Document O3DJ94BZVZEd3jaaNdkEndrGQ
. PCBs--Compliance Is/And Our Responsibility
*y
R. K. Parrish, Member IFEE J. J. Kelly, Member IEEE
Transformer Maintenance Institute Div. S. D. Myers, Inc. Akron, Ohio
Abstract - Federal regulations do not require the re moval of PCBs (polychlorinated biphenyls) from service la totally enclosed industrial and utility transformers earlier than normal. Many of the estimated lk0,000 askarel-filled and 35 million oil-filled units in service can and will be around for many years to cone.
sections of TSCA. The first "Disposal and Marking Rule" took effect on April 18, 1978, while the 19?9 "PCB Ban Rule" took effect on July 2, 1979. This lat est regulation supercedes completely the 1978 version.1*
II. Unraveling the EPA PCB Regulation
During the state of frustration that the PC9 control issue is la nov, the best route to go Is to keep in formed of the latest state and local regulations, aad to make a "reasonable effort" to conply with existing U.5. regulations.
The law is clear -- choosing to keep PCB transformers in service requires proper identification; choosing to dispose of units requires the same Identification plus proper storage and disposal procedures. Either option requires accurate recordkeeping.
At least seven chemiesl waste landfills for non-liquid
A. Definitions
PCBa have been approved by the EPA (Environmental
Protection Agency).
Notable among the PCB associated terminology definrd
in Table I is a PCB Item. A PCB item is any PC?
Oa the other hand, until such time as EPA approved p_*B llculi incineration becomes feasible--ir. terns of distance and backlog--don't panic! Hold on to the
liquid n FPA approved containers, store In an EPA approved manner, and inspect weekly until incineration
associated thing that deliberately or unlstentlocally
contains or has as a part of It any PCB or PCBs at a concentration of 50 parts per million or core . (0.005 per cent on a dry weight basis) and is therefore subject to EPA regulations.
becomes practical. Don't ecntraet for shlpawnt to seas facility that gag have an approved incinerator as you nay be subject to spill liability.
..........
Both askarel and are rarely found on a transformer
nameplate. Many people are more familiar with one of the insulating fluid tradenames, as Pyranol^, Inerteet*
1. Introduction
AroelorR, and so on. As a natter of reeord, PCB was
Invented In 1929 by Swann Chemical, later bought out
federal EPA regulations do not require the removal of
by Monsanto Chemical. The late Dr. F. M. Clark patent
PCBs from service in totally enclosed industrial and utility transformers earlier than normal, therefore,
ed its application for use as an Insulating fluti for the Oencral Electric Co. In 1931.$
any of the estimated lkC.OOO askarel-filled and five
million oil-filled power and 30 million distribution
8emeone has illustrated the meaning of quantity in part
wilts In service can and will be around for many
per million (PPM) using this analogy: One (l) pert ir.
years to coa.s.1
'
a million is comparable to one (l) minute in 1.9 year-,:
The definition of PCB mixture includes transformer
But U,9. EPA regulations do control the use, maint
oil and other liquid coolants that bars bean inadver
enance, handling, labeling, storage, and disposal of polychlorinated biphenyls (PCBs) within tboee trans
tently contaminated. Major transformer manufacturers have acknowledged that "some oil-filled transforcers
formers A large power capacitors. Even though FCB
may contain varying concentrations of PCB." In this
has been the most listed Item in U.8. regulations, it
regard it is Illegal to deliberately dilute PCBs. Tht*
has not been totally banned nor is this anticipated
la the future.*
'
precludes topping off a mineral-oil filled transformer that's contaminated with PCBs. At the same tine.
It stands to reason if the oil level has dropped over
PCBs, known generics}]/ as "askarel", have been used
the passage of time below the transformer core, the
for 90 years for cooling and Insulating electrical
addition of mineral oil as a maintenance step orty.
equipment In situations where high fire resistance was required. Another plus was PCB chemical stability.
should not violate the Intent of the PCB regulation.
But this sane characteristic of persistence that swde
This paper will first cover changes that took place
PCBs useful for industrial purposes has made'them harm in the 1979 rule and also eonslder other PCb related
ful, especially theii cumulative effect on the food
legislation -- both existing and forthcoming.
Chain from plankton (the simplest plant or aaltisl) to fish, birds, and so on thru to the hunta species.*
Current PCB r*,-,\slc.ticr.* apply to all persons vhe r-n-.t-
A 1972 attempt at voluntary control was unsuccessful. Therefore, subsequent stages have involved government
facture, process, distribute in cosaiercc, use, or dis pose of PCBs. Our focus will be upon those who esc and dispose of PCbs.
al regulations. The first step was the adoption of the Toxic Substavcct Control Act (Public Lav #9b-V69
B. In Service Units
known as TSCA) which vent into effect January 1, 1977.
