Document NErOG1dwN7xyM1bKq5N5Gwyd8

TABLE OF CONTENTS /- SECTION A TRANSFORMER ASKAREL I. Introduction II. History of Trade Name Types Table I - The Composition of Transformer Askarels III. Interchangeability IV. Table II - Official Transformer Askarel Shipping Specifications V. Ordering Instructions VI. Stability VII. Precautions When Handling Drums, Tankcars and When Opening Transformers A. Keep Dry During Handling . Table III- * F-- p'1'1 Te*. p * v.. B. Use Ordinary Personal Precautions C. Precautions on Opening an Askarel Transformer VIII., Avoid Environmental Pollution fi X. Labeling Askarel Transformers { X, Disposal of Liquid and Solid Hastes C,X, Conditioning of New or Recycled Askarel 0 Jr, Teardovn of Transformers for Repair or Scrap 1 y. Transformer Disposal IX. Expected Service Life X. General Characteristics of Transformer Askarel Fluid XI. Sampling Transformer Askarel Fluid XII. Evaluation of Askarel Received in New Equipment XIII. Dielectric Breakdown Voltage - Moisture Relationship Table IV - Relation of Dielectric Breakdown Voltage to Amount of Dissolved Hater in Askarel and Mineral Oil XIV. Turbidity MQNS 075205 -2- XV. Check Points for Maintaining Askarel Insulation A. General Considerations B. Modern Sealing Procedures C. The Older Sealing Arrangements XVI. Periodic Fluid Inspection and What Checkpoints Mean A. Visual Inspection B. Dielectric Breakdown Voltage XVII. Inspection Checklist XVIII. Contamination in Transformers Table VI - Effect of Common Insulation Materials on power Factor and Dielectric Strength Table VII* Effect of Common Insulation Materials on Volume Resistivity of Askarel XIX. ASTM Method For Investigating The Compatibility of Transformer Insulation and Construction Materials in Askarels XX. Refining Aakarel for Re-Use A. Filtering Through Dry Blotter Paper to Remove Moisture and Extraneous Particles Table VIII - Guide to Rate of Dissolved Water Removal by Filtering Askarel Through a Paper Press B. Disposal of Solid Wastes C. D. Earth Treatment for Maximum Improvement of power Factor and Volume-Resistivity Table IX - Volume Resistivity XXI. Cleaning Arced Transformers XXII. Sampling Askarel SECTION B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS I, Introduction II. Sources of Contamination III. Sealing Switches and Terminal Chambers IV. Askarel Used Under Mild Arcing Conditions V. Maintenance for Askarel Filled Switches VI. Askarel Under Excessive Temperature or Fault Conditions MON$ 075206 3- SECTION C ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO Types of Analyses Available: fadlbkM 1) Routine Maintenance Check Anaryafj 2) Complete Analysis 3) Analysis After Earth Refinement Appendix A Appendix B Appendix C Appendix 0 Appendix E Appendix F Appendix C Appendix H Appendix I Appendix J Appendix K Askarel Stability and Composition of Arc Formed Gas Solubility of Gas In Transformer Askarels Effect of Temperature on Dielectric Breakdown Voltage of Askarel Comparison of the Approximate Viscosity In Saybolt Universal Seconds of Transformer Askarels & Mineral oil The Density of Inerteen 54201 KA 7336-9 and Transformer pyranol A13B3B-2 Tticrmel Heat Capacity Coefficient of Expansion Fire Resistance Seals, Properties and procurement Caution Label AU3MH-3- MGNS 075207 DATE JOB _July_10, 1973________________________ ASKAREL Inspection & Maintenance Guide, IC/FF-38_____________________ ASKAREL Inspection & Maintenance Guide Technical Bulletin IC/FF-38 Section A Transformer Askarel X. Introduction The tern "askarel" as defined by IEEE* ASTM and the National Electrical Code generally describes a broad class of non-flammable synthetic chlori nated hydrocarbon Insulating liquids widely used in transformers! reactors and accessory equipment operated at power frequencies. Askarela of various compositional types are in use. (For the general properties and types see ASTM D-2283.) Under arcing conditions the gases produced, while consisting of predominantly non-combuatibie hydrogen chloride, can contain varying amounts of combustible gases depending upon the askarel type. Thla manual describes the operating characteristics of transformer askarel liquid Lnsulation and how It differs from mineral oil. Appropriate handl ing and disposal procedures for both scrap askarel liquid and impregnated solid materials are given in accordance with the guidelines recommended by the American National Standards Institute. 