CHAPTER 29
1965 Guide And Data Book
For balancing, air systems may be equipped with dampers
in supply, return, and outdoor air ducts, splitter dampers, or
dampers in outlets. In selecting the desired type of damper
or balancing method, the following points should be kept in
mind:
*'
1. Unfavorable effect on air stream and noise level should be avoided. This will often rule out blank-offs or dampers in out lets, unless such dampers are of special design.
2. It should be posable to alter outlet volume without'alteN
ing the direction of discharged air, and to measure the amount
of air handled without difficulty. Blanking off part of the area
of supply outlets
this difficult.
Generally speaking, it is most satisfactory to install
dampers at some distance back of outlets so as to avoid
disturbing the air flow. Dampers in both supply and return
ducts form the most flexible means of controlling supply of
air to the room and static pressure within the room: (Refer
to Chapter 30 for discussion of various air distribution control
devices.)
1
"'
Instruments for balancing include instruments for meas
uring air quantities, static pressure, temperature and hu
midity. Commonly used instruments are the rotating vane
anemometer, deflecting vane anemometer; thermal ane
mometer, smoke gun, clamp type ammeter-voltmeter, sling
psychrometer and thermometers. Pressure, humidity and
temperature recorders are sometimes useful. The Pitot tube
and a manometer may be used on higher velocities, but
only with the technique prescribed for its use-by the manu
facturer for the tube used. (See Air Flow Measurement in
Chapter 16.)
The following balancing procedure is recommended for air
systems:
1. Open all duct and outlet dampers.
2. Measure fan capacity. This can most often be done with a
rotating vane anemometer inside the fan inlet plenum. For ex haust fans the discharge outlet will often serve.
3. Measure fan motor input.
' ;,
4. Begin balancing the supply system at the last outlet on the
branch farthest from the fan (branch number 1). This is outlet
Dumber 1, number 2 is the next to last outlet.
-
5. Measure the air flow at outlet number l'(Q) and compare
with the design air flow fqr that outlet (Qj), record the ratio,
(.QJQ*).*
6. Measure the air flow at outlet number 2 and determine the
ratio {QJQi)t. Compare (Qm/QJ)* and (Q/QA.
7. If these ratios are not within 10 percent of each other, adjust
outlet number 2 to bring ratios into closer agreement. . Do ant
adjust outlet number 1.
8. Measure and again determine (Q^/Qj)i and (Qm/Qe)i and
compare. If these are within 10 percent of each other, no further
adjustment is necessary. Proceed to outlet number*3.
9. Determine (QJQd)t and compare with (Qm/Q*)\- If necee-.
saiy, adjust number 3 so that (Qm/QJ)s and (QwjQJ)do not vary
by more than 10 percent. Do not adjust outlets I art. (Adjustment
of outlet 3 automatically changes the Qm/Qi ratios of ontlets 2
and 1. The ratios for all these outlets approach the same values.
For this reason, once the outlet has been adjusted, it does not re
quire further adjustment.)
10. Proceed to outlet number 4 and adjust to obtain agreement
between (QAQA and (Q_/&)>-
11. After all outlets on branch number 1 are proportionately
balanced to each other, proceed to branch number 2, etc.
12. Upon completion of proportionate balancing of all outlete
the branches should be proportionately balanced.
13. Select typical outlets in branches 1 and 2.... Adjust
number 2 branch damper to obtain agreement of the Qm/Qi ratios
for the two branches. Proceed in like manner to obtain agreement
between branches 2 and 3,3 and 4, etc..
14. Upon completion of proportionate balancing, recheck the
fan capacity. Adjust the fan speed to obtain a Qm/Qi ratio of 1.0
at the fan. Since the system has been proportionately adjusted,
the Qm/Qi ratio throughout the system wiu bo approximately 1.0
and the flow from each outlet will be the design air flow rate.
(The fan laws apply when changing speeds; 'quantity varies directly with speed--power input as the cube of speed.) Use power input readings to check possibility of overloading the motor.
The procedure outlined may be shortened depending on
the type of installation. For instance, where many outlets
serve one room, exact balancing of each outlet may not be
required, so long as drafts, noise, and temperature differences
are checked. Experience and judgment are valuable in de
termining how carefully or thoroughly, a system must be
tested and adjusted.