The intent of TCCA has been to protect in a reasonable
Existing totally enclosed transformers ran eontinu* In
and prudent mnoner the public health and the environ
definitely i service. Proper labeling, recorlkcvpl't..
ment from further contamination from toxic chemical
and voluntary inspection are the only necessary
sulstancee ai,l fixtures. PCS is only one of the chem
llr.es.
icals to U teguiatew. Cw.grtu aiuo mandated that
detailed regulations be published to implement certain
However, free breathers may be phased out by 1989. Vher
(?) D. D. '.Ivcrs, In-.. 10'f'l
1
MQNS 013394
TOM K*. Kl>
FCB Transformer
FCB Contaminated Transformer** FCB Article
FCB Container
* Table 1 Environmental Protection Agency FCB Regulation Terminology*
DEFINITION Any chemicsl substsnee containing only a biphenyl molecule that has been chlorinated to varying degrees or any combination of substances vhich contain sueh substsnee. Any transformer that contains 500 ppm PCB or greater.
Any transformer that contains 50 ppm or greater of PCB but leas than 500 ppm PCB.
s Any manufactured item, other than a PCB container that contains PCBs and vhoae surface(s) has been in direct contact vlth PCBs.
Any device used to contain PCBs, or PCB articles, and vhose surfaee(s) has been in contact vlth PCBs.
"
EXAMPLES FCB liquids and nom-llqmlda.
Askarel filled, retrofllled unit, or mineraloil filled unit as found from testing.
Typical oll-fllled transformer or FCB retrofilled unit.
Large Midi or lev voltage capacitors, transformers, FCB cooled motors.
Bottle, barrel, draa or box.
FCB Article Container FCB equipment
FCB Item
Any device used to contain PCB articles or PCB equipment, and vfcoss surfsce(s) has not been in contact with PCBs.
Any manufactured item other than a PCB container or PCB article container that contains s PCB article or other PCB equipment.
Any PCB article, PCB article container, PCB container or PC? equipment, that deliberately or unintentionally contains or ha3 a pari of it any PCB or PCBs at a concentration of 50 parts per million (ppm) or more.
Shipping or storage carton for capacitors.
Industrial television receiver, alerovav* oven, fluorescent light-!
lng fixture.
' Aroclorj*, Inerteen*.
j
PyranolR, contaminated j
transformer .(mineral)
oil, or coolants retro- j filled to transformers j
formerly containing FCB.!
Sours.: r.S.r.1 B-rlst-r. tql. " , So. 106. Port VI. so 3151`-31558.
Ron FCB Transformer - Any transformer that contains less than 50 ppm PCB - term not formally defined la this regulation.
Table 11
Requirements for Labeling PCB-Related Items* (For FCB liens of 50 ppm or sore only)
yci vrmafornur
(.`or units 000 ---. onlv )
Large FCB high-voltage capacitor or capacitor* mountH in t protected location such as on a pole, struc ture* or behind s fence, only one label need be poeted oa the pole, structure or fence. A telephone nyqher Is sufficient ovncr contact Identification.
Otter FCB articles-FCB cooled electric motors, FCB tedrsullc equlpaient end *ysteam, FCB heat-transfer equipment and system not associated with transforwer and capacitor cooling.-----------------------------------------------
FCB equipment (containing a FCB transformer or FCB large hlah-volisae caracltor).
FCB storage areas, PCD containers, and FCB article containers_.----------------------------------------------------------------------------------
FCB transport vehicles (motor vehicle or rallear) earr-vina core than >5 kr, (9?.* lbs) of rCB*s.
See Figure 1 for required label format
Figure 1
TSCA requires that PCB items be identified as spe
cifically prescribed with the largest FCB narh
practical for a PCB item. When a PCB article
or FCB equipment is too small to accomodate
the smallest permissible site of Nark
Mark Ns
may be used. Detailed requirements for size, eolor
and durability are given in the Federal Register.
Part VI , P.31556.
j CAUTioN 1
|
CONTAINS
|
PCBs I iCAUTlONjFdytMlihnN BiptoayH) I
Uj. (mmiwwiI Iiwk'iw Aytnrv n,:^.iN-*oc> re*. fw P'ml IManokM* rMci
Cm ** U.S, MA OMici.
