insulated transformers, which aro
also sealed.
'
7. Open dry-type transformers, which are cheaper
than sealed dry-type transformers, cannot bo
used In certain corrosive or hazardous atmospheres,
e. e* on furnaces or on electrostatic precipitators
near hot stacks, ' '
*
Summary
.
'
1. For technical or legal reasons It would be Impossible
to replace most askarel-lnsulated transformers now
In sprvlce by oll-insulated units of equivalent
rating and reliability without major construction
changes that would be required to compensate for
the firo and'explosion resistance of the askarel-
lnsulated units,
.
2, For certain applications and locations, dry-type
transformers could replace askarel-lnsulated trans
formers, but with a significant reduction In system
' reliability,
MONS 035147
-I/-.
CM'AC ITOKS
Definition t
A capacitor is a device that stores electrical energy. It
consists o tvo motel surfaces or electrodes separated by an
insulating medium such as air, paper, plastic film, or oil. When s
voltage is applied across the electrodes, electrostatic energy is
stored in the insulating medium.
In typical industrial capacitors the electrode material is
aluminum foil and the Insulating medium or dielectric is paper
tissue and/or plastic film,which for many applications is impregnated
with a liquid dielectric. A liquid lmprcgnant is used to fill the
voids within the paper or plastic film structure, to fill the voids
between sheets, and to contribute to the capacitance or charge
carrying ability of the composite. Voids must be eliminated within
capacitors that are to be used above 200-300 volts, which exceeds
the dielectric breakdown strength of air.
In our definition of transformers we emphasised their Importance
in the transmission and distribution of electrical power (kilovolt
amperes) from the generating plant to the ultimate load. If the
load were purely resistive (e.g. an electric heating element) no
further modification of the power supply delivered to it would be
required. Other loads (e.g. induction motors) may require that
a portion of the kilovolt-amperes delivered to them be used to pro
vide e magnetising current, which does not contribute directly to
tho useful power output of the load. This portion of the total
kva delivered to the load la designated as reactive kilovolt-amperes
(kvsrs). It has been found moro economical to produce kvars from
total kva's near the point of load rather than near tho point of
kva generation, and capacitors provldo the most efficient vay of
HONS 0351A8
*ib-
offcctinc this transformation at the point of load*
Why Askarcls are Usod tn Capacitors
Prior to 1930 most liquid-filled capacitors were made with
mlnorel oil. The subsequent substitution.of askarels for mineral
oil mado possible significant technical improvements in the else,
reliability, and life of these capacitors.
-
' A. Site The single most Important property of a liquid to be usod in a' capacitor is its dielectric constant (the ratio of its ability to store electrostatic energy relative-to air). The dielectric constant of
capacitor-grade askarcl (Aroclor 1242) is 5.85 while that of mineral oil is 2.25. When capacitor'tissue is Impregnated with these liquids the dielectric constant of the paper-liquid composite is (.1 for
. askarel and 2,9 for mineral oil. Furthermore, because of the relatively close match between the dielectric constants of.cellulose, (6.6) and askarel
HONS 0 3 5 1 4 9
(5.85), it is possible to stress askarel-lmpregnated paper to ^00-500 volts/rail, while the stresses that can be applied to comparable paper-mlnoral oil
capacitors are limited to 300-350 volts/mll. The
combined effect of these technical advantages of askarels has been to permit a reduction of capacitor . slses to less than 147. of what theywero in 1924. In 1965 a new dielectric system consisting of paperI polypropylene fllm-askarol was i'ntroduced with stress capability up to 900 volts/mll, overall. Bealdos - favorable stress distributions, the ability of askarel --. . tn Increase, the dielectric strength of polypropylene
-i*-
Is partly responsible for this Improvement.
B Reliability end life
.
