Document NGbJqVEQ0VVEabzJEje48M3Vb

American Society of Heating and Ventilating Engineers Guide, 1931 2. The drop in pressure in the mains and riser to the farthest heating unit should nTM exceed 1 oz. per 100 ft. of straight pipe or its equivalent length, with a lower rate drop for systems with long runs. ___________________________________, J W<UVJ<VW) nJiw V SUL. luligtst actual iUil IS <j|, over 200 ft. and where the firing periods extend over several hours, resulting in pressure, fluctuating from zero to about 1 lb., the total pressure drop should not ex3 2 oz. for gravity systems. In large buildings, where boilers are under the constwl care of a fireman and a uniform pressure is maintained, and where the water-iine ference will permit, the total drop in pressure may range from 3 to 8 oz., dependii upon the equivalent length of the longest run. 4. The total allowable drop in pressure depends upon (a) the water-line difference^ (6) the equivalent length of main and riser from the boiler to the farthest heating unitAi and (c) the regularity of the pressure maintained at the boiler or source of steam supply |J 5. The water-line difference, or distance between the water line of the boiler and the low point of steam main and dry return main should be not less than 24 in., becauseo(sj the heavy drop in pressure from condensation in heating up a cold system. This'll difference should be increased 2 in. for every ounce pressure drop in the system. If thep total pressure-drop were 6 oz., the water-line difference should be 6 X 2 + 24 or 36 i0|f 6. There should be a nearly uniform drop in pressure between the source of steanjf supply and the farthest heating unit on every riser. Care should be taken, however, toS psee that the maximum allowable Velocity for smooth operation is not exceeded. ' 7. In using this method of proportioning a system, care must be exercised to see thatl no pipe carrying condensate counter to the steam is loaded to a capacity above the maximum lor the particular part of a system in question. | While the pipe size tables given in this chapter, literally followed out,?.] will doubtless serve as an efficient guide to the designer, it is impossible! entirely to eliminate the factor of good engineering judgment. Forf] example: While a given main might be calculated to begin at 5 in. and|| to end at 134 in., better practice often would make it begin at 4 in. andH end at 2j4 in., since the dryer steam and higher velocity at the entry! would compensate for smaller size at the end. % LTable 5. Maximum Allowable Capacities of Up-Feed Risers for One-Pipe Low Pressure Steam * Based on A. S. H. V. E. Research Laboratory Tests Pipe Size A' i 1M m 2 m 3: i'A 4 Velocity Feet fee Second B- 14.1 17.6 20.0 23.0 26.0 29.0 31,0.. 32.0 Pressure Dbop Ounces raa 100 Ft. C 0.68 0.66 0.66 " 0.57 0.54 0.48 0.44 0.39 So. Ft. Radiation D 45 98 152 288 464 799 .1144.. 1520 Capacity B.t.u. per Hour E 10,961 23,765 36,860 69,840 112,520 193,600 277,000 368,000 Lb. Steam per Hoar. F 11.-3 24.5 38.0 : 72.0 , 116.0 199.8 .286.0 380.0 ' INSTRUCTIONS FOR USING TABLE 5 1. Capacities given in Table 5 should never be exceeded on one-pipe risers. 2. Capacities based.on M Jb. condensation per square foot equivalent radiation and actual diameter of standard pipe.'....... "* ~-_c`........ ` ' ....... ^ 3. All pipe should be'well reamed and free from constrictions. Fittings should be up to size. (Set g Tables 7 and 8). 156 Chapter 10--Piping for Steam Heating Systems MAfe-Pipe System air-vent one-pipe system (Fig. 1) is considered by many engineers '--plest steam circulating system. It may be either of the ' atmospheric or oofi the vacuum type dep--e--n-d--i-n-og o.n..w__h_e_t_h_e_r or not vacuumtype or non-return air valves are used on radiators and return mains. ; If vacuum-type air valves are used the entire system must be tight and 'reasonably free from air leaks through supply valves, piping and boiler trimmings. Each radiator has but a single pipe connection, through which steam i must enter and through which the condensation also must return flowing --in the opposite direction to the steam flow. The main from the boiler should pitch downward from the highest point above the boiler, and at the end of this main it should drop down and be sealed independently below the boiler water line. This may be done at, the remote end of the Tmain or the main may loop back, above the boiler water line, to a point Onear the boiler, where it may be more convenient to seal it. Steam , and condensation flow in the same direction in-this , supply main and the branches from the main are taken off the top. : >. The ends of the supply mains, before they are sealed below the water . line, must be vented. Each radiator must haye an air valve; Perfect - grading of the mains and radiators sp that no pools of water will lie in depressions in the pipes is imperative with this system, since these water pools always cause objectionable noise. Radiators with this system usually, require that the supply valve, be all-open or all-closed, since any intermediate valve-position is likely to :cau^e interference with the neces sary return of condensation. It should be emphasized that ih any part'of a system in which water from the heating units returns counter: tO;. the steam the velocity?:of the