Document OEV0BNm3o5JE9E2ZK50qJa5zj

American Society of Heating and Ventilating Engineers Guide, 1934 the top floor, that the length of run from the tank to the farthest fixture is 200 ft, equiva lent length of fittings 100 ft, and the pressure required at the fixture is 7 lb. The 30-ft head is equal to a static pressure of 0.43 X 30 or 12.9 lb per square inch and to maintain a pressure of 7 lb at the highest fixtures the drop allowable in pressure is 12.9 -- 7.0 lb or 5.9 lb. As the total equivalent run is 300 ft, this is a drop per 100 ft of 1.97 lb, or practically 2 lb. Therefore, all risers and mains from the top floor back to the v Table 4. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals Riser No, 1 Floor of Bldg. Fixtures on Floor GPM PER Fext. Max. Fixt. GPM Probable Use (per cent) Probable Fixt. GPM Probable Allowable Riser GPM Drop Lb per 100 ft Pipe Size In. 1st IS.S. '4, . 4 ZOO 2nd 1S.S. 4 4 100 3rd 1 s. s. .4 3 4th 10 Lav. 3 13 5th 4 W. C. 50 2 U. 40 6 3 Lav. 16 3 4 12 ' 30 .. .42 200 80 280 9 51 80 45 . 40 45 4. 4 4 8 10 10 19 19 112 . 22 134 30 x . .30 ' A *30- K 30 1 30 2 6th 4 W.C; 50 2 Xj. 40 12 3 Lav. 3 19 200 80 560 25 9 60 42 140 25 165 30 2 7th 4 W. C. 50 2 U. 40 18 . 3 Lav. .. ...... 3 22 200 80 840 18 9 69 40 151 28 179 30 . 2M 8th . 4 W. C. . 50 2 U. 40 200 80 24 1120 15 3 Lav. - 3 9 168 25 78 40 31 199. . :--r-- 24 tank must be sized on the basis of a drop of 21b per 100 ft. Tables 4; 5, 6 and 7 showthe schedule for Risers Nos. 1, 2 and 3 with the maximum possible flow taken from Table 1, the percentage of use at the peak taken from Fig. 1 and the maximum probable flow at the peak worked out for each portion of the riser, the riser sizes being taken from Table 2 as far as possible and from Fig. 3 where the amounts exceed the values given in this table; a drop of 30 lb per 100 ft is used except on the riser from the top floor back to the tank where 2 lb per 100 ft is the allowable limit. ' : The reduction in pipe size which would occur if flush tank water-closets were used on the top floor and only 3 lb pressure used on the fixtures is given in Tables 8 and 9. 556 Chapter 39-^Water Supply Piping tloor when a house tank is the---s-o--u--r-c--e--o--f wa..tteMr purceisusyurae.ie suDstituted'O' n the uppermost If it is now assumed that Riser No. 1 is to be fed from the bottom and the minimum street pressure is 75 lb with the top fixture of the riser 80 ft above the main, the problem Table 5. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals Riser No. S Floor of Blog. Fixture 5 on Floor GPM . PER Fixt. 1st 1 w. c. 50 2nd 2 W. C. 1 u. 50 40 4 1 Lav. 3 3rd 4 W. C. 50 2 U. 40 10 3 Lav. 3 4 4 W. C. ; 2 u. 16 3 Lav. 7 50 40 3 6 W. C. 22 . 4 Lav. 11 50 3 6 W. C. 28 4 Lav. 15 -___ 7th 6 W. C. 34 4 Lav. 19 8th 6 W. C. 40 4 Lav. 23 50 3 50 3 50 3 Max. Fixt. GPM .- 50 100 40 190 3 200 SO 470 9 12 200 80 750 9 21 300 1050 12 33 300 1350 12 45 300 1650 12 57 300 1950 12 69 Probabl b Use (per ceni0 Probabl.b Fixt.GPM Probabl b Allowable Riser Drop . gpm LBPBR 100 Ft Pipe Size Itr. 100 50 50 . 30 1% 50 95 100 3 98 . 30 141 70 8 149 30. : ix . 30 2 20 150 70 14 164 15 157 ... 48 16 173 12 162 45 20 182 10 165 . 42 24 189 9 175 40 27 202 30 2 30 2 30 2 - 30 2X 24 0.43 lb X 80 or 34.4 lb 557 per 100 ft.