Document NGkv7e0jvpDRdnEJOEQGENbZp
(U<$s) Tiger Brand High Temperature
Applications:
For leads to motors, trans formers, etc. where 'high temperature conditions exist and a flexible cable is re quired. Motor lead cable can withstand continuous high temperature without deterioration and can be used in either wet or dry locations.
Conductor Temperature
200C (Mox.-lntermittent Service)
Specifications:
Copper Conductor--Annealed uncoated
Insulation--Silicone rubber
Outer Covering--Asbestos braid
Finish-Black FHM (flame, heat, and moisture re
sistant)
'
--
This product is manufactured and tested in ac cordance with IPCEA Publications S-19-81 and S-28-357 where applicable and Underwriters' Lab
oratories requirements for type SA.
TB1-402 HIGH TEMPERATURE
Type SRI Apparatus Motor Lead Cable Table SR-ML
ULTypeSA Single Conductor
600 VOLTS
Oats Issued: May, 1973
Size AWG
14 12 10
8 6 4
2 1 1/0
2/0 3/0 4/0
250* 300*
350* 500*
No. of Strands `
41 65 104
49 133 133
133 259 349
349 475 475
475 475
475 475
Insulation Thickness
64th s Inch
.045 .045 .045
.060 .060 .060
.060 .080 .080
.080 .080 .080
.095 .095
.095 .095
Braid Thickness
Mils
45 45 45
45 45 45
45 45 45
45 45 45
45 45
45 45
Approx. O.O.
Inches
.262 .281 .310
.400 .441 .500
.567 .609 .678
.732 .793 .844
.925 .980
1.041 1.224
Approx. Net Weight Lbs./1,000 ft.
33 42 64
112 150 213
313 427 473
583 726 841
1028 1192
1405 1941
Packing
500* Coils 500' Coils 500' Coils
500' Coils 500' Coils 1000' Reels
1000' Reels 1000' Reels 1000' Reels
1000' Reels 1000' Reels 1000' Reels
1000' Reels 1000' Reels
1000' Reels 1000' Reels
& Diameter subject to 5% tolerance. For ampacities refer to Page TB1-801.
For conduit sizes refer to Page TB 1*802. * Same as Table SR-MLA
U.9.S. AND TICER BRAND ARE REGISTERED TRADEMARKS.
PLAINTIFF'S EXHIBIT
USY-/3
ARCHITECTS/ENGINEERS
How to specify this product ; for purchasing purposes: j
"Cob/e shall be U. S. Steel I
Tiger Brand TBI*402
j
or approved equal"