Specification No. EP-187-N
Engineering Department El Paso Refinery February 16, 1966
PLAINTIFF'S EXHIBIT
CHV-9 _____
Limpet Insulation Precipitator Inlet Duct
Plant 18-FCC
SCOPE
1. General - The general conditions of the contract are a part of this speci fication. This specification covers the furnishing, delivering, unloading, hauling, storing, protection and application of Limpet to complete all insulated surfaces as shown on Drawing TA 18-1140.
2. Work Included - The contractor shall furnish all supervision, labor, mater ials, tools and equipment to perform the work specified herein.
3. Supplied by Owner -
.
a. Owner shall furnish 110 or 480 volts, 60 cycle, single or three phase A.C. electric power, water at no less than 35 p.s.i. pressure (4 gallons per minute) and air at 8 cu. ft. per minute.
b. Necessary staging.
c. Installation of studs.
Materials
4. Sprayed Limpet Asbestos - Insulation shall be Limpet of appropriate grade, ao supplied by Armstrong Contracting & Supply Corporations LW-25 for use to 700 F.
5. Finishing Materials - Finish shall be Chevron Asphalt Company's Laycold Weathercoat.
Application
6. General
a. Surface Preparation - Prepare as necessary, removing all grease, dirt and loose material such as flaking paint and rust likely to -interfere with bond of Limpet to base surface.
b. Supports - Supports shall be in the form of 3/8" x 3-1/2" studs welded to the surface. These supports shall be used for anchoring galvanized wire mesh, located over the applied Limpet insulation.
CHEV BB 0000447
Specification Ho. EP-187-H Pago 2 *
c. Limpet Application - Application of Limpet shall ho carried out solely by approved applicators, licensed by Armstrong Contracting & Supply Corporation, and shall he -
(1) By skilled mechanics, thoroughly trained by Armstrong Contracting & Supply Corporation,
$2) Applied with the use of patented Limpet Spray Machinery,
(3) Sven in texture and applied to density and thickness as defined
in this specification and listed on drawings and written instruetions issued for this specific contract.
d. Outdoor Finish -
(1) Sard Weather Finish - After Liapet has been applied and pressed to proper thickness, apply 1" hexagonal 20 ga. wire mesh as specified in Section 6b. Over this, trcwel Laycold Weathercoat to a thickness of 1/4".
Warranty
7. Contractor shall warrant the satisfactory adherence Limpet insulation for
a period of one year.
.
CHEV BB 0000448
CALIFORNIA. OIL COMPANY - WESTERN DIVISION EL PASO REFINERY
EL PASO REFINERY INSTRUCTION NO. Lkoh PAGE 1 OF 4
GENERAL INSTRUCT;ONS TO CONTRACTORS WORKING WITHIN THE REFINERY
PURPOSE .
1. The purpose of this Instruction, is to acquaint you vith general rules and regulations of the Refinery pertaining to your vork while in the Refinery. Your cooperation in complying vith these regulations is requested.
CONTRACTOR
2. The term "Contractor" as used in these instructions, shall he understood to include any and all subcontractors performing vork Tinder terras of the contract under consideration. Contractor is responsible for getting this information to subcontractors and for directing and supervising vork of subcontractors.
COMPANY
3. In order to assist you in following these instructions, a Company
REPRESENTATIVE
representative will be assigned to you. It is his duty to act
as the Company's agent in all matters relative to your activities
while in the Refinery. All questions concerning these instructions
and additional instructions or information necessary for the
proper performance of your vork shall be referred to the Company
repre s entative.
4. Under no circumstance shall any vork be started until the Company representative has been contacted.
PASSES
5. Contact the Company representative prior to the start of. vork to arrange for Refinery passes for each of your employees. Badges are assigned to individual employees,* and are not transferable. Vehicle passes, when required, will be supplied by the Company.
PROTECTIVE EQUIPMENT
The Contractor shall be solely responsible for the badges issued to his employees and final payment on the contract will be delayed until all badges are returned. In the case of loss of a badge, a report should be made to the Company representative immediately, including badge number, time and place of loss, and circumstances surrounding the loss.
6. All of your employees must wear hard hats whenever they are in field operating, maintenance or construction areas. Certain areas in the Shops Buildings where hard hats are required will be clearly identified.
The Company representative will advise you of the type of eye protection required and other Refinery personnel protection requirements.
MATCHES
7. Carrying "strike anywhere" matches in the Refinery is prohibited. Any cigar or cigarette lighters carried within the Refinery shall have the flint, steel, and operating mechanism enclosed in such a manner as to prevent the ]?ossibility of accidental lighting or sparking.
