Document NeQD67aoJ1v6kkgBmN7xo4kjp
508
Chapter 26
1945 Guide
A section of a typical counter-flow tower is shown-in-Fig.- 4:--If- the
reduction in water rate due to evaporation within the volume is neglected,
the energy balance for this differential section of the exchanger volume
may be written as:
.,
L c dt = G dh
"- -_
(2)
The potential for net energy transfer due to heat and mass transfer from the water to the mixture in contact with it may be expressed with reasonable accuracy as the difference between the enthalpy of saturated air at the water temperature, An, and the enthalpy of the main stream air vapor mixture7, Aa. The rate of energy transfer is given by the expression:.
Ka (A" - A*) dV
(3)
which equation defines the over-all rate coefficient, Ka; the latter being
Fig. 5
Temperature Enthalpy Diagram for Air Water Vapor Mixture Showing the Operating Line for Example 1
the product of the over-all energy unit conductance, K, and the ratio of the transfer surface to the exchanger volume, a.
Equations 2 and 3 are conveniently illustrated by means of the tem perature-enthalpy diagram of Fig. 5. Equation 2 indicates that the succession of air and water states existing in the exchanger sections must combine to form a straight line (for L = constant) on the temperature
enthalpy diagram. The slope of this operating line is
Since
dt G
the heat capacity of water is approximately unity, this slope is the ratio
of the water to the air rate. Equation 3 indicates that the potential for
energy transfer at any section is the difference between the enthalpy of saturated air at the main-body water temperature at that section and the enthalpy of the air stream in contact with that water. This potential is
the difference in the ordinates of the saturation and operating lines for
the water temperature at the plane in the tower which is under con sideration.
'Determination of Unit Conductances for Heat and Mass Transfer by the Transient Method, by A. L. London, H. B. Nottage and L. M. K. Boelter (Industrial and Engineering Chemistry, April, 1941, Vol. 33, p. 467).
Spray Equipment___________ __ ________________ '
__________________ :_______________________ ___
509
--Combination of Equations 2 and 3 results in the^expression :
Gdh = Ka (A" - K) dV
(4).
Integrating this equation over the length of the exchanger:
G dh Ka A" - Aa
V
(5)
The integration of the left side of Equation 5 determines the tower
volume required to achieve the desired energy exchange. This summation
is readily accomplished for counter and parallel flow arrangements. G and
Ka are usually independent of the tower volume and Equation 5 then
becomes:
NTU =
l dh A' - Aa
KaV G
(6)
Where NTU is defined as the Number of Transfer Units and is a measure of the difficulty of the cooling process.
The integration is made numerically or graphically. In the graphical
integration
is evaluated as a function of Aa. This determination
involves the use of the energy balance equation integrated from one section to the section in question. The area under the curve between any two abscissae is the number of transfer units required to change the air
state from A, to hi.
An approximate value for the number of transfer units can also be determined by a simple graphical method of direct constniction on the temperature enthalpy diagram8. This method cannot be applied very satisfactorily to cooling towers as the operating range is small and the
value of the NTU is near unity.
When the relationship between the enthalpy of the saturated air and the temperature is linear over the range of water temperatures involved, it can be shown* that the logarithmic mean of the terminal potentials, Aim', is the correct driving force. This is true to a good approximation .when the water cooling does not exceed 15 F. The approximation to linearity may he determined by inspection of Table 6, Chapter 1, or the temperature enthalpy diagram of Fig. 5. If the logarithmic mean is a valid potential, Equation 6 may be written:
Ai -- A, _ KaV
AAlm -
G
and the need for the numerical integration for the determination of the
tower volume is eliminated.
The over-all rate coefficient, Xo. must be known if the tower volume is to be determined. Experiments conducted on towers containing different packing construction have yielded some magnitudes of this coefficient, evaluated on an over-all basis. These data are presented in Fig. 6 as a function of the gas mass velocity through the packing, and apply only to the particular packing structure for which they were obtained. The over-all rate coefficient (Ka) may also be a function of the water rate,
Graphical Method of Determining Number Transfer Units, by T. Baker (Industrial and Engineering Chemistry, August, 1935, Vol. 27, p. 977)*
Loc. Cit. Note 4, p. 79.