2-M5S-0377-6 The Information is based on facts gathered by Monsanto over 40 years as a producer of askarel, plus knowledge gained from the experience of trans former manufacturers and users. This guide outlines the very simple main tenance required for. askarel fluid in "modern" transformers and offers suggestions for sealing and maintaining askarel in old units. By following this guide, we believe users will obtain maximum service from aakarel in sulation with a reasonable minimum of maintenance. If questions arise re lating to the designing and building of transformers, these should be re ferred to regular transformer suppliers. HONS C752Q8 Monsanto -2- Monsanto gracefully acknowledges the assistance, guidance and the con tributions of certain data by the following: Edward L. Raab -- General Electric Dr. T. K. Sloat -- Vestlnghouse Electric 11. Hlatory of Trade Name Types "Askarel" Is the generic name for the non-combustible liquid Insulation and coolant first used by General Electric Company In 1932 for their Pyranol* brand name fire-resistant transformers.' Other brand names used by electrical manufacturers to designate transformer askarels used In their products Include: Asbestol** Chlorextol*** Inerteen No-Flamol Saf-T-Kuhl Whatever Che trademarked brand, the askarel contains chlorinated biphenyl - - - one of the best liquid Insulations developed by science. This Inert material Is chemically stable, fire-resistant, heat stable, non-corrosive, and has high dielectric strength under the operating conditions encountered in transformers. In addition to manufacturing Aroclor (chlorinated biphenyl), Monsanto also mixes this dielectric fluid with chlorobenzenes to produce the presently used Inerteen and pyranol blends described In Table I. Table I The Composition of Transformer Askarels __ Type D Method ASTM D 2283 Type E Type P Trade Names Inerteen 54201KA Inerteen 5420101 Pyranol A13B3B2 Inerteen 70-30 Inerteen 100-42 Ingredients ({ by wt.) Aroeloi*^1254, pentachlorobiphenyl 70 - Aroclor^l242, trlchloroblphenyl - 100 trichlorobenzene 30 "- trl-tetrachlorobenzene - - phenoxypropene oxide scavenger 0.18 to 0.22 0.18 to 0.22 diepoxlde scavenger 45 55 0.115 to 0.135 * Trademark of General Electric company ** Trademark of Carbola Chemical Company, Inc. Trademark 0 Allis-Chalmers ^Registered trademark of Monsanto Company HONS 075209 -3- ASTM Method D 2283, titled "Chlorinated Aromatic Hydrocarbons (Askarels) For Transformers". also Hats the composition of all transformer aakarels used at various times since 1932. Monsanto manufactures similar transformer askarel fluids in England where the trade name Pyroclor is used. Ill, Interchangeability In general all transformer askarels are interchangeable. However, it is suggested that the transformer manufacturer be consulted prior to mixing in significant proportions or total substitution. IV, Official Transformer Askarel Shipping Specifications The official shipping specifications for the three modern transformer askarel fluids are shown In Table II. V. Ordering Instructions Monsanto's current policy is to sell askarel transformer fluids only to transformer manufacturers. Others interested in these fluids should contact the manufacturers of askarel transformers and not Monsanto. The transformer name plate indicates the transformer maker and usually gives sufficient data to Identify the specific askarel fluid used. VI. Stability Askarel liquid insulation is highly pure, fire-resistant liquid made under close chemical control to meet the exacting