CHAPTER 51
1949 Guide
For the handling of chlorine and chlorinators, the U. S. Pubhc Health Service87 stipulates the following safety requirements:
. 1. Suitable gas masks and a small bottle of ammonia for testing for leaks should be kept at convenient points immediately outside the room or enclosure in which chlo rine is being stored or is in use. Gas masks should be inspected at regular intervals and kept in serviceable condition. Note:--All purpose masks offer adequate protec tion only when the concentration of acid gases does not exceed two per cent--See
"Safe Practises Pamphlet #64 National Safety Council".
2. Chlorinating equipment and cylinders of chlorine should be housed preferably n separate buildings above the ground level.
3. The room or building housing chlorinators in service should be maintained at a temperature above 60 F, but never in excess of the normal summer temperature. The cylinders of chlorine should be shielded, where necessary, from excessive heat or cold. Direct heat Bhould not be applied to cylinders of chlorine nor should hot
water be poured over them or come in contact with the cylinder valve.
.
4. Adequate ventilation should be provided for all enclosures in which chlorine is being fed or stored.
5. All joints of tubing connecting chlorine cylinder and chlorinators should be kept absolutely tight and inspected.frequently to insure tightness. Tubing should slope . upward from the cylinder.
LEGAL REGULATIONS
In a number of states, the water used for humidification, even in in dustrial plants, is required to'meet , drinking water standards insofar as bacteriological quality is concerned. A ruling of the U. S. Department of Agriculture, Meat Inspection Division prohibits the use of chromate in water used for air washing when the air later contacts foodstuffs88:
There is an ever growing consciousness on the part of public health
officials of the necessity for regulations to protect potable water supplies.
Attesting this is an .ordinance89 now in effect in Detroit, Michigan, which
stipulates in part:
'
"No physical connection shall be maintained between lines carrying city water
and pipes, pumps, or tanks supplied from any other source. Where dual supplies are necessary or desired, lines carrying city water, must be .protected against back
flow of polluted water by an atmospheric gap--Secondary supplies and emergency
sources shall include: surface waters from rivers, lakes, ponds lagoons, and reservoirs; well waters both deep and.shallow.; any supply of water which has been stored, held,
' or reserved after being used for industrial purposes; cooling water, or water which has in any way been treated, processed, or has been subjected or exposed to any con
tamination of a bacteriological or chemical nature; and water from any other source
than the city supply."
The U. S. Public Health Service stipulates:
..
' "Salts of barium, hexavalent chromium, heavy metal glucosides, or other sub stances with deleterious physiological effects, shall'not' be allowed in the water supply system."
The same agency recommends that the concentration of the substances listed be held below the the values cited in following table:
Substance
Max Concentration,
ppm .
Substance
Max Concentration,
ppm
Iron & Manganese (Total)..
3.0 0.3 125:0 . 15.0 0.1 1.0
Poly-phosphate of Sodium:. pH Value 25C............
0.05 0.05 0.001 10.0 10.6
Corrosion and Water Formed Deposits, Causes and Prevention
985
The Board of Directors of the American Water works Association has accepted these values as standard for off public .'water supplies in the
United States40. While their action is hot binding, prudence dictates that
no form of treatment should be used that will result, in-raising .'the; con
centration of the substances listed above the value cited..
:-
Since virtually all of the permissible chemicals used for scale, slime, and corrosion control have deleterious, physiological effects if taken internally
in relatively large doses, they should always be carefully proportioned: To ihsure this, the Detroit ordinance stipulates, that the chemical feeding device must have the following major characteristics:
"1. There shall be a visible means of checking the quantity of material being applied by the feeding device.
2. A water metering device, sealed to prevent tampering, shall be installed to measure the flow of water being treated.
3. The device shall be constructed so that in: the event of back-flow or vacuums, the maximum amount of material that may be, possibly back-siphoned from the device or any of its attachments or parts shall not exceed one fluid ounce.
4. -Should there be a failure of the water, metering, device or the water supply, the feeding device shall automatically cease operating."
REFERENCES
rf'.;:;
_
1 Annual Report (1947) Committee D-19 (American Society for Testing Materials)
1 Handbook on Corrosion, Electrochemical Society (Unpublished) :
I Discussion, Corrosion and Material Protection, May 1945, p. 2.
4 Round-Table Discussion on Organizing the .Classification of Industrial Waters, by W. C. Schroeder (Proceedings, American Society for Testing Materials, Vol. 44,
1944, p. 1051) .
'
.4 Typical Water Analyses for Classification with Reference to Industrial Use,'by W. D. Collins (Proceedings, American Society for Testing Materialsi Vol. 44, 1944,
p. 1057).
* A.S.T.M. Standard I)-596--41 (American Society for Testing Materials).
7 Discussion oh Preventing Solution of CO in Condensates, by E, W. Guernsey
(A.S.H.V.E. Transactions, Vol. 51, 1945, p. 69).
'
.
* Studies of the Mechanism of Solution of.GOj in:Condensates Formed in Steam Heating Systems of Buildings,,by L. F. Collins (A.S.H.V.E. Transactions, Vol. 51,
1945, p. 39).
* The Analytical Control of Anti-Corrosion Water Treatment, by W. F. Langelier (Journal, American Water Works Association, Vol. 28, 1936, p. 1500).
14 Surface-Active Properties of Hexametaphosphate, by G. B. Hatch and Owen Rice (Industrial and Engineering Chemistry, Vol. 31,1939, p. 51).
II Slime Control in Cooling Equipment with Phenol Derivatives, by J. A. Holmes (Proceedings, Annual Water Conference, Engineers Society of Western Pennsylvania, 1944, p. 61).
" Tuberculation of Mains as Affected by Bacteria, by H. G. Reddick and S. E. Linderman (Journal, New England Water Works Association, Vol. 46, 1932, No. 42).
11 Microbiological Anerobic Corrosion of Steel Pipe Lines, by R. F. Hadley (The Oil and Gas Journal, September, 1939).
14 Tests of Corrosion Inhibitors for Water Treatment in Air Conditioning Equip ment, by James H. Wilson and E. C. Groesback (Research Paper 1305, National Bureau of Standards Journal of Research, Vol. 24,1940, p.665).
14 The Control of Corrosion in Air-Conditioning Equipment by Chemical Methods, by C. M. Sterne (Proceedings, American Society for Testing Materials, Vol. 38,1935, Part 2, p. 261).
14 Cold Water Vacuum Deaeration, by S. T. Powell (Proceedings, Water Confer ence, Engineers' Society of Western Pennsylvania, 1945, p. 51).
17 Corrosion--Causes and Prevention, by F. N. Speller (McGraw Hill Book Co.< 1935, p. 366).