CHAPTER 18
1956 Guide
Substituting in Equation 1
p = 120."" (68-3 ~ 3M)
= 243,000 lb. (
1.00[70 -- (--10)11000
Example 2: What would be the fuel cost to heat the building in Example 1 during an average heating season, using stoker-fired bituminous coal at $14.00 per ton having a calorific value of 13,000 Btu per lb, assuming that the seasonal efficiency
of the system is 65 percent?
Solution: Substituting in Equation 1
.
F
=
120,000 (68.3 - 36.4) 5088 = 28,800 lb. 0.65(70 - (-10)113,000
The fuel cost is then (28,800 4- 2000) (14) = $201.00
Example 8: What will be the estimated fuel cost per year of heating a building with gas, assuming that the calculated hourly heat loss is 92,000 Btu based on 0 F, which includes 26,000 Btu for infiltration? The design temperatures are 0 F and 72 F. The normal heating season is 210 days, and the average outside temperature during the heating season is 36.4 F. The seasonal efficiency will be 80 percent. The heating plant will be thermostatically controlled, and a temperature of 65 F will be maintained from 11 p.m. to 7 a.m. Assume that the price of gasis7.5 cents per 100,000 Btu of fuel consumption, and disregard the loss of neat through open windows and
doors.
Solution: The average hourly temperature is
i
(72 X 16) + (65 X 8) t. = 24 = 69.7 F.
The maximum hourly heat loss will be h
II = 92,000 Btu.
The seasonal heat loss is
92,000 (69.7 - 36.4) X 24 X 210 = 2697 hundred thousand Btu.
100,000 X 0.80 X (72 - 0)
The estimated seasonal fuel cost will be
2697 X $0,075 = $202.00
It should be noted that savings from night setback may not result as calculated. Room temperature may not decrease and combustion efficiency may be poor during morning pickup. See Reference 8.
Several time-saving procedures have been devised for quickly estimating the hourly Btu loss of one and two-story residences in order that fuel estimates can be predicted more quickly from Equation 1. A graphical method of calculating heat losses has been developed9 which makes pos sible a quick solution if the gross wall, ceiling, or floor areas and respective transmission coefficients are known.
The Federal Housing Administration has originated a short-cut formula for residential heat loss determinations which makes use of the floor area and three selected transmission coefficients. The formula was developed to apply to detached houses approximately rectangular in shape with total exterior door and window areas equal to about 25 percent of the floor area, and with a floor area not greater than about 1500 sq ft. Equation 2 is for a one-story residence, and Equation 3 is intended for two-story structures.
Hi = A (G + 17. + 17. + l/i) (fi - f) H, = A (G + 1.2 V, + 0.5(7. + 0.5 U,) d - f.)
,
(3)
Estimating Fuel Consumption for Space Heating
449
where
Hi = heat loss from one-story residence, Btu per hour. Hi = heat loss from two-story residence, Btu per hour.
A = floor area, square feet, measured to the inside faces of enclosing walls and is the sum of the following areas: (1) all the area on each principal floor level; (2) the area of all finished habitable attic rooms, including bath rooms, toilet compartments, closets, and halls; (3) all other areas intended to be heated and not located in the basement.
<7 = glass and infiltration factor for ordinary construction: (0.45 for no weather stripping or storm windows), (0.40 for weatherstripping), (0.30 for storm windows with or without weatherstripping).
[/. = coefficient of transmission for outside wall.
Ut = coefficient of transmission for ceiling. Ui = coefficient of transmission for floor. Id = inside design temperature, Fahrenheit degrees. to = outside design temperature, Fahrenheit degrees.
Notes for application of Equations 2 and S.
1. The calculation of heat loss from heated spaces into adjacent spaces such as attics, basementless areas, and heated or unheated garages shall be based on the assumption that the temperature of such adjacent spaces is the same as the outside design temperature.
2. For all floors over basements or other warmed spaces assume TJt = 0.
3. For structures having concrete slab floors laid on the ground a modified appli cation of the formula may be made. Assume TJt = 0 and calculate the heat loss in accordance with the checkformula. Then add the slab loss determined in accordance with the procedure developed by the National Bureau of Standards and described in BMS Report 103.
4. No basement area is to be included in the formula calculation. If finished habitable rooms in the basement are to be heated, the additional heat loss should be calculated separately and added to the amount obtained by the formula.
Both the graphical method9 and FHA formulas, when used within the limitations established, have been found to give reasonably accurate results' for the average residence, but if precise estimates are required, the procedure outlined in Chapter 12 should be used.
In the case of gravity warm air heating installations, the load was for merly expressed in square inches of leader pipe which can be converted into Btu per hour by multiplying the square inches of leader area by 111, 167, and 200 for first, second, and third floors, respectively.
DEGREE-DAY METHOD
This method is based on consumption data which have been taken from buildings in operation, and the results have been computed on a degree-day basis. While this method may not be as theoretically correct as the Cal culated Heat Loss Method, it is considered by many to be of more value for practical use.
The amount of heat required in a building depends upon the outdoor temperature, if other variables are eliminated. Theoretically it is pro portional to the difference between the outdoor and indoor temperatures. The American Gas Association10 determined from records in the heating of residences that the gas consumption varied directly as the degree-days, or as the difference between 65 F and the mean outside temperature. In other words, on a day when the mean temperature was 20 deg below 65 F, twice as much gas was consumed as on a day when the temperature was 10