Askarels ore thermally and oxidatively more stable
than mineral oils, and dischargee, which can occur
In capacitors, are less likely to generate gases
from askarels than from mineral oils. The chemical
stability of askarels In the presence of capacitor
tissue and plastic films and the favorable stress
' '
distributions between solid and liquid referred to
above have made it possible to design low-cost
capacitors with a life expectancy of more than 10
.years life In lighting applications and more than
20 years In electric utility applications. In
each application the first-year failure rates are
less than 0.27.. This level of life and reliability
hod not boon achieved prior to the introduction of '
askarels. Furthermore, the non-flammability of
askarels Is greater than that of mineral oil, which
reduces the fire hazard that might otherwise
accompany those failures that result In' rupture of
the case,
1
'
Whereas the transformer manufacturer has had to
essentially "design around" the properties of
askarels In order to be able to take advantage of
the safety factor that they Impart to his equipment,
the capacitor manufacturer has been able to "design
with" the properties of askarels and obtain significant
technical Improvements along with tho Improved safety
factor. As a.result askarels have virtually supplanted mineral oils In more than 907, of the power and Industrial
OSTSCO SNOW
t
,
-20-
Note: Prior to 1952 the liquid used in askorel-lmprcgnatod capacitors was Aroclor 1254 (547. chlorine); it was then replaced by Aroclor 1242 (427. chlorine), which has better electrical properties end as notod in the. "Askarel" section, in September 1971 Monsanto Introduced e new capacitor-grade askarcl, Aroclor MCS-1016, which . Is a modified Aroclor 1242. Unlike askarel-lnsulated transformers, the liquid in askarel-impregnated capacitors contains only Aroclors
and does not contain added chlorobenzenes. Types and Applications of Askere1-impregnated Capacitors
The principal typos of askarel-impregnated capacitors and
.
their applications arc described in Appendix 3. Almost 60 million such capacitors are manufactured annually, most of them for first- time use. Unlike transformers, capacitors are not rebuilt and returned to service after failure. They are disposed of (see "Background" section, item concerning ANSI Committe C107) and
replacod by new capacitors. '
Capacitors used In lighting and air conditioning applications
contain 0.005 to
gels. (0.05 to 1.0 lbs.) of askarel per
unit. The largest power capacitors' contain about 6.7 gals (77 lbs.)
of askarel. The most popular size contains about 3,1 (36 lbs.)
The National Electrical Code requires that any Installation of
capacitors In which any single unit contains more than 3 gslloqp of combustible liquid shall be in a vault like that required for transformers. During 1968, the last complete,"normal" year for the'elee trleal industry, the total amount of ?CB's used In
capacitors was approximately 14.4 thousand tons.
MONS 035151
. If J'CU's wore to be no longer available for closcd-system 0 lee trlea 1 uses -- no (hey are no (longer available from Monsanto for open - cy o tern pp 1 i ca c ions -- uhnt alternatives to askarol-imprcgnatcd capacitors could now bo supplied by the electrical Industry, and what would be the effect upon the user should askarol-imprognatod
'capacitors no longer be available either os new or replacement units;
l'osoiblo alternatives to asknrel-imprcgriated capacitors are
copnclloro impregnated with mineral oil, or capacitors impregnated
with certain otliev liquids,
.
A, Mineral Oil
' Replacement of askarels by mineral oil would essentially
. return capacitor technology to its pro-1932 level. Some
specific consequences of such a replacement would bei
1. Safety. None of the possible liquid alternatives
to askarels arc nonflammable, and a fire haaard
would bo created by any capacitor failures that
,
were accompanied by rupture of the ease. Presently
the use of capacitors containing flammable liquid
is governed by the National Electrical Code 'Articles
A00 and 501.
' 2.' Si'/.c and Cost. A few specific examples wl.ll illustrate
the else and cost penalties associated with a switch
from askarel to mineral oil in capacitors. The nost popular sisod power capacitors today ere rated at
200 KVAR, If mineroT oil were substituted for
asknrcl the volume of the capacitor would be
t
. quadrupled and the direct labor and material costs
associated with its manufacture would lncrcdso by . 70'/.. Today power capacitors sre available, in A00 uv.\R
MONS 035152
KVAR because of increased heat dissipation probi
with Increased volume. In addition to increases in
direct costs, the power capacitor Industry would
face Increased capital expenses estimated at
$2,000,000 to provide the increased volume of
material at proJected.KVAR requirements.
Steel companies faced with increased slue, cost
and flammability of capacitor banks for induction heating furnaces would probably not install new
.induction heating capability. Utilities would
have difficulty with substation-size in crowded
. urban areas. An Increase in the size of capacitors
for air conditioning would not be critical.
In lighting applications a 3.75/,075 uf 540 VAC
rating for high output applications is typical.
If mineral oil were substituted for askarel, tho
capacitor would be 71% larger end materials would
cost 467. more. Lamp ballast manufacturers would
have to Increase the size of the ballast to accommo
date tho larger capacitor. This would change the
thermal performance of the unit and require U.L,
approval of new ballast designs. Lighting fixture
manufacturers would also face redesign costs to
take larger ballasts.