REFERENCES
1 Alfred Koestel and G. L. Tuve: ASHAE Research Report No. 1553--Performance and evaluation cf room air distribution systems (ASHAE Transactions, VoL 61, 1955, p. 533), and J. J. Reinraann, Alfred Koestel, and G. L. Tuve: ASHKAE Re search Report No. 1697--Evaluation of three room air distri bution systems for summer cooling (ASHRAE Transactions, Vol. 65, 1959. p. 717).
* John Rydberg and Per Norback: ASHVE Research Report No. 1362--Air distribution and draft (ASHVE Transactions, VoL 55, 1949, p. 225).
* F. C. Houghten, Carl Gutberlet, and Edward Witkowski: Draft temperatures and velocities in relation to skin temperatures and feeling of warmth (ASHVE Transactions, VoL 44, 1938, P- 289).
* H. E. Straub, S. F. Gilman, aind S. Konzo: Distribution of Air Within a Room For Year Round Air Conditioning--Part I (Uni versity of Illinois Engineering Experiment Station Bulletin No. 435. July 1956) and H. E. Straub and M. M. Chen:.Distribution of Air Within a Room For Year Round Air Conditioning--Part II (University of Illinois Engineering Experiment Station Bulletin No. 442, March 1957).
* J. Rydberg: Perforated Ceilings For Air Injection (Kylteknisk Tidsfcrifl, nr 2, April 1963.
* J. Rydberg: Cooling Effects and Air Quantities Permissible in Space Air Distribution (Kylteknisk Tidskrift, nr 3, June 1963.
I G.L.Tuve: ASHVE Research Report No. 1476--Air veloci ties in ventilating jets (ASHVE Transactions, VoL 59, 1953, p. 261).
* H. B. Nottage, J- G. Slaby. and W. P. Gojsza: ASHVE Re search Report No. 1458--Outlet turbulence intensity as a factor in isothermal-jet flow (ASHVE Transaction's, Vol. 58, 1952, p. 343).
* G. E. McElroy: Air Plow at Discharge of Fan-Pipe Lines in Mines (U. S. Bureau of Mines Report qf Investigations, R. I.. 3730, November 1943, p. 19).
' Alfred Koestel, Philip Hermann, and G. L. Tuve: ASHVE Research ReportNo.-1366--Air streams from perforated panels (ASHVE Transactions, Vol. 55,1949, p. 283)- -
II Air Diffusion Council Test Code 1062 III.(Air Diffusion. Council).
** Alfred Koestel, Philip Hermann, and G. L- Tuve:' ASHVE Research Report No: 1404--Comparative study of ventilating jets from various types of outlets (ASHVE Transactions, Vol. 56, I960, p. 459).
u R. D. Madison andW. R. Elliot: Throw of air from slots andjets (ASHVE Journal Section, Heating, Piping and.Av Condi-, Honing, November 1946, p. 108).
Entrainment in Ventilating Jets (Case Institute of Tech nology, unpublished paper).
u H. B. Nottage, J. G. Slaby, and W. P. Gojsza: ASHVE Research Report No. 1443--Isothermal ventilation--jet funda-) mentals (ASHVE Transactions, VoL 58,1952, p. 107).
Alfred Koestel and J. B. Austin, Jr.: ASHAE Research Re port No. 1580--Air velocities in two parallel ventilating jets (ASHAE Transactions, VoL 62,1956, p. 425).
17 Alfred Koestel: ASHAE Research Repost No. 1618--Jet velocities from radial flow outlets (ASHAE Transactions, VoL 63,1957, p. 505).
11 Alfred Koestel: ASHAE Research Report No. 1534--Paths of horizontally projected heated and chilled air jets .(ASHAE Transactions, VoL 61,1955, p. 213).
* Alfred Koestel: ASHVE Research Report No. 1512--Com-, puting temperatures and velocities in vertical'jets of hot or cold , air (ASHVE Transactions, Vol. 60, 1954, p. 385).
Space Air Distribution
551
* D. W. Nelson, D. H. Krans, and A. F. TuthOl: ASHVE, Research Report No. 1155--The performance of stack heads ' fASHVE Transactions, Vol. 46, 1940, p. 205). ^ *> D. W. Nelson, D. H- Lamb, and G. E. Smedberg: ASHVE Pftf.Hflg Report No. 1206--Performance of stack beads equipped with grilles (ASHVE Transactions, VoL 48,1942, p.
