Document O3wOr44ZVRZ28XJ3xL1e6MMYQ

EXHAUST SYSTEMS, GENERAL 6 COMFORT VENTILATION TABLE 28-K MINIMUM CONTROL VELOCITY (FPM) FOR UNDISTURBED LOCATIONS Class Enclosing Hood One Open Two Open Side Sides Lateral Exhaust Canopy Hood Three Open Four Open Sides Sides A-l, A-2, and B-l........... A-3, B-2, and C-l........... B*3 and C*2 * A-4, B-4, C-3, and C-4.. 75 100 100 125 65 90 75 100 50 75 50 75 Adequate general room ventdabon required 175 150 125 method is not to be used if operator has to lean over the tank) 4 General room ventilation that employs no local exhaust hoods The room air is di luted by fans or ventilators set m the room wall or ceiling Only those tanks classified as Classes A-4, B-4, C-3, or C-4 should be ventilated in this manner All others should have hoods of one of the three types listed above 5 Other methods employ special devices such as push-pull systems, where air 15 blown across the tank into the exhaust hood in order to conserve heated room air Minimum control velocity Table 28-K gives minimum control velocibes, for the three types of hoods, in locations where the desired flow of air is undisturbed by cross drafts which might come from open win dows, wall fans, unit heaters, or moving machinery Should such cross drafts exist, Table 28-L gives a value to add to the minimum control velocibes shown in Ta ble 28-K. Ventilation requirements The final step is to calculate the cfm that must be exhaust ed through the hood, based on the minimum control velocity, given in Table 28-K For an enclosing hood, the cfm should be not less that the minimum control velocity times the net area of all openings in the en closure, through which air can flow into the hood When lateral exhaust hoods are used, the ventilation rate in cfm per square foot of tank area is given, for different minimum control velocibes, in Table 28-M The rates depend on whether the tank is free standing Fig 28-14. The hood should be located so the contaminant is removed away from the breathing xone of the worker Courtesy American Conference of Governments Industrie! Hygienists TABLE 28-L SUGGESTED VELOCITIES TO COMPENSATE FOR ROOM CROSS DRAFTS AT TANK LEVEL Draft DefimUon Add to Minimum Control Velocity for Undisturbed Locabon (fpm) Slight ........................... 25 Moderate....................... 50 Strong"........................ 100 Very Strong"................ 200 It u pnferabla to use baffles to overcome strong drafts rather than to use additional control velocity 28-53