CHAPTER IS 1948 Guide Cooling Load 289 It is Assumed that.both the motor and the driven equipment arq within the conditioned space. If the motor-is without the space, then do not divide by the motor efficiency in Equation 19. The load factor is merely the fraction of the rated load which is being delivered under the conditions of the .cooling-load estimate: Motor efficiencies may be approximated as follows: about 50 to 60 per cent at J'jj hp rating, increasing to 80 per cent , at 1 hp, and to 88 per cent at 10 hp and above. Appliances. Care must be taken in a cooling-load estimate to properly account for the heat gain from-all appliances, electrical, gas, or steam. Table 23 presents recommended data I6. Note that the maintaining rate in Table 23 is-the heat input required to-maintain the appliance at the'normal operating temperature even though it is not being used; t.e.yno coffee is being made, no toast is being made, no food is being cooked in the fry kettle, etc. The maintaining rate is useful in setting up a lower limit to the heat gain to a room- from.the.apphance when in operation. Experienced judgment must be used in the application of data given in Table 23. Consideration must be given to the heat contributed by appliances which are in use at the time of peak load. The -quantity of heat will depend upon whether products of combustion are vented to a flue, whether they escape into'the space to be conditioned, or whether appliances are hooded allowing part of the heat to escape through a stack. There are no generally accepted data available on the effects of venting and shielding heating appliances but it is believed that, when they are properly hooded with a positive fan exhaust system through the.hood, 50 per cent of the heat will be carried away and 50 per cent dissipated in the space to be conditioned. The same effectiveness of the hood should be figured for both latent and sensible heat. LOAD FROM MOISTURE TRANSFERRING THROUGH PERMEABLE BUILDING MATERIALS The diffusion of moisture through all common building materials is a natural phenomenon which is always present to a greater or lesser degree. The rate of moisture transfer through :unit area of a material may be expressed, as proportional to the vapor pressure difference between the adjacent air on the two sides of the material, and proportional to an over all moisture transfer coefficient called the permeability of the. material. Permeability is a characteristic of the material and of the surface, transfer conditions prevailing for moisture transfer; its magnitude is expressed as {grains, of moisture) per (square foot) (hour) (inch of mercury vapor pressure difference). Permeability values 17 are given in Table 24. , In the usual.comfort air-conditioning application, it is common practice to neglect moisture transfer through walls, for the actual rate is quite small and the corresponding latent-heat load is hardly significant. Socalled vapor barriers are frequently employed in modem construction for the purpose of keeping moisture transfer to a minimum, particularly, because of the deteriorating and insulation-destroying effects of moisture! Industrial jobs, on the other hand, frequently call for a quiet low moisture content to be. maintained in a conditioned space: Here the matter-of moisture transfer cannot be neglected; indeed, it is quite possible to have the latent-heat load accompanying this transfer be of greater magnitude than any other latent-heat load. The equation for computing this load is: (-J-) - (Permeability) X . K')076-Btu Per (hr) (sq ft). (20)