Document O3xLJzvzyqv2ZeNb1NGbBG7ej
HEATING i VENTILATING :AIR CONDITIONING GUIDE 1940
It is important to keep the lowest points of the steam mains and heating units sufficiently above the water line of the boiler to prevent flooding. The minimum water line difference depends on the initial steam pressure and piping pressure drop plus a safety factor for heating up.
Steam pressure at
end of mam
i Return water
Water Hne of boOer
line
^-4-**Rlse.water II tine difference
Level -- >Vetreturn
Fig. 5. Difference in Steam Pressure on Water in Boiler and at End of Steam Main -
Referring to Fig. 5 it will be noted that the water in the wet return is a U-shaped container, with the boiler steam pressure on the top of the water at one end and the steam main pressure on the top of the water at the other end. The difference between these two pressures is the pressure drop in the system, the friction and resistance to the flow of steam in passing from the boiler to the far end of the main and the pressure reduction in consequence of the condensation occurring in the system. The water in the far end will
CHAPTER 15. STEAM HEATINC SYSTEMS
would require lA of 28 in., or 14 in. for the difference in steam pressure, 3 in; for the flow
through the return, 4 in. to operate the check, and 6 in. for a factor of safety, making a total of 27 in. as the required distance. Higher pressure drops would increase the distance accordingly.
GRAVITY TWO-PIPE AIR-VENT SYSTEMS
The gravity two-pipe system indicated in Fig. 6, is now considered obsolete although many of these systems are still in use in older buildings. The same general principles governing its piping design are used when connecting radiators as in other types of gravity systems where they must discharge their condensation to the wet return pipe. Separate supply and return mains and connections are required for each heating unit. Radiator valves are required in both the supply and return connection to the radiator, and air valves are installed on the heating units and the mains. Where the return main has to be located high to function as a
rise sufficiently to overcome this difference in order to balance the pressures,-and it will rise far enough to produce a flow through the return pipe and overcome the resistance of
check valves if installed.
If a one-pipe steam system is designed, for example, for a total pressure drop of Ys lb,
and utilizes an Underwriters' Loop instead of a check valve on the return, the rise in the water level at the far end of the return due to the difference in steam pressure would be
Ys of 28 in. (28 in. head being equal to one pound per square inch), or 3Ys in. Adding
3 in. to overcome the resistance of the return main and 6 in. as a factor of safety for heating up gives 12A in. as the distance; the bottom of the lowest part of the steam main and all heating units must be above the boiler water line. The same system, however,
installed and sized for a total pressure drop of Yi lb, and with.a check in the return.
270
/-Floor
Fig. 7. Method of Connecting Two-Pipe Gravity Returns to Dry Return Main
dry return, it is advisable to connect the return risers to the dry return main through water seals, as shown in Fig. 7, to prevent steam from one riser entering another.
The steam main in the down-feed system is carried to the top of the
building, and the piping of the steam side is arranged as in the down-feed
one-pipe gravity system. On the return side of the system, the piping is
arranged in exactly the same manner as the up-feed gravity two-pipe
system.
........
AIR LINE HEATING SYSTEMS
Both one- and two-pipe systems are at times provided with air valves which instead of venting to the atmosphere direct, vent to a return pipe system of small size, which in turn is vented to atmosphere or connected
to a vacuum pump. These are known as one-pipe and two-pipe air line systems. Where the air line is exhausted by a vacuum: pump they are termed one-pipe or two-pipe vacuum air line systems.
ONE-PIPE VAPOR SYSTEM
The one-pipe vapor system operates under pressures at or near atmos pheric and returns its condensation to the boiler by gravity. In this
271