In mm < K(*mnt ' <. rMI WM lift MnUi.C*mi Csdtt* Himmi >mw N041IIM)
{
contains
|
PCBs |
| FdytMmlmirt SiNniN |
| FOR PROPER DISPOSAL [
I INFORMATION CONTACT I
I (^.ENVIRONMENTAL I | PROTECTION ACINCV I
HONS 013395
will eonslnt of railroad transformers, primarily. WlU fW industrial units involved.
1. Transformer Identification
Under the latest PCB regulation, all items listed in Table JI should now display the appropriate PCB label* (Figure 1).
B. Requirements for PCB Recordkeeping
a. Who Must Comply
Since July 2, 1976, an inventory must be kept concern ing the status of your PCB items. The requirements apply to each facility owner or operator who has on his premises:
One or more PCB transformers and/or
Indicated that very little mineral ell dielectric fluid will be contaminated with FCB beyond ::: rfn. EPA thus anticipates that most trsnrfor*.'*r cw;r/ operators will matte such an assumption.
2. Schedule over a period of time, as the budget per mits, a one time PCB analysis test on each mineraloil-filled transformer of unknown PCB concentra tion beginning wltn the most critical wilts -- by location (near a waterway) and by disposition (rear the end of life expectancy), first, those ur.it* tested and found below the 50 ppm PCB standard would thus be exer.pt from si) disposal requirements and any PCB spill associated problems. Secondly, testing would serve ss a preventive maintenance tool. Since there is evidence that over 100 tpm PCB In mineral oil reduces the impulse strength of oil,testing would indicate suspect units.9
. 50 or more PCB large high or low voltage capacitors (See Table 111) and/or
. At least *5 kilograms (99.* lbs) of PCB*.
These records will fora the basis for a required an nual doctawnt prepared by each facility. It should Be available on July 1, 1979, and each succeeding July 1 thereafter. For multiplant companies in scat tered locations, one record for the entire corporation could be maintained at a central location.
Current lav requires that records are to be maintained 1a the Individual companies' own file, subject to re quest of copies or on-slve EPA inspection upon the presentation of appropriate credentials, along with written aotiee of the facility to be inspected.
b. What Data Required
Total weight in kilograms of PCBs and PCB items In containers Including identification of container contents, such as liquids or capacitors (total weight means excluding the vefght of the containers).
. Total number of PCB transformers and total weight
In kilograms of any PCB liquids contained in the
transformer. .
.
. Total number of PCB large high or lew voltage espacitors.
At Table 7 shows, a distinction has now been made be tween PCB transformers, these eontainlng 500 or more ppm, and PCB contaminated units, those containing be tween 50 and *99 ppm, and non-PCB transformers, those with less than 50 ppm PCB.
Those units that contain less than 500 ppr. do not require labels. However, special identification of "PC3 contaminated units" (50-1*99 ppm) may be the best way to nature special treatment. Obviously, sueh action necessitates scheduled one-time PCB analysis, but it facilitates compliance with the law. Thus, these two suggested steps provide:
. Immediate Identification for ongoing inspection of units and recordkeeping.
. Minimise future disposal eosts.
. Meet probable testing prerequisite prior to ar.y con tracted transformer nsintensnee work.
Consider this typicsl laboratory data (about 1*30 samples of mineral oil):
PCB Concentration
Percentage of Samples Tested
. Location of PCB item.
Use nameplate information to determine PCB weight re quirements. Your annual reports must be kept for at least five (5) years after a facility ceases to own or operate PCB related items in the prescribed quantities.
Failure to keep proper records is a violation of the lav. Civil penalty of up to fc?5000 could be Imposed for violation of TSCA; eaeh day the violation con tinues is considered a separate violation.
c. Row Aecpetable Records Generated (To test or not to test!)
Testing for PCI concentration In transformer mineral oil is not required in the latest PCB ruling. There fore, consider two possible options.
1. Do nothing (l.e, do not.test). Unless there la . a specific reason to believe s given transformer has more than 500 ppm PCB, assume the unit to have 50 Vo *99 PPS PCB. Available EPA information has
1. > *99 ppm 2. 50 - *99 ppm
3. < 50 ppm
*. 0 ppm (Pure mineral Oil)
109
TV. kos
Two out of every three units tested will likely con tain less than 50 ppa PCB.
As transformer oils are tested for FCB-content, base.*, on the 50 ppm EPA standard for PCS item, units can then be properly labeled, where beneficial.
3, Voluntary Periodic Inspection
Consider all possible precautions that ear. prevent n
spill.
_
a. Establish a checklist for periodic Inspection. 1. Insure that units are structurally sound.