27o9).b- ; W7 Nelson and G. E. Smedberg: ASHVE Research Report No. 1226--Performance of side outlets on horizontal ducts (ASHVE Transactions, VoL 49,1943,jj. 58). ' ** Alfred Koestel and G. L. Tuve: ASHVE Research Report No. --The discharge of air from a long'slot (ASHVE
Transactions, Vol. 54, 1948, p. 87). * Alfred Koestel and C. V. Young: ASHVE Research Report
No. 1429--The control of air streams from a long slot (ASHVE
Transactions, Vol. 57,1951, p. 407). 0 Testing and Balancing Manual for Ventilating and Air Con
ditioning Systems. (Veatilatingand Air Conditioning Contractors Association of Chicago).
BIBLIOGRAPHY
Note: This guide to the literature on air distribution is pur-' posely restricted to papers resulting from research sponsored by ThbAmrucan Soqett op Heating and Ara-CoNDmoioNa Enginbss and other easily accessible material.
ASHAE Research Laboratory
Cyril Tasker: ASHVE research in air distribution and air duct friction (ASHVE Journal Sechon, Heating, Piping and Air Conditioning, April 1948, p. 125).
H. B. Nottage: Ventilation Jets in Room Air ' Distribution. Originally submitted as a Ph-D. thesis to Case Institute of Tech nology (3 volumes). Loan copies available from ASHRAE.
Volume I: Data and Interpretations of Teste for Ventila tion Jets Discharging Horizontally into a Large Confining Space (131 pages + 67 figs. + 9 tables).
Volume II: Appendix A. Survey of the Literature on the Problems of Ventilation Jets and the Related Fundamentals of Turbulent Flow (499 pages incl. figs, and tables).
Volume HI: Appendixes B to H. General Features of lhe Experimental Installations, Instrumentation, and Operations, Boundary-layer Theory and Work-energy Treatment (142 pages incL figs.).
He following papers baaed on the above report have been pub lished:
H. B. Nottage: ASHVE Research Report No. 1360--Turbu lence--a fundamental frontier in air distribution (ASHVE Transactions, Vol. 55, 1949, p. 193).
H.B. Nottage: ASHVE Research ReportNo. 1402--A simple heated-thermocouple anemometer (ASHVE Transactions, VoL 56, 1950, p. 431).
H. B. Nottage, J. G. Slaby, and W. P. Gojssa: ASHVE Re search Report No. 1443--Isothermal ventilation-jet funda mentals (ASHVE Transactions, VqL 58, 1952, p. 107).
H. B. Nottage, J. G. Slaby, and W. P. Gojsza: ASHVE Resrabch Report No. 144!--A V-wire direction probe (ASHVE Transaction, Voi. 58, 1952, p. 79).
H. B. Nottage, J. G. Slaby, and W. P. Gojssa: ASHVE Re search Report No. 1458--Outlet turbulence intensity as a fac tor in isothermal-jet flow (ASHVE Transactions, VoL 58, 1952. p. 343),
H. B. Nottage, J. G. Slaby, and W. P. Gojssa: ASHVE Ressarcb Repost No. 1461--A smoke-filament technique for ex perimental research in room air distribution (ASHVE Trans actions, Vol. 58, 1952, p. 399).
H. B. Nottage. J. G. Slaby, and W. P. Gojsza: ASHVE Ressabch Report No. 1459--Exploration of a chilled jet (ASHVE raANSACnoNS, VoL 58, 1952, p. 357).
ASHAE Cooperative Research at Case Institute of Tech nology
G. L. Tuve, D. K. Wright, Jr., and L. J. Seigel: ASHVE Re search Repost No. 1140--The use of air velocity meters (ASHVE Transactions, VoL 45, 1939, p. 645).
G. L. Tuve and D. K. Wright,.Jr.; ASHvi/ Rsssabch Report
No. 1163--Air flow measurements at intake and discharge open ings and grilles (ASHVE Transactions, Vol. 46, 1940, p. 313).'