Issued: 4/3/63
:hev bb
CALIFORNIA OIL COMPANY - WESTERN DIVISION EL PASO REFINERY
EL PASO REFINERY INSTRUCTION NO. PAGE 2 OF 4
GENERAL INSTRUCTIONS TO CONTRACTORS WORKING WITHIN THE REFINERY
SMOKING
8. Smoking by Contractor's employees will be permitted only within areas designated by Company representative and subject to his restrictions.
MOTORIZED EQUIPMENT
.
DRIVING
PARKING
DOCTOR, HOSPITAL & AMBULANCE ACCIDENTS
OPERATING UNITS
FIRES & FIRE EQUIPMENT
9. Your motorized equipment shall be equipped with mufflers in good condition, and the wiring in good order before the
equipment will be allowed to enter the Refinery.
10. Drive carefully. Maximum speed limit in the Refinery is 20 mph. A walking guide must, be furnished by you when cumbersome loads or equipment is moved on Refinery streets.
11. Your motorized equipment shall be perked within the Refinery only within areas designated hy the Company representative. Employees' privately owned cars are not permitted within the Refinery.
12. Furnish the Company representative with information as to which doctor, hospital, and ambulance is to he used In case of accident or injury to Contractor's personnel.
13. In the case of any injury sustained on Refinery property by any of your employees, report the circumstances promptly to the
Company representative.
14. Do not allow your employees to enter operating units or operate any valve except water bibbs specifically designated by the Company representative.
15. Do not use or move fire fighting equipment, except that which is assigned for your use. Keep space around fire hydrants. extinguishers, hose houses, etc., clear at all times. In case of fire, keep away from the vicinity of the fire and out of the way of fire fighting activities.
In case of fire:
15.01
Call local 333.
15.02
Report location of fire.
15.03
15.Ok
Keep clear of the burning area to allow Refinery personr.
to extinguish fire.
'
Remove equipment and employees from the area.
MATERIAL DELIVERIES
l6. Notify the Company representative of expected material deliveries
Issued: 4/3/63
CHEV BB 0000450
Specification So. SP-137N Engineering Departnent El Faao Refinery February 16, 1966
Lirapefc Insulation Precipitator Inlet Duct
Plant IS-FOS
Scope
1. General - The general conditiens of tha contract are a part of this speci fication. This specification covers the famishing, delivering, unloading, hauling,, storing, protection and application of Liepet to collate all insulated surfaces as shown. 6n Drawing TA 13-1140.
2* Work Included - The contractor shall furnish all supervision, labor, mterials, tools and eguipasnfc to perform the work specified herein*
3. Supplied by Owner -
a. Owner shall furnish. 1|0 or 430 volts, 50 cycle, single or three pfaa.se A.C. electric poser, water at no leas than 35 p.s.i. pressure (4 gallons par isinute) and air at 3 cs. ft. per nxnufce.
fa'. Hecessary staging.
c. Installation of studs.
Hatesials
4. Sprayed Lisgset Asbestos - Insulation shall be Limpet of appropriate grade, as supplied by Armstrong Contracting & Supply Corporationj U?-25 for use to 70Q5]?-
5. Finishing Materials - Finish shall be Chevron Asphalt Cojapany*a Laycold Weathercoat.
Application
6. General
a. Surface Preparation - Frepara an necessary, removing all grease, dirt and loose material such as flaking paint and rust likely to interfere with. bond of Liispet to base surface.
b. Supports - Supports shall be in the fora of 3/3" x 3%" studs .welded to the surface. These supports shall be used for anchoring galvanized wire nesfa, located aver the applied Liapefc insulation.
CHEV BB 0000451
Specification. Ho. EP-137H
Sags 2
c. Little Application * Application of Lifflpet shall he carried out solely
hy approved applicators,, licensed by Arrastrcog Contractlag & Supply
Corporation, and shall bo -
-
^1) B? shilled mechanics,. thoroughly trained by Armstrong Contracting & Supply Corporation,
. (2) Applied with the use of patented Limpet Spray Machinery>
(3) Syett 1st tenfcuxc and applied to density and thickness as defined in this specification, and listed on drawings and written instruc tions issued for this specific contract-
cf. Outdoor Finish -
(1) Hard Heather Finish - After Limpet has been applied and pressed
to proper thickness, apply 1" heragonal 20 gs. vise mash as
specified in Section
Over this, trowel laycold Heathercoat
to a thickness a
Warranty
7. Contractor 3hall warrant, the satisfactory adherence of Limpet insulation for a period of one year-
CHEV BB 0000452