Labels for PCB liens contnininc 50 *99 ppm re r*ot required before October 1, 1979. 3
MONS 013396
2. Cheek for gasket leaks (covers, hand-hole or Bushings).
equipment, it win probably be several years before sufficient incineration capacity will be available.
3. Check sampling valves and other fittings.
k. Check pumps and cooling radiators for leaks.
h. establish a consistent schedule for such inspec tion (aenthly minimum).
e. Consider diking and curbing for units near water ways.
d. begin to establish a spill prevention plan - a series of operations procedures to be followed in the performance of a PCB activity (operating or testing apparatus).^
e. Begin to prepare a control and countermeasure plan-to be followed when a release of PCBs occurs at a PCB uae or servicing operation.
k. Maintenance
Boutin# maintenance (oil testing, end so forth) by the owner or outside contractor of all units Is permitted.Movevect contractor performing transformer servicing Is required to obtain a rpeclal annual CPA authorisation.
Until such time as EPA approved PCB liquid Incinera tion becomes feasible, hang looseI Eves now,prac tical logistics -- distance and backlog -- make lsaaedlatc incineration difficult. Therefore, hold on to the liquid In "PA-DCT approved containers. "tore properly and Inspect it weekly until disposal Is practical.
Fortunately, the EPA recognizes the limitations of technical and economic feasibility to Incinerate all FCB Items. Therefore the law permits disposal of PCB solids.contaminated liquids (50-I99 ppn) st ETA approved chemical virste landfills or high efficiency chemical boilers. At least se**er approved ehemicel waste landfills are now "open". The boiler rating must be at least 50 million BTU per hour and must meet certain stack gas characteristics.
Since disposal in landfilla will not result in PCB destruction, other new approaches now In the prototype etage may become available; e.g., the use of alerovave radiation.
PCB transformers, notably, can be permanently disposed of in a chemical waste landfill if all these conditions are met:
PCB contaminated transformers (50-i*99 ppm PCB) nay be
topped off, refilled or rebuilt wivh dielectric
fluids containing leas than $00 ppn PCB. Existing
skarel rilled units may be topped off with FCB die
lectric fluid. However transformer repair, Including
rewinding of colls, linotpemitted on units of 500 or
sort ppm PCB.
but, PCB transformers ret.ro-
ftiled to PCB contaminated units say then be rebuilt.
. The unit must be drained of all free-flowing liquid, and the liquid mt-t be treated in the manner pre
scribed for PCB liquids in Table III.
. It oust then be filled with a suitable solvent (such
ss kerosene, xylene, toluene) in which PCBs are
readily soluble. (Some of these liquids are also
hAXsrdous.)
,
During the next five years, EPA will be examining the
uae of substitute insulating fluids in older units
to determine the feasibility of phasing out all use
Of PCBs.
..
C. Out-of-Service Units
All out-of-service PCB items (Table II) must alto be properly labeled, whether spare units or those await ing disposal.
. The solvent must be left in the unit for st lesst Id hours, snd the unit must then be drslned thor oughly.
. The drsined solvent -- which is now a PCB Item -- must be treated in the manner prescribed for PCB liquids in Table III.
Any PCB contaminated transformer (50-*99 ppm PCB) requires only these steps: '
Slmce April 18, 1978, PCB liquids (2$30ppm) must be giapoeed of in only an EPA approved incinerator. All low liquid PCBs esn be disposed of in an EPA approved ehemicel waste landfill.
. Transformer drslned cf sll free flowing liquid.
. The dielectric fluid may be disposed of In a chemical waste landfill or high efficiency boiler.
The various PCB Items must be labeled and stored as summarised In Table III for PCB Items containing more than $0 ppm PCB, unless otherwise stated.
A transformer declared as a spare can remain In a
substation. If tUt unit is declared for disposal,
then it must be moved to an EPA approved storey
facility pending appropriate disposal.
'
l. Permanent Disposal
The only known way to permanently remove PCBe from the environment Is high temperature (at lea't 1200C) in cineration with proper dwell tine. EPA regulations ro longer penal*, eto rage of PCB liquids > m ppm. How ever, st present only two approved Incinerators are
open.9
Several other companies have applied. One vss approv ed, but local ordlna...e ah,t the facility down. Becnus; of this daisy In obtslnlng permits and delivrry of
. . Drained transformer carcase may then be disposed of
in a municipal landfill or sold for salvage.
.
2. Temporary Storage for Disposal
Storage for disposrtl means temporary storage cf PCBs that have been designated for disposal. Table IV lists the provisions for temporary storage of FCB articles, equipment or containers.
When storage Is desired prior to disposal, contamin ated FCB liquids (50-b?9 ppm) and non-liquid TCP* must be stored In an EVA approved storage facility.
Ar EPA approved storage facility has been deflneJ as a roofed, vailed and diked enclosure with aa imper meable floor, such as Portland cenent concrete or steel. Ho storage facility nay be loeated at a site which is below the 190 year flood water elevation (that is. a flood that has an average frequency of occurrence In the order of once in 100 years). There-
The first incinerator still nay not be EPA approved until September 1, 19(9>
U
HONS 013397
Table III
1
Permanent Disposal or Long Ten Storage of PCB's Pending Disposal
(Por PCS item* of 50 ppm or more, unless othervlse stated)
Disposal Mans the Intentional or accidental discharging or other completion or termination of the*useful life of an object or substance.
|
j
I |
TOW
KB liquid. (7 500 ppm)
PCD contaminated mineral oil dielectric fluid <50-1*99 ppm)
PCD contaminated waste liquid (5<^h99 ppm) such as hydrau lic or beat transfer fluids.
Don-liquid PCBs; contam inated toil* rags, or other debris from uncontrolled pill (trash, trees, lumber).
Bon-llquld KB waste; dredge polls, eunlelpal sevagetreataent sludges.
DISPOSAL PROVISIONS Disposal In EPA approved hl-temp. Incinerator. Bo storage permitted.
| |
Disposal In EPA approved hl-temp. Incinerator; ETA approved chemical waste |
landfill or an high efficiency boiler.*
j
Disposal in EPA approved hl-temp. Incinerator; EPA approved chemical waste landfill or an EPA approved high efficiency boiler.*
Disposal In EPA approved hi-temp. Incinerator; or EPA approved chemical waste landfill.* However, items may be considered to have been disposed of If they were deposited in a chemical waste landfill before b/18/78.
Disposal in EPA approved hl-temp. incinerator. EPA approved chcmicol waste
landfill, or by other EPA approved method.* The digging **P of debris and
other Items disposed of In a landfill prior to h/l8/70 is net required but
the Intent of the rule is that you can't add to an existing site and
let it sit.
__
. ...
jj
!
|
KB transformers (> 500 ppm) KB contaminated trans former {50-1*99 ppm) PCB large high or low voltage capacitors (more than 3 pounds cr 1 quart of KB liquid) KB small capacitors (less than 3 pounds or 1 quart of PCB liquid)
KB hydraulic machine (dla-eaatlng) Other PCB articles
KB container ( 500 ppm)
KB container (50-199 ppm)
Disposal in EPA approved hi-temp. incinerator or EPA approved chemical wuste !
landfill, following procedure given in article text.*
^
Disposal la municipal landfill or sold for salvage following procedure
given in eytlcle text.
'
.. Disposal In EPA approved hi-teap. Incinerator; disposal permitted until 1/1/80 in EPA approved chemical waste landfill.*
j
|
j
Capacitors owned by eapacltor manufacturers or KB article aanufacturers (production quality-control rejects, etc.) to be disposed of In hi-teap. incinerator; disposal permitted in EPA approved chemical waste landfill until 1/1/80. All other small capacitors may be disposed of as mumcipal solid waste.
[ f ' , :
Disposal as municipal solid waste or sold Tor salvage following procedures
given in article text.
.
, :
Disposal In EPA approved hl-temp Incinerator, EPA approved chemical wuste landfill; following thorough draining end proper disposal of KB liquid.*
Disposal in EPA approved hl-temp. incinerator or EPA approved chemical waste landfill (following temporary storage at an EPA approved facility until-properly drained end PCB liquid has been properly disposed of).*
.
Dispose] as municipal solid vasts, following proper draining and disposal
of KB contaminated liquid.
.
Lone tern storage of this iten is permitted in ITA-IX/i.' approved containers nnd/or located in an ETA-approvod facility until l/l/Qh.
HONS 013390 5
Tabic IV
.
Temporary Storage of KB iteas Pending Disposal
-
ITCi
STORAGE PROVISIONS*
Bon-lesking PCB article or equipment.
Pen-leaking structurally undamaged large high voltage KB eapaeiter PCB contanlnated transfomer
Storage In temporary area up to 30 days Instead of standard EPA defined facility. Check weekly for leaks. Long term storage required after 30 days in roofed and diked enclosure with inpermesbl# floor until 1/l/Bk. Check st least once every 30 days for leaks.
Long term storage on skids next to an EPA defined storage facility until 1/1/63. This makes a facility immediately available if a leak should develop. Reason: In ease of delay in the construction of proper incineratlcr. facilities or for new capacitors to be used at a construction site; cheek woeklv for leaks.
Leaking KB articles and ouloarat
Stored in non-leaking EPA-D0T approved containers for up to 30 days (eontalnlna sufficient sorbent materials to absorb liouids KBs)
FCB containers containing non liquid KBa (soil, rags) or llnild PCB. (50-k99 nr*).*"
Storage In temporary area up to 30 days instead of standard EPA defined facility, provided s spill prevention control and counter aeasure plan prepared.
Leak, leakage or leaking mim any instance In vhlcb a PCB article, container or equipment has any FCB oa any portion of its exterior surface.
Date FCB itea reaoved from service noted on the PCB itea.
St la no loafer permissible to store drums of liquid PCBs t> 500 PPM).
fore, Immediately cootact your regional office of U.S. Oeologleal Survey for a hydrological aap that docu ments whether or not your present site Is adequate or should be relocated.
3* Becordkeasing
In conjunction vitb disposal requirements, the trans former owner/operator oust keep the following data for the annual composite record, documenting the status of FCB iteas slated for disposal:
. Date removed from servlet. -
. Bate placed into storage pending disposal.
Ignoring or- attempting to conceal a leak, a spill, or other uncontrolled discharge of KB Is engaging in un lawful disposal and subject to criminal prosecution.
1. Preventive Action
Weekly Inspection for all items temporarily stored in non-EPA approved facilities or on skids; 30 dsy ninimua Inspection for all items stored in an EPA approved facility. Experience has already shown that inspec tion for leakage should be made more often than every 30 days -- even with new KB containers. In antici pation of possible rules for hazardous spills, spill prevention is the only sure way to treat a spill sltutatlon.
Dote placed in transport for disposal.
2. Corrective Action
.
Total weight (in kilograms) and identification of Pds in KB containers.
. Total nur.ber of KB transformers and total weight (in kilograms) of any KBs contained in the trans ferases.
a. Iu the Event of Minor KB Leakage
Proper actions to he taken consist of:
. Transfer leaking containers and articles, and their contents, to properly marked, nonleaking containers.
. Total nuaber of large high or low-voltage KB capacitors.
. Use sorbents such as imbiber beads te dean up any spilled or leaked material immediately.
. Location and r.aac of ovner of initial storage or disposal facility (Bill of lading).
. Dispose of (or store for future disposal) residue as Indicated in Table III or IV.
St la permissible to determine the weight of KB by calculation (using valid assumptions of the density of the FCB chemical substanee or mixture) if the voliate af the container or transformer is known.
Failure to keep these proper records Is a civil vio lation of the KB lav.
B. KB Spills
'
Spills and other uncontrolled discharges of. liquid KBs are defined as disposal; therefore, proper
procedures must be undertaken.
b. In the Event of a Major Spill*
' A rCB spill is any discharge of sufficient magnitude to give reason to suspect that it has produced, at any point in the surrounding soil, erevel, sludge, fill, rubble, or other land-based substances, a KB contarvlnation level exceeding 50 ppm. The following mea sures must be taken in the event of a spill.
. Transfer leaking containers and articles, and their contents to properly marked, nonlenktag containers.
. Use sorbents to clean up any spilled or leaked caterial immediately.
6 MQftS 013399
*, Dispose of (or store) residue as Indicated In Table IXI or IV.
. Conduct tests, using EPA-approved sampling techni ques and laboratory methods, to determine If PCB concentration In soil, etc., exceeds 50 ppm.
. Decontaminate areas containing more than 50 ppm of Kb in accordance with EPA regulations.
Several companies tfavc already established their own special teaeta that are aent out to handle PCB spills and elean up. Contracted cleanup services eertalnly could also be an option.
_ Therefore, begin.a bound logbook containing this data (compliance under RCRA and/or state law).
k. Assigned clear responsibilities*!
a. Make sure that specific technical and legal people are Involved in day-to-day decisions on PCB storage and disposal.
b. Inform other company personnel as to the lates Information on how to make a "reasonable effort" to comply with all regulations.
5. Transportation for disposal.!2
1X1. EPA Approved Method* of Testing for PCS Concentrstien
Implementation of the foregoing guidelines requires first a procedure to readily identify transformers containing PCB mixtures.
Although testing for PCB eontent in oil by alcctron capture gas chromatography (GC) Is the most prevalent laboratory method,7 the BMlstein field test can be a preliminary test to detect PCS* at a level or five (5) per cer.t ($0,000 ppciP or greater. Very few units -ore this grossly contaminated.