specifications as shown in Table II. It does not vary in composition like the commercial range of mineral oils. Askarel insulation must never be mixed with mineral oil. Over two percent of mineral oil by volume in askarel begins to lower its fire resistance. Askarel does not deteriorate when exposed to air, heat, hot metal; It doe9 not break down over long use to form conducting or corrosive chemicals; it does not oxidize or sludge, Askarel will remain perfectly stable year after year unless broken down by severe electrical discharge. MOMS 075210 Official IHMfsiMF Askarel Shipping Specification* Specification Properties General Electric Co. Transformer Pyranol A13B3B-2 ASTM P2283 Type P Westlnghouse Transformer Inerteen 54201KA or Inerteen 70-30 ASTM D2283 Type D Westlnghouse Transformer Inerteen 54201CM or Inerteen 100-41 ASTM 16283 Type E Color, APHA Condition . Water content, ppm (ASTM D1533-60) Acidity, mg KOH/g (ASTM D974-55) Dielectric Strength,25*C,0.1 in. gap (ASTM D877-49) Dielectric Constant,100*C, 60 Hz (ASTM D924-49) Volume Resistivity, 100*C, 500 volts DC 0.1 inch gap, 109 ohm-cm (ASTM DII69) Inorganic chlorides, ppm (ASTM 01821 and O.E. Method E4C41B) Refractive Index, 25 C (ASTM DI807) Viscosity at 37.80C (ASTM D88-56) Saybolt Universal Seconds Pour Point C (ASTM D-97-57) Specific gravity 25/15.5C (ASTM D1810) Burn point (ASTM D92) Distillation range (ASTM E20-56) corrected for stem and barometric pressure Fixed chlorine Corrosion test Color, APHA Acidity, mg KOH/g Inorganic chlorides ppm Condition Scavenger content . Typical Properties Coefficient of Thermal Expansion (ASTM D1903), cmz/"Z/^X Arc formed gasea * 150 max. Clear 30 max. 0.014 max. 35 KV, min 4.2 to 4.6 100 150 max. Clear 30 max. 0.014 max. 35 KV, min 4.2 to 4.5 100 60 max Clear 35 max. 0.01 max. 35 KV, min. 4.7 to 4.9 100 - S O (A Z X 0.10 max. 0.10 max. 0.05 max. 1.6060 to 1.6070 39 to 43 1.6153 to 1.6173 1.6240 to 1.6260 56 to 6l 82 to 92 -42 or lower 1.515 to 1.525 None to boiling 1st drop 21o"C min. 35% 24o to 270 55* 290 to 330 -30 or lower 1.518 to 1.528 None to boiling -17 or lower 1.381 to 1.392 None to boiling 1st drop 200C min, 10* 325*C min. 35% below 270*C 90% 360 max. 90% 379 to 39^ 6556 365 to 380 9556 375 to 395 _ ,. ^ 58.5 f 556 55.6* min. 43+0.5* After heating with aluminum for 6 hrs. at 200 to 220 C, the aluminum must not be corroded on either visual or weight Inspection and the askarel should meet the fol lowing specifications 200 max. 200 max. 0.014 max. 0.014 max. 0.15 max. 2.0 max. Clear Clear 0.115 to 0.135* Dlepoxlde 0.18 to 0.22* phenoxy propane oxide r $00 . fl.Ol y c/sans 0.18 to 0.22* phenoxy propene oxide 0.0007 0.0007 0.00068 Pootnote 1 Footnote 1 . Askarels of various compositional types are used. Under arcing conditions the gases produce, while consisting predominantly of non-combustible hy,jrogen chloride, can Include varying amounts of combustible gases depending upon the askarel type. Insulation oystems Incorporating these askarels and celluloslc or other organic materials aay, when arced, produce gaseous mixtures which are moder ately flammable. As a precaution, ouch gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas si>nCe with dry nitrogen before any work Is performed on tho apparatus. MONS 075212 -6- In modern transformers, the only real "enemy" of askarel Is contamination by water. Keeping askarel water-free will insure long-time service. Askarel la heavier than water. If water gets into askarel Insulation, only a tiny amount (approximately 125 ppm) dissolves - - the rest floats on top, Askarel is very Insoluble in water, only about 200 parts per billion of askarel dissolve in water, at normal temperatures. VII. Precautions When Handling Drums, Tankcars, and When Opening Transformers The American Institute of Electrical and Electronic Engineers Guide No. 76, December, 1958 has been revised to give more detailed instructions and guidance "For Acceptance and Maintenance of Transformer Askarel in Equip ