CHAPTER 32
1955 Guidfc'
c
< o' " 3 2Q
rHo ^Cs>
r
1
figurecLseparately.)--The .d-ucf ZenjyfA of- any section -should include - the equivalent length of any elbows occurring within the section.
The static regain charts are intended primarily for constructions where regain takes place unaccompanied by radical change in direction; thus, in Fig. 14 they are strictly applicable along the main run A to E, and at the junction of Sections F and G, but not at the junction of Sections A and F. Although some regain will usually occur at the branch take-off (where velocity is generally reduced), there are so many varieties of elbows and branch take-off connections, that estimation of an average value of regain would be quite impracticable.
The static regain method finds its widest application in the design of long duct runs containing numerous successive outlets (usually designated the
Air Duct Design
745
outlet run). An outlet run is typified by Sections C-D-E in Fig. 14. On larger systems several methods of duct sizing may be combined to secure equal or approximately equal pressures at all outlets. Example 6 shows the method of approach as applied to a very small system.
As with any other method of duct design, balancing dampers should be
installed in each branch, and each outlet should be equipped with means
of regulating air volume.
'
Example 6: (Static Regain Method). A duct layout is shown in Fig. 14. The fan delivers 8000 cfm. Outlets 1, 2, 3 and 4 deliver 1500 efm each, and outletB 5 and
6, 1000 cfm each. The operating pressure loss at all outlets is 0.12 in. water. Initial trunk velocity is assumed as 1500 fpm; the area of the trunk duct will-then be 5.33 sq ft, and the size will be 48 x 16 in. It is assumed that for this example it is de sirable to maintain a 16 in. depth on all duct sections. Determine the sizes of duct sections B, C, D, E, F and G so that substantially the same static pressure will be obtained at each of the outlets, and find the total pressure-loss of the system.
Fio. 14. Duct Layout fob Example 6
Solution: . 1. Size Section F by the equal friction method so that it has the same rate of motion loss as Section A. Section A is equivalent to a 29.2 in. round duct (Table 2) and the pressure loss from Fig. 2 is 0.13 in. per 100 ft. For 2000 cfm flowing at this rate of pressure loss, the indicated round duct diameter for Section F is approximately I7 in. (Fig. 2). This is equivalent to a 15 x 16 in. duct, which will be used for Section F, The velocity in Section F will be 1200 fpm.
IDete.rm>ne the pressure loss in Section F. Actual length of duct is 10 ft: equiva lent length of elbow take-off is assumed as 10 W, or 12.5 ft.. Therefore, the total
equivalent length is 22:5 ft. The pressure loss in F = 0.13 in. X = 0.03 in. water.
, Usiug Static Regain Chart, Fig. 13, size Section B for a net pressure loss equal to the loss m F, or 0.03 in. water as follows:
affrvn^l ti- y .------------v,
vui TCU-iuiCT-W-micnfCUl-kUB-UI*"
lin nal j/Se Llne' From tlu8 point, rise vertically to the 0.03 net static pressure loss
ne, and from this intersection proceed horizontally to the Air Velocity Base-Line.
*ndC?K paralIel to curved lines to intersect ordinate for 25 ft equivalent duct length, ana then move horizontally to left margin and read the velocity (1500 fpm).
Since Section B carries 6000 cfm, the area required.will be~|j ~ 4 sq ft, and the size of duct will be 36 x 16 in.
E ^a**c Regain Charts (Figs. 12 and 13) determine size of Sections C, D, U*' allowing 0.03 in. net loss, which was used for Section B,
. "7 ,m \ne diagonal Base Line vertically to the no gain or loss diagonal. The frnm6?nfn r ec*-iu E is shown by the dotted line and arrows on Fig. 12: starting
" lu*0 fpm velocity, which is the velocity in Section D.
Duct sizes determined by the given procedure are listed in Table 7 on next page.