Since evidence has shove that more than 100 ppm PC? la mineral oil tends to reduce the impulse strength Of oil, testing vould indicate suspect units. The technology to remove FCfcs from mineral oil is being actively developed to assure the transformers max imum design lightning strike capability.9
IV, Other PCB Associated Federal and State lavs
Xmplmentation of the foregoing present and projected regulations in no vay precludes compliance under, other regulatory rulings. In fact the Intent of the various statutes is integrating all facets of the PCB problem yet without doing so at eross-purpodet.
The tvo moat important rCB associated documents are (1) The Resource Conservation and Recovery Act (RCRAP.L. #9k->?0, 1976), involving hazardous waste manage ment and (2) Section 311 or the federal Water Pollu tion Control Act (r*TCA-?.L. #92-500, 1972).
Sven though detailed rules of RCRA ney not be pub lished until *14-1960 and Section 311 is under a court injunction declaring it void, existing state lava indicate that the prudent way to go vould be to prepare even no * for inevitable U.S. regulations in one form or another.X
Suggested steps thst should be taken include:
1. Inventory of PCB items - In service units;-spares or units pending disposal (Required under current PCB rule).
B. One-time PCB in oil analysis (best vay to assure proper transformer treatment).
3. Tracing of PCB wastes (manifest system).
Several states already require s ranifest system ("radle-tp-prave*' paperwork) for off-site dis posal. The ranifest is defined as the fora used for identifying tiie quantity, composition, origin, routing* and destination of PCB liquids and solids, during transit from the point of generation to the point of storage or disposal.
a. Train shipping personnel.
1) Proper packaging and labeling:
Per EPA-Depertment of Transportation (DOT) specified containers for PCB liquids or non liquid PCBs. Mineral oil dleleetric fluids of unknown concentration may be shipped via United Parvel Service (UPS), but askarel liquid should be shipped with a Class P poison label. Therefore, askarel cannot be shipped by UPS.
2) Response control and countermeasure plan when PCS release occurs.
b. Provide truck drivers with complete bill of lading and current response Information In case of an accidental spill. Include phone numbers of site destination point and reg ional EPA. Start reporting now harmful quantity discharges near waterways to the Rational Response Center: (600) k?b-S802
-* (under FVPCA, Section 311). ,
6. Keeping abreast of state legislation - transit of hazardous wastes; both home stste and those thru which shipping likely will go.
T. Review of off site disposal agreements. Written eontrset should spell out in detail what you as PCB generator will do and what disposal contractor will do. When do title, ownership and risks transfer from the PCB generator to disposal con tractor?
6. CAUTIOff: You cannot assume PCBs are being proper ly disposed of. You should follow thru - make
. regular checks of waste contreetor and routine on site inspections. Evaluate the facility la terms of coaipetencc, staffing, permits, problem history and general suitability for PCB disposal. Bss fa cility received U.S., State and local approval for dlsposal?13
V. Other Options'Available to Owners of PCB Transforr.crs
Retrofilling or replacing a PCB transformer are also alternative?, in addition to retaining PCB units.
A. Rctrofil) Aaharcl-Filled Unit With Hon-PCB Alternative Coolant!**
The residual mixture should be tested at lerst an
nually (preferably more frequently) to determine its
exact PCB eontent, as it will flucuate as it seeks
equilibrum.
'
" Using retroflll procedures only one time will erokablr
T HONS 013400
ttlll result in t ccntnminst/d transformer that would' have to be treated as an askarel unit In all Other rtifveti. Therefore) retroflll In wtuallty totalIs series of rrtrofilla and/or subsequent fllterlna with aetlvated carbon.
Keen then the unit still eight he treated as a PCB Its*. drending upon concentration; however, the po tential economic liability becomej considerably less than the coat of decontamination in the event of a spill lsvolvlng a concentrated KB.
Disposal of both existing PCB liquid and flushing liquid requires incineration. So Ion# as disposal thru incineration remains a problem* the best lo cation for PCla is the transformer itself.
soever* when sufficient facilities do become approved, retroflll may be the primary vehiela In preparing for ultimate disposal of PCB transformers and thus phasing out of aakarel-fllled transformers.
1. heelace the Aikarcl-fllled Unit
If a transformer is located near a drainage canal, stream* or waterway the only safe option Is to replace the unit with one containing a non-PCB coolant, gas dlelectrle or an alr-eooled* dry unit.