.
-
3, Reliability. Users of capacitors in all application
areas, have come to expect long life and very low
initial failure rates. The present performance stan
dards have been achieved after many years of field
testing and acceloratod testing by manufacturers and users., The reliability of dasigns containing
HONS 035153
-2 3mineral, oil in many applications would bo uncertain, Available records show that capacitor reliability prior to the fivallublllty of askarel vac only a fraction of what it is today, h. Replacement Market. The implications of changes in capacitor alee have been,d1scussed in terms of nev designs. In each major application area some capacitors arc sold for replacement business. Rover and induction heating capacitors are generally Installed in racks of a few to thousands of capa citors. It would not be possible to make simple substitutions for failed capacitors while main taining the system rating. In air conditioners replacement of failed capa citors might be as simple as installation of new brackets. On the other hand,' tight designs might not take a larger capacitor at all, Lighting systems would be seriously affected by increases in capacitor site. Larger replacement ballasts would not fit into existing fixtures without altered mounting arrangements. It is possible that space requirements would force complete replacement of lighting fixtures for the want of a replacement ballast. 5. Material Sources. Mineral oil is currently used in a relatively small number of specialty capaci tors. In this country there Is a single source of capacitor-grade mineral oil with limited facilities for acid refining of crudes from a single oil field. Increased demand would require
MONS 035154
expanded facilities end investment and considerable
development in defining technical requirements for capacitor-grade mineral oil. Efficient use of. mineral oil in capacitor design* would require higher density capacitor tissue . -
than is currently prqduced in this country. At
the least this would require extensive paper
machine modification. Capacitor winding techniques
and machines would need to bo developed for winding
tighter rolls.
'
Other Liquids
1, Castor Oil. The dielectric constant of castor
oil is ft.5 end this materiel is useful as an
.
impregnant in P.C. energy etorage capacitor*.
Howovcr, A.C. capacitors filled with this liquid
have relatively short lives and are not very stable
under A.Ci discharges and in the presence of water
derivable from the celluloslc paper.
2, plbutyl sebaento. This ester is especially useful
In high frequency parallel plate capacitors because
of Its low, flat loss characteristics over a broad
frequency range.' Xn this type of construction the
. liquid is the sole dielectric materiel. When used in conjunction with paper, this eater Is also
unstable. . 3, Silicone Fluids. These materials have a dielectric
constant of 2,7 and would generally be subject to .the same disadvantages as mineral oil'.
' .
Alternative Pe'slgns
'
- HONS 035155
In addition to liquid dielectric substitutes, olternotlves
to the paper-liquid dielectric might be considered. Those would Involve the use of plastic film coated with aluminum foil or vapor-deposited aluminum as electrodes. Since the free volume of the system Is less than that of paper the capacitance of the system Is less dependent on the dielectric constant of the liquid and the stress distribution between the plastic films and low dielectric constant liquids Is more closely balanced. Such dielectric systems are difficult to construct completely free of voids, It Is expected that several years will be required to achieve the required level of reliability In such dielectric systems
i
MQNS 035156
possmi.v: ^l^:vET.o)'N):^'^J, or new iNsm.ATm; uquids
The cost n.f niikarol liquids is shout $2.00 per gallon, compnrcd to about .
$0.30 per gallon lot mineral oil. Thus, long before there were any environ mental concerns about PCB's there wnc a strong economic incentive to find o.tber less-expensive insulating liquids with the d'oslrnblc characteristics
of asharels. Since the 1930's, at least 10 major chemical or electrical
companies have invested large amounts of time and money in this search, all ' with no success. There arc today no fluids that can be used as one-for-one
replacements for PCB's.
.
The continued search for new fluids would probably start with fluorochemicals.
Fluorochomicnls are nonflammable, nbntoxic, and as far as is presently known
represent no environmental hazard. High-boiling fluorochemicals might thus
be potential replacements for PCB's. Considerable laboratory study, over at
* least a one-year period, of the physical, chemical, and dielectric properties
of thoso materials would be required in order to identify specific candidate
materials.
-
At least another year would be required to develop a finished product based
upon a fluorochemical. On one hand, the physical and dielectric properties would certainly be sufficiently different so that substantial engineering redesign hy ' electrical manufacturers would bo required to accommodate a fluorochemical. On the other hand, a one-year lead time is needed to construct a chemical plant to
produce the identified fluorochemical in the millions of pounds that would
be required per year.
