SUBJECT Rust and Corrosion - 85 Magnesia vs. FROM Mr. Harry A. Kieselbach
Kaplo
Mr. Muehleck has requested that the following
tests described by the writer at our meeting On January 22nd be furnished you in triplicate
Flease bear in mind that these tests were of
the Kitchen laboratory type and can
cators
serve only as indi-
They are subject to check by properly controlled
tests simulating actual service conditions
Purpose of Tests
1 2 3
To check reported claims by Keylo salesman that a 85 Magnesia accelerates rusting of iron pipe b Karlo inhibits rusting
To determine whether 85 Magnesia will cause conrosion electrolysis in the absence of
oxygen
Dc Kaylo
4
To determine whether 85 Magnesis made with
and asphalt emulsions exhibits less
wax
chemical ac-
tivity than the untreated product
,
Materials used in Tests
Standard 85 Magnesia Block Keylo Block
K
voltage '
Small cube of W.R. Magnesis M
Canadian Asbestos Sports H for
,
readings
only )
ePe
USAA 620128
RUSTING
| ;
Test No. 1
:.
1 Iron
filings Magnesia Kayle and
to soak submerged
855 were sprinkled on lumps of
W.R. Magnesie which had been allowed
in open dishes of tap water for 24 hours
Duration of test - 20 days
to make up for evaporation
Tap water was used
- All samples showed about the same
Thin strips of iron from / bands were placet
in open test tubes containing containing
s
b)
c d
Tap water Tap water in which allowed to soak
85
Magnesia
had
Do. Kaplo Boiled tap water
to remore air in
stoppered test tube
been rubber
Results -- Very little difference in the quantity
of sediment in E b and c A few specks in d
Kote This test was conducted at an average
of about 80 deg F. The test tubes were SUB-
temperature
of about 60 deg and about two inches
pended at an angle
return line to induce slight
abore & 1steam heating
currents in the liquids
in the
test tubes
the
convection line was warm about 50 of the time during
The return
day and about 25 during the night
ELECTROLYSIS AIF EXCLUDED
Test No. 3
Strips of iron were bolted to strips of sheet
brass and placed in stoppered test tubes containing
a Tap water in which 85 Magnesia had been
allowed to soak
b Do. Kaylo c Do. W.R. M
nesie
-$-
USAA 620129
Test tubes were supported in the manner des-
cribed for Rusting tests for a period of about two months
Results -- Kaylo showed the greatest corrosion
{
deposit at bottombottom
of test tube Magnesia showed about 1/3
that bottom 1/10 f of Karlo Magnesis showed about
that of
85: Magnesia
in the ated
completely These results indicate that with an improvement
W.R. process corrosion might be
elimin-
They also indicate the reason for the activity of
the manufacturers of Kayle insuletion in research on water-
repellency
ELECTROLYSIS AND OXIDATION
The purpose of this test was to determine whether
these materials would form electrolytes wher immersed in water and to obtain an approximation of the voltages developed between an iron pipe and a brass valve or fitting exposed to such materials under water The composition
of the brass or bronze used in the manufacture of valves
is probably different from the sheet brass used in this
test and might show somewhat different results
were
electrically Strips of iron and brass connected electrically
suspended in open jars containing tap water and
a
5 b Asbestos c
Lumps of
Magnesis
lumps ofKaplo
Canadian
Shorts
placed house
The
heating
jars were
steam boiler
and
on top of an insulated maintained at an average
temperature of about 9E de .F. The liquid level in the
jars varied due to evaporation and the contents were
allowed to dry completely three times during the test
Voltage Feadings
Brass Brass Brass Brass Brass
to Inen
Meter 20,000
ohms
per reft ^'
a b c
0.52
C.4E
C.
Volts
Volts
*
average
average
"
Current Readings Brass to Iron Meter 4,166 ohms
a b 0
600microamperes average - about 300
sc in of iron
microamperes 500
measured usst
Not
in
measured
of
measured
average - about 250
iron
a ox
USAA USAA 620130
The Iron Strips Showed Rust Deposits as follows
b c
Very little Located at level of average
Entire surface heavily About 50 of surface
water
covered
Extending
down
from
As the test proceeded & deposit over the contents of the Magnesia jar and
formed in the Kaylo jar immediately under
of rust settled
a dark green deposit
the iron electrode
General
On the basis of these crude tests the writer
believes it safe to assume that Kaylo will not cause less
rust or corrosion electrolysis than 85 Magnesia on
piping submerged under water
be the CESS
In fact the opposite may
It appears that accurate laboratory tests siru-
~...
lating actual service conditions conditions could be used to
in overcoming the claims made by this competitor advantage
HAR BE
Very truly yours
-
t=
.
.
-
.
a ena
ee ee toh aE
on7s 4a
H. A. Kieselbach