CHAPTER 39
1965 Guide And Data Boole
Although only one steam-jet ejector is shown in FigB. 1 or 2,
more than one ejector can be used in parallel, discharging into
a common condenser. A common evaporator cannot be used.
plnstead, an evaporator containing multiple compartments
capable of being separated by water legs equal to the pressure
difference between the evaporator and condenser must be
'."employed/ .
.
Steam-jet Ejector
Rg. 1 .... Steam-Jet Refrigeration System with Surface Condenser'
- Hie design of an evaporator requires the water to bedis^
tributed in small droplets or thin sheets so that the main body
of the water can attain equilibrium temperature by the time
it reaches the bottom of the evaporator. The vapor space in
the evaporator must provide volume for the vapor to freely
separate from the liquid at a sufficiently low velocity to pre
vent liquid carryover into the booster suction. Spray systems
are more susceptible to water carryover problems than cas?
cade type systems. *
<>*
- It is important to keep pressure losses to a minimum be
tween the point of vapor release from the water and the steam
ejector suction, as any loss will require additional compres
sion. A pressure loss of only 0.0056 psi (0.156 in. of water) wiH
increase the required temperature lift by 1 F deg. This.is a 2
percent lift increase in a typical application. As ejectors are
inherently inefficient compression devices, it' is important,to
minimize the compression work for maximum efficiency.-* i ,:
Evaporators can be further divided into two types:
1. The open chilled water system in which the refrigerant water from the evaporator is circulated directly to the cooling bad, such
as heat exchangers or other equipment which must be cooled. 2. The dosed chiUed water system in which the refrigerant.water
is recirculated within the evaporator over a coil or other heat transfer device through which is circulated another Quid (water
or brine is commonly used) which never mixes with therefrigerant water, and which in turn is pumped to the cooling load. .
0 -. -The steam-jet ejector is the heart of the steam-jet refrigera tion cycle. The characteristics of this component have a major effect on the operating cost of the system and the size of both the condenser and condenser cooling water system. A steam ejector is shown in Fig. 3. The terminology, of the Heat'Exchange Institute b given, biit in addition, the' sections are identified functionally. The high-pressure steam which b used to energize the ejector b called the primary fluid or motive steam. .The induced stream, which b to be raised to a higher pressure level, b the secondary' fluid and is'often referred to as .vapor. Hie motive steam is expanded through' a converging-diverging nozzle to velocities of the order of 4000 fpsi The corresponding nozzle presure ratio b very high For example, a nozzle expanding 150 psia motive steam to an evaporator pressure of 0.30 in. of-mercury absolute (45 F chilled water temperature) will have a pressure ratio of about 1000. Nozzle-pressure ratios of less than 200 are'uncommon due to poor ejector efficiency when operating at low steam pressures. The high-velocity steam issuing1 from `the''nozzle entrains the water vapor in the suction chamber,- 'and'the two 8treams''mix at constant momentum in the mixing section which b-typically conical in shape. Theoretically, mixing is assumed to take place at constant pressure. This has been confirmed;by test. For a typical steam-jet ejector in a re frigeration-cycle, the mean velocity of the mixture will be supersonic'(after mixing b complete at Siation 1 of Fig. 3). In tire constant area throat section this supersonic mixture undergoes a static pressure rise through a complex shock
The open chilled water system is more efficient since one less
stage of heat transfer is required. Actually, for the Bam'e
rhilbH water temperature the refrigerant water temperature
(Le., evaporator) can be 5 to 10 F deg higher using.the open
syst&n.
'
1'
Evaporator freeze-up may occur in steam-jet syBternswhen
certain control malfunctions occur. The open system has two
distinct advantages in such a situation. First, the 5 to 10 F
deg higher refrigerant water temperature means -that the
system has a greater safety margin above the possible freeze
level. Second, should ` freeze-up actually occur, there'is no
danger of tube rupture which is certain to occur in theclosed
system. However, despite these disadvantages, some applica
tions necessitate the use of a closed water-system in order to
isolate the chilled water system/due to somespecial process
requirement
The open system must be'carefully designed to avoid leaks.1
It is recommended that the chilled water in open systems be
pumped sufficiently above atmospheric pressure so thafthe
water returning to the evaporator will-be-at 1 .or 2>psig.
This will prevent air leaking into the-pressure ride of.thf
system and also will prevent vapor lock in;the piping..The
returning water is introduced into the-evaporator through !a
back-pressure valve in such a case.
Rg. 2 .... Steam-Jet Refrigeration System with Barometric Condenser
Steam-Jet; Refrigeration. Equipment
657
wave in which the mixture velocity-b decelerated from a supersonic to a subsonic velocity..Thb process actually, takes
dfotanw* to be completed and in practice occurs between Station 1 and 2. .The major portion of the ejector pressure rise actually occurs between these two. stations. The'subsonic diffuser b typical of all conical, diffusers:and continues to decelerate the mixture to the design exit velocityat Station 3,
Condenser
,
.