Location, use and naacplate capacity required would determine this final choice.
vi. Conclusion
Much criticism hoe been directed toward the expense or EPA regulation. It is a fact that the long ter?, effect Of PCB eo the food chain may not be known for years. 15 Tel public support for costly environmental protection remains strong.16 That's because of the high cost of the alternative -- not regulating.17
In any event, while the issue of PCS control continues in a state of frustration, the best routs to go is to Beep Informed of the latest state and local regulations and to make a "reasonable effort" to comply with exist ing federal regulations (required marking, record keeping,voluntary Inspection, and suggested one-time PCB analysis of transformer mineral oils).
9. 10a.
b. c. 11.
12.
13. lb.15a.
b. 16. 17.
E. 1. Rnb. 2- elt- . August 3, 1970 sn* April 11. 1->*.
R. S. Claubingcr, "A Guide to the Resource Con
servation and Recovery Act, Chemical Dialn--rlw
Magazine, MeCrav-Hill, Rev York, R.Y., January 29, 1979, pp 79-61.
Richard Sobel (Allied Chemical Corporation),
"Mow Industry Can Prepare for RCRA " Ibid. m.
82-85.
--------
T. H. Msugh II, "Toxic Waste Disposal a Crowing
Problem." Setcnee.American Association for the
Advancement of Science (AAAS), Volume ?0A, 25
May 1979, p. 819.
V. D. Beebe (Potomnc Electric Power Company)
"Askarel/Folychlorlnnted Biphenyl (PCB) Pro
cedures," Minutes of the b6th Annual International
Conference of Doble Clients, 1979, Doble engi
neering Co.; Watertown, Mass., Section 10fr>l.
Ken Snow (Plying Tiger Line) "Shipping hazardous
Material," Chemical Engineering Magazine, MeGrav Hill, Mew York.R.Y.^ November o, 1978, pp 102
106 (Discussion of Dept, of Transportation DOT regulations.)
Allan Hall, "Waste sites may be major liability
for CPI" Chemical Week. May 2, 1979. p 18.
T. O'tJell 4 J.` JVKelly, "Silicone Retroflll of
Askarel Transformers',' Minutes of the 13th
Slettrieal/Eleetronlc Insulation Conference,
Chicago, 11 Sept. 29, 197T. p. 167.
John Walsh, "EPA and Toxic Substance* Law; Deal
ing with Uncertainty," Science. Volume 202,
10 November 1978, p 598.
Bruce R. Ames (Professor of Biochemistry* U. of California, Berkeley),"Identifying Environmental
Chemicals Causing Mutations and Cancer."Science.
Vol. 20b, n May 1979. p 587.
Luther J. Carter* "Public Support for Environ
mental Protection Remains Strong** Science. Volw* 203. 12 January 1979, p 15b.
Nicholas A. Ashford (Associated Professor of Technolofy A Policy, Massachusetts Institute of Technology), "A plea for a new hind of realism*"
The Rev York Times. Business Section* December 17, 1978.
Til. References
1. Mieroetoncaic Impacts of the Proposed PCB Ban Reg-
ulatians. Versar. Inc. (ETA #560/6-77-35, May 1978,
pp 7, 37-38. 2. D. E. Hutchinson, American Electric Power Service
Corporation "Regulatory Status of the PCB Sub stitutes," 1979 Winter Meeting, Bcw York,Rev York,
IEEE Power Engineering Society* February 6, 1979.
pp 6-7. J, Edward L. Raab (Retired* General Electric Co..Pitts
field* Maas.) in conversation held at Transformer
Consultants* Dlv. S. D. Myers, Xne. Akron*-Ohio*
August 3* 1978, and April 11. 1979.
.
b. R. R. Parrish A J. J. Kelly "Warning: TSCA May be
Vatardoos to Your Professional Health," Plant
M.J 11, 1979, p. 133. Th 1978 l.v
is found In the federal ReeUtcr. February 17, 1970,
vl, 1), Ho. 3**, Part V, pp 7150-7l6b. The 1979
"PCS Bam" Rule published May 31* 1979, is located
la the Federal Register. Vol. U
Ho. 106', Fart Vi, pp 3151b-31558.
5. E. L. Raab, jj>. cit., August 3, 1970.
6. Itepa die may be required under Section 311 of
the Water Control Aet. Some states already have such.
?. 0. Ruuinger, S. Safe, V. Zltko, The Chemistry of PO'a.cme Press, Cleveland* Ohio 197*, pp $07,
210*212.
I, U.g. Vary BEPSS (Rival Environmental Protection
Support Serv. ^Information Bulletin,! July 1970.
` *
-
. .
HONS
013401
0