Shakeouts Foundry
Spray coating
Tanks, open surface Tumbling mills
Hollow trunnion type
Tumbling mills, drums, cages, barrels
Enclosure
Booth--operator in side
Booth-operator outside
Booth--downdraft
(See Table 47-L)
200 fpm through all openings in enclosure, but not less than 200 cfm per sq ft of grate area
100-200 fpm at booth cross sec tion
150-200 fpm at booth cross sec tion
100-200 fpm downdraft
Exhaust connection by manufacturer
Enclosure
Use branch diameter same size as exhaust outlet For round mills branch diam should be V, diam of mill, for square mills branch diam should be 1 in plus /, side dimension of mill
400 fpm through openings but not less than 75 cfm sq ft plan area
Welding
Local hood with flange
Downdraft bench Booth
6 in from arc-150 cfm 6-9 in from arc-275 cfm 8-10 in from arc-425 cfm 10-12 in from arc-600 cfm 150-250 cfm per sq ft gnlle area 100 fpm at booth face
Woodworking
Miscellaneous Packaging machines, granulators, enclosed dust producing units Packag ing, weighing, container filling, inspection
(See Table 47-K) Complete enclosure
Booth Downdraft
100-400 fpm indraft through in spection or working openings, but not less than 25 cfm per sq ft of enclosed plan area
50-150 cfm per sq ft of open face area
75-150 cfm per sq ft of dust pro ducing plan area
From ASHRAE Guide and Data Book, 1970, Chapter 20 Uted by permission
3,500 1,500-2,000 1500-2,000 1,500-2,000
3,500-5,000
3,500
2,000-4.000 2,000 2,000 3,000 3,000 3,500
Use higher ventilation rate for small booths 4 sq ft or less
Where equipment is enclosed and dust tight dunng rotation, enclosure may not be needed if feed and discharge opera tions can be otherwise run