Furthermore, a significant program of environ
mental testing would be needed to ensure that the new material was.indeed not an ecological hazard. The foregoing arc -all highly optimistic time catima
The cost of manufacturing fluorochemicals is inherently high. Prices of high-boiling liquids are $10.- 15 per pound, or'higher. At best one would .hope
HONS 035157
that in sufficient volume the price might approach that of Teflon, currently
$3 * 4 per pound. Even this optimistic figure is approximately twenty times
the cost of PCB's, end since the value of FOB in.a transformer is roughly
one-tenth the total value of the transformer, the total cost of a fluoro-
chemlcal-lnsulated transformer would be at least three times that of an
equivalent askerel unit.
.
MQNS 035158
-28-
Appcndlx 1
ftombetshlp of ANSI Committee C107 on Use and Disposal of Askarel Deed In Electrical Eciulpment
Humber of Representatives
Organization Represented
2 Department of the Army
2.
. . Environmental Protection Agency
1 U.S. Department of Agriculture
l`
.
Tennessee Valley Authority
1 General Services Administration
.1
...................National Bureau of Standards
2 Certified Ballast Manufacturers Association
'1
. . Edison Electric Institute
1 Institute of Electronic & Electrical Engineers
5 National Electrical Manufacturers Association
2 Monsanto Company
2'
Commercial Waste Disposal Companies
1'
. Engineering Consulting Firm
'1 `
' .
Capacitor Manufacturer Serving as an Xndependet Member
HONS 035159
Appendix 2
.
Types of Askarel-Insulated Transformers
*. miribution Transformers
.,
1. Network (up to 2500 KVA)
2. Single- end three-phase (up to 2500 KVA)
3. Pole-mounted end station (up to 500 KVA)
.
'
The application of these transformers in power distribution systems
places a great premium upon their reliability and high overload capability
(which they share with comparable oil-insulated units): such as 1001
overload for 8 hours and 200% overload for 2. hours.
.A. Precipitation (high voltage DC)
These transformers are part of the power supply for electrostatic
precipitators, which are gaining increasing use in preventing air
pollution by particulate matter. They are generally Installed close
to hot gas stacks in an atmosphere that would be a fire hatard to
oil-insulated transformers and a corrosion hazard to open dry-type
transformers. Sealed dry-type transformers are impractical for high
voltage DC.
r.
' ', Power Trens former's
'
. *
1, Secondary substation
..
a. Load center units
' .
b. Secondary substation generation units
c. - Switchboard units
HONS 36l6
d. ' Integral unite
.*
e. Motor control units
.
These5comprise the largest group of askarel-insulated transformers,
and they find widespread application in the automobile, paper,
-30i,
,.
chemical, textile, (tecl, nonferrous metal, cement, mining, and
petroleum Industries. 'They are used in commercial and public
buildings, such as schools and hospitals; In defense and
nuclear energy Installations.; and by private and public
utilities.
2. Master unit substation
'
3. Primary unit substation
-
It. Limited ampere substation
3. Industrial furnace
.
, These transformers are used in the hot, dirty atmosphere In
proximity to glass melting and Induction furnaces, which require
high current, low voltage power supplies (more than 2500 KVA at
no more than 13.8 KV). Existing technology does not permit construc
tion of sealed dry-type transformers for these power ratings.
6. Rectifier
These transformers are used for large rolling mills and DC
industrial power supplies, and are covered by the same comments
given for industrial furnace transformers.
''
,
1. Transportation . a. Third rail
' ."
'
''
'
These transformers are used for rapid transit systems, and are
basically serving a rectifier function. .
b, Locomotive
MONS 035161
. . Prior to 1932, all on-board transformers were open dry-type.
Because of problems with them, railroads went to sskarel-insulatcd transformers. The changes in locomotive design since the 1930's
vould not now accomodate open dry-type transformers as replacements
for askarel unit*. -A recent trend hai been to replace aekarcl by
oil unite, and thle will continue unless new DOT regulations '
, require nonflammability.
'
8. Multiple-unit ear (MU)
. '
These transformers ere mounted under the flat-bed of passenger cars.
