Document O3wOr44ZVRZ28XJ3xL1e6MMYQ
EXHAUST SYSTEMS, GENERAL 6 COMFORT VENTILATION
TABLE 28-K MINIMUM CONTROL VELOCITY (FPM) FOR UNDISTURBED LOCATIONS
Class
Enclosing Hood
One Open Two Open
Side
Sides
Lateral Exhaust
Canopy Hood
Three Open Four Open
Sides
Sides
A-l, A-2, and B-l........... A-3, B-2, and C-l...........
B*3 and C*2 * A-4, B-4, C-3, and C-4..
75 100 100
125
65 90 75
100
50 75 50
75
Adequate general room ventdabon required
175 150 125
method is not to be used if operator has to lean over the tank)
4 General room ventilation that employs no local exhaust hoods The room air is di luted by fans or ventilators set m the room wall or ceiling Only those tanks classified as Classes A-4, B-4, C-3, or C-4 should be ventilated in this manner All others should have hoods of one of the three types listed above
5 Other methods employ special devices such as push-pull systems, where air 15 blown across the tank into the exhaust hood in order to conserve heated room air
Minimum control velocity Table 28-K gives minimum control velocibes, for the three types of hoods, in locations where the desired flow of air is undisturbed by cross drafts which might come from open win dows, wall fans, unit heaters, or moving machinery Should such cross drafts exist, Table 28-L gives a value to add to the minimum control velocibes shown in Ta ble 28-K.
Ventilation requirements The final step is to calculate the cfm that must be exhaust ed through the hood, based on the minimum control velocity, given in Table 28-K
For an enclosing hood, the cfm should be not less that the minimum control velocity times the net area of all openings in the en closure, through which air can flow into the hood
When lateral exhaust hoods are used, the ventilation rate in cfm per square foot of tank area is given, for different minimum control velocibes, in Table 28-M The rates depend on whether the tank is free standing
Fig 28-14. The hood should be located so the contaminant is removed away from the breathing xone of the worker
Courtesy American Conference of Governments Industrie! Hygienists
TABLE 28-L
SUGGESTED VELOCITIES TO COMPENSATE FOR ROOM CROSS
DRAFTS AT TANK LEVEL
Draft DefimUon
Add to Minimum Control Velocity for Undisturbed
Locabon (fpm)
Slight ........................... 25 Moderate....................... 50 Strong"........................ 100 Very Strong"................ 200
It u pnferabla to use baffles to overcome strong drafts rather than to use additional control velocity
28-53