G. L. Tuve, G. B. Priester, and D. K.-Wright, Jr.: ASHVE Research Report No. 1204--Entrainment and jet-pump action
of air streams (ASHVE Transactions, VqL 48, 1942, p. 241).
G. L. Tuve and G. B. Priester: ASHVE Research . Report No. 1248--Control of air streams in large spaces (ASHVE
Transactions, VoL.50, 1944"p. 153). .
Alfred Koestel and G. L. Tuve: ASHVE Research Report No. 1328--The discharge' of air. from a long "slot (ASHVE
Transactions, .VoL 54, 1948, p..87).
Alfred Koestel, Philip Hermann, and G. L. Tuve: ASHVE Resbabch Repoht No. 1366--Air streams from perforated panels
(ASHVE Transactions, VoL 55, 1949, p. 283).
Alfred Koestel, Philip Hermann, and G. L. Tuve: ASHVE Research Report No. 1404--Comparative study of ventilating'
jets from various types of outlets (ASHVE,Transactions, Vol
66, 1950, p. 459). . Alfred Koestel and C. Y. Young: ASHVE Research Report
No. 1429--The control of air streams from a long slot (ASHVE
Transactions, VoL 67,'1951,.p..407).
,.
G. L. Tuve: ASHVE Research Report No. 1476--Air veloci ties in ventilating-jets (ASHVE Transactions, Vol. 69,1953, pi
261).
ASHVE Cooperative Research at Kansas State College
Linn Helandcr and C. V. Jakowatz: ASHVE Research Re port No. 1327--Downward projection of heated air (ASHVE
Transactions, Vol. 54, 1948, p. 71).
Linn Helander, S. M. Yen, and R. E. Crank: ASHVE Re search Repost No. 1475 (In cooperation with the Industrial
Unit Heater Asociotion)--Maximum downward travel of heated jets from standard long radius ASME nozzles (ASHVE
Transactions, VoL 59, 1953, p. 241).
Linn Helander, S. M. Yen, and L. B. Knee: ASHVE Re search Report No. 1511--Characteristics of downward jets of heated air from a vertical delivery discharge unit heater (ASHVE Transactions, Vol. 60, 1954, p. 359).
S. M. Yen, Linn Helandcr, and L. B. Knee: AfiHAF, Research Repoht No. 1562--Characteristics of downward jets from a verti cal discharge unit heater (ASHAE Transactions, Vol. 62, 1956,
p. 123). Lina Helander, S. M. Yen, and Wilson Tripp: ASHAE Re
search Report No. 1601--Outlet characteristics that affect the downthrow of heated air jets (ASHAE Transactions, VoL 63,
1957, p. 255). Rudiger Knaak: ASHAE Research Report No. 1619--Veloci
ties and temperatures on axis of downward heated jet from 4-inch long-radius ASME nozzle (ASHAE Transactions, Vol.
63, 1957, p. 527).
ASHVE Cooperative Research--General
E. L. Davies: ASHVE Research Reports No. 857, 911, and 966--Measurement of the flow of air through registers and grilles (ASHVE Transactions, Vol. 36, 1930, p. 201; Vol. 37, 1931, p. 619; and Vol. 39,1933, p. 373).
D. W. Nelson and D. J. Stewart; ASHVE Research Report No. 1076--Air distribution from side wall outlets (ASHVE Transactions, Vol. 44,1938, p. 77).
A. M. Greene, Jr. and M. H. Dean: ASHVE Research RspobtNo. 1092--The flow of air through exhaust grilles (ASHVE Transactions, VoL 44, 1938, p. 387).
D. W. Nelson, D. H. Krans, and A. F. Tuthill: ASHVE Re search Report No. 1155--The performance of stack heads (ASHVE Transactions, Vol. 46, 1940, p. 205).
A. P. Krate, A. E. Herehey, and R. B. Engdahl: ASHVE Re search Report No. 1165--Development of instruments for the study of air distribution in rooms (ASHVE Transactions, VoL
46, 1940, p. 351). D. W. Nelson, D. H. Lamb, and G. E. Smedberg: ASHVE
Research Report No. 1206--Performance of stack heads equipped with grilles (ASHVE Transactions, Vol. 48, 1942, p.
279). D. W. Nelson and G. E. Smedberg: ASHVE Research Rb-