They ride along in this location,,about 8 Inches above the rail, at
speeds up to ISO mph. The transformer must be ruggedly built to with
stand the Impact of flying debris and constant vibration. Power to
the cars Is brought In through an overhead catenary and Is fed to the
underside of the cat where the transformer, controls, and propulsion
'equipment are located. Present voltage la 11 KV, but new electrification
is expected to be 25 KV.
.
Space and weight are critical In this application. There are only
about 33 Inches above the'rail. The width of the transformer Is
limited by the width of the car.
Only oil- or askarel-lnsulated units would provide the required
performance levels In the space available. As with locomotive applications
present DOT regulations do not restrict the use of flammable liquids,
and' the use of askarel units has been dictated largely by the economic
considerations of fire Insurance rates.
.
-
MONS 035162
-32-
''
' Appendix 3
Types of Askar'cl-Insulatcd Capacitor*
.
A* Hir.h Voltage Power , '
'
. Generally AC capaoltors are uted to Improve the power factor of
a circuit. Power factor la the ratio of true power In watte to the
apparent power aa obtained by multiplying the current flowing to the
load by the circuit voltage. The power factor correction can be made
directly at the load or at utility aubatatlona. In the latter cate
high.voltage unite will be dealgned for 4,600 to 13,800 volt service.
To the utility engineer the uae of capacltore lr purely a matter of
' econdralce. The main beneflta that result from the use of capacitors
arei
1, Reduction of losses associated with the delivery of electrl-
, cal power to the point of use.
-
2. Reduction of the Investment required In equipment for de
livering electrical power to the point of use, which may be
broken down Into: a. Reduction of current for the tame kilowatt load.
- b. . Reduction of the kva rating of equipment required to
. ' handle the eame kilowatt load.
' e. Reduction of the voltage drop for a given kilowatt load,
d. Control of. delivered voltage If the capacitor kva Is
varied.
.
Electric utilities also use capacitor banks In series with distri
bution circuits to Improve voltage regulation. High voltage utility
capacitors', low voltage power capacitors, and Induction heating
. capacitors are manufactured at tho rate of 200,000 per year, about 2 to
3% of which are for replacements', the balance are for new Installations.
HONS 0 3 5 1 6 3
33-
i B. y.QW Voltage Power
.
,
Capacitors Installed In Industrial plants at the demand site (typi
cally large motors and welders) are designed for 230 to 57$ volt service.
Capacitors Installed near the loads are the.most efficient way to supply
the magnetizing current to produce the flux necessary for the operation
of Inductive devices. Rates for the sale of power are generally struc
tured to encourage power factor correction at the site, eliminating the
noed for the electric utility to transmit both power-producing current
nd magnetizing current all the way from the generator to the plant site.
The same considerations apply to Induction heating applications, the
principal difference being that eapaeltors for this rapidly growing appll-
' cation are designed for operation at 960 to 9600 Hz.
C. . Lighting
Capacitors Improve the efficiency of lighting systems. A fluorescent
or mercury vapor lamp can be ballasted without the use of a capacitor, but
the power factor of the lighting system would then be in the range of SO
to 60%. For commercial or Industrial lighting with either fluorescent or
high Intensity discharge lamps, the use of a capacitor In the circuit
provides part of the lamp ballasting and brings system power factor Into
the range of 90 to 9$%. The current market for these applications Is
about 66,000,000 units annually of which about 10% are estimated to be
replacement ballasts.
-
1). Air Conditioning
'
, MONS 035166
As In the lighting applications, the capacitor Improves system effi
ciency. Air conditioners could be made to operate without capacitors,
as do home refrigerators, but because of the higher capacity required for current
air conditioners, the resultant line/would virtually eliminate homo "plug
in's" and would still further overburden a seriously threatened national
power network. Almost ell air conditioner pump motors are of the split
winding type on which the capacitor provides phase differential for the
so-called start winding,
thus delivering good starting torque. The
proper size capacitor permits high <907. ) power factor after start-up.
The current market for this application Is about 12,000,000 units an
nually, with about 57. of these estimated to be for replacement usage.
Industrial Electronics
This market category Is a catchall covering many varied applications,
two Important ones being motor run and power supply applications. Motor
run applications are for pumps, fans, and farm feed equipment, and do
not differ significantly from air conditioning applications. The power
supply market usee capacitors principally to provide high power factor,
but through careful design the capacitor can also provide wave shaping
where desired. The market is estimated at 23,000,000 units per year
with no estimate as to the relative size of the replacement market.
MONS 035165