The can:be one of three baric types:'(1) a-conventional surface condenser,- (2) an evaporative condenser; or (3) a barometric condenser.
The conventional surface condenser b commonly employed befflniM of its compact size and ability to be located anywhere,' inciting inside a building (Fig. 1). When a natural supply, of cooling water b. not available (Le.-river, well, ocean, etc.), it b.necessary-to.employ a cooling tower.-Use of a-cooling tower wifl raise the condensing temperature above that which would be necessary if either an evaporatiTO'or'barometric pnfyfcnspr were used. Hus means that the steam consumption will be correspondingly higher, and a larger surface condenser and cooling water system will be necessary. - . ............
The evaporative condenser contains tubes in.which.the steam.from the ejector condenses. Forced.air is.drawn over the tube bundle upon which water b sprayed or otherwise db-,, tributed to produce the condensing effect through .vaporiza-. tion of water from the outer tube surface..Such condensers were used in railway .car steam-jet refrigeration unite of 5 to 7, tons capacity,during the.late 1930's and.are now being made available in more modern, larger capacity .units.1 However,, since such condensers cannot be located indoors, they are limited to outdoor installslions.-The. evaporative condenser operates at a condensing temperature 3 to 8 F deg below that of a surface condenser with cooling tower and .this in turnresults in'a favorable decrease in steam consumption. - The barometric or contact mndenser is used to advantage, in those installations which do not have space limitations.(pri-. marily vertical), and.where.it.b economically/feasible.to, treat the evaporator and boiler water on a onoe-through basis' (Fig.' 2). It has'low first cost, and, since,cooling water mixea directly with tee steam to condense it, thb results in'a closer/ temperature.of approach between the cooling water and'the con'denring temperature than would be found in eithera sur face or evaporative condenser. A barometric'condenser will re quire an air ejector'of considerably huger capacity'to maintain condenser vacuum due to additional air and noncondensablegas load that will be found absorbed in the cooling water that enters tins type of condenser. In the majority of comfort
air conditioning-applications, barometric condensers are not
employed, but they, have found acceptance in.industrial and
other special applications. -
* ..........
Air Ejector
The air or noncondensable gas ejector typically employs two small steam powered ejectors operating in series.' An inter- and after-condenser b often employed to improve economy. In-a tight system, an air ejector unit will have a capacity of 0.1 lb of air per ton of refrigeration. However,'in many installations, particularly batch process applications, evacuation time of the system-may be the governing factor in sizing the air ejector package.
Controls . -
The controls of a steam-jet unit are usually relatively simple as compared to other types' of refrigeration systems. The evaporator water level and the condenser hot-well level are usually controlled by liquid level control devices suchas float valves. A thermostatic control of the chilled water tempera-' tures can be applied to operate the steam-jet unit' .(or in,' multiple ejector applications sequential activation) in an off mode.
DESIGN CONSIDERATION
Not much material on the physical design of efficient steam:
ejectors has been published. The majority of papers in the
literature describe' the best ejector of a particular investigative
series, but unfortunately these have rarely, if ever, been' as'
efficient as commercially available ejectors.*-*-4 It'b therefore
undesirable to utilize or rely upon the design data generally'
found in the literature as a basis for an'efficient ejector'
design. Nevertheless, much valuable work b recorded in the'
literature, and thb contributes toward a better understanding'
of ejector design problems. The reluctance of ejectormanu
facturers to publbh design data b understandable,' since'these'
concerns have.evoived their designs through decades of costly'
experimentation. Only through relative' secrecy can- they'
realize a return'on the'investment required to obtain their'
knowledge. Thb implies that ejector design b more of an
art than a science and thb is, in fact, the situation.at the,
moment. A major contribution to the science of ejector'design'
has been.the paper by Keenan, Neumann, and Lustwerk.*
While thb b a one-dimensional ideal analysb, it b very useful:
in describing a logical mathematical model of ejector opera
tion.
- .
: >iU
Nozzle
. The motive steam nozzle-has a' characteristic convergent^,
divergent shape. Its throat b sized to give the desired steam
flow at the design inlet steam conditions. The nozzle's diver-'
gent section b typically conical in shape and the theoretical -
area ratio -(cone-outlet area to the-throat area).-b found;
through .conventional-supersonic flow equations.* The-cone;
nglpg (total -. included angle) employed - in the - divergent >
nozzle cone range from 8 to 15 deg, with 10-12 deg being ^
most common..
`
The theoretical area ratio and an assumed.design divergent *
cone angle-will define the theoretical length. However,- ex---
perience has shown that in practice ,the cone length at. the i
design cone angle should be reduced to 70-80 percent of the
theoretical length for a broader efficiency.characteristic ohthe}
ejector. Thb arises from the necessity of the > ejector- ,to
operate at off-design conditions. It has been found*, that it bv
more efficient to operate the ejector when,the last portion off
the expansion process in.the divergent nozzle section takes,-
/