Document O8nvxyDy1G9aor43z5DeMqoX
164
CHAPTER 12
1959 Guide
A
Boom or Spece
Bedroom A and Closet
Table 9 .... Heat Loss Calculation Sheet for Uninsulated Residence (Fig. 1)
B C0 E F
fart of Stmdvn or InfVfrafioo Air Cbongot
Walls Glass Ceiling Infiltration (34)*
Ne# Area or Air Volume
238 sq ft 40 sq ft
252 sq ft 1510 cfnk
CoeffxMAf
0.29 0.45 0.74 0.018*
Temp. Oiff.*
80 80 39.8d . 80
Heel Ion (flh per hour)
5520 1440 7410 2180
Bedroom B and . Closet
Walls Glass Ceiling
Infiltration (34)*
40 sq ft 170 sq ft 1020 cfhk
0.29 0.45
0.74 0.018*
80 80
39.8d 80
1440 5000 1470
Bedroom C and Closet.
Walla Glass Ceiling
infiltration (3i)*
114 sq ft 27 sq ft
129 sq ft 874 efhk
0.29 0.45 0.74
0.018*
80 80 39.8d 80
970 3800 1260
Bedroom D and Closet
Bathroom.1
Bathroom 2
Walls Glass Ceiling Floor over garage Infiltration (34)
Walls Glass Ceiling Infiltration (1)*
Walls Glass Celling Floor over garage Infiltration (I)*
118 sq ft 20 sq ft 110 sq ft 110 sq ft 660 cfh
30 sq ft 14 sq ft 55 sq ft 440 cfnk
79 sq ft 9 sq ft
35 sq ft . 35 sq ft 280 cfnk
0.29 0.45 0.74 . 0.26 0.018*
0.29 0.45 0.74 0.018*
0.26 0.45 0.74 0.26 ' 0.018
80 80 39.8d 35*
so.
80 80 39.8d 80
80 80 39.8d 35* 80
2740 720
3240
950
690 500 1620 630
1640 320 1060 320* 400
Living Room
Walls Walls (adioining garage) Glass Floor Infiltration (l%)h
267 sq ft 94 sq ft 50 sq ft
294 sq ft 3745 ctnk
0.29 0.39* 0.45
0.018*
80 35* 80
80
1280* 1800
5400
Dining Room
Walls Glass (doors) Glass (windows) Floor Infiltration OH)*
166 sq ft 35 sq ft 20 sq ft 168 sq ft 2140 cfhk
0.29 0.85 0.45
0.018*
80 80 80
80
2380 720
3080
Kitchen .and Entrance to Garage
Walls Walls (adioining garage) Glass Door Floor
Infiltration (1H)}
51 sq ft 18 sq ft 17 sq' ft 125 sq ft 1595 cfhk
0.29 0.39* 0.45 0.51
0.018*
80 35* 80 35
80
700* 650 300
2300
Lavette and .Vestibule
Walls Walls-(adioining garage) , Glass Door Floor
Infiltration (lK)k
82 sq ft 85 sq ft
9 sq ft 19 sq ft 30 sq ft 383 cfnk
0.29 0.39* 0.45 0.51
0.018*
80 35* 80 80
80
1160* 320 780
550
Entrance Hall
Walls Door Ceiling' Infiltration (2)1
39 sq ft
21 sq ft 87 sq ft 1110 cfhk
0.29 0.38 0.74 0,018*
80 80 39.8d 80
900 640 2560 1600
'
Garage.
Walls Glass Doors
Infiltration (1M)" Floor Gain adjoining rooms
167 sq ft 53 sq ft 44 so ft 2360 cfhk 29 ft*
0.29
1.13 0.51 0.018* 0.81
45* 45 45 45 45
2180 2700
1910
-4420*
Recreation .Room*
Walls Glass Floor
Infiltration (!)
220 sq ft 8 sq ft
287 sq ft 2010 cfnk
0.10 1.13 0.10 0.018*
38 80 20 80
840 2890
TOTAL
G Totaii (Bfu per hour) 16,550 11,530 8,680
8,610 3,440
3,740
14,680
10,030
6,170
4,710 5,700
4,450 5,020 103,310
Heating Load
165
Notes for Table 9 ... Heat Loss Calculation for Uninsulated Residence (Fig. 1)
. nn.c indoor-outdoor temperature difference is 70-- (--10} or 80 F except 7here otherwise noted. k Volume of infiltration, cfh = (do. air changes) x (floor or ceiling area) x (ceiling height). * From Equation Sa. d The ceiling heat losses are calculated by estimating the attic temperature and then calculating the loss through the ceiling Rising the proper temperature difference. This unheated attic is not ventilated during winter months. The attic temperature is estimated from Equation 1 to be 30.2 F when the outdoor temperature is --10 F and room temperature is 70 F. The temperature difference is then 70--30.2 or 39.8 deg. For the insulated residence, attic temperature becomes 4.6 F and temperature difference 70--4.6 = 65.4 deg. * Temperature in garage assumed to be 35 F. 1 Coefficient for wall adjoining garage calculated on basis of metal lath and plaster on both sides of studs (JJ " 0.39). * One-half of value from Table 4, Chapter 11, for storm windows or weatherstripping. k Exposed on two sides, weatherstripped windows offset by fireplace. Use 1 1 Window on one side weatherstripped but double-doors are hard to close tightly. Hence, conservative value of 1)41 Assuming kitchen vent, door to vestibule usually open, allow full table value of 1Hk One-half value in Table 4, Chapter 11, increased to 1\4 by nearby outside door in vestibule. 1 Full value in Table 4, Chapter 11, to allow for frequent opening of outside door. m Two sides exposed, large doors but large volume. Use value IK as given in Table 4, Chapter 11. a Two small unweatheratripped windows in protected location, but fireplace, indicate 1 change. * Heat losses from these rooms into garage are heat gains for garage. i Neglect heat loss to basement, as losses from boiler, piping, etc., will probably keep basement near, if not above, 70 F. ' Upstairs hall ceiling figures with downstairs. Heat should be provided downstairs for both. * Linear feet of exposed edge.
Fig. 1 .... Floor Plans of Residence
rage and basement (1.13; from Chapter 9, Table 18, U is 1.13 for all glass and the application factor is 1X10). French doors in dining room 50percent glass, no storm doors (085; from Chapter 9, Table 18, U is 1.13.for all glass; by interpolation the applica tion factor is 0.75).
Floor (Bedroom D): Maple finish flooring on yellow pine sub flooring; metal lath and plaster ceiling below (0.26).
Floor (Basement and Garage): 4 in. stone concrete on 3 in. cinder concrete (0.10).
Solution; The calculations for this problem are given in Table 9, and a summary of the results in Table 10. The values in col umn F of Table 9 were obtained by multiplying together the figures in columns C, D, and E. The heat losses are calculated to the nearest 10 Btu. See reference notes for Table 8 for fur ther explanation of data.
Attention is called to the summary of heat losses (Table 10) for the uninsulated residence. As storm windows are used in this instance the glass and door transmission heat losses of 198 per
cent are relatively small. The infiltration losses of 14.0 percent are nlgn comparatively small because the storm windows axe equivalent to weatherstripping. In this problem, the wall, ceiling, and floor transmission losses comprise 662 percent of the total.
Example 7: Calculate the heat loss of residence shown in Fig. 1 based on the same conditions as in Example 6 but having construction improved or insulated to obtain coefficients as fol lows:
Walls, 0.13: WaU of Dormer over Garage, 0.12; Attic Walls, 028; Walls Adjoining Garage, 0.18; Basement Walls (Recrea tion Room), 0.10.
Roof, 083.
Ceiling (Second Floor), 0.15.
Windows (Same as in Example 6). Floor (Bedroom D), 0.18. Solution: Hie procedure for calculating the beat losses is similar to that for Example 6. A summary of the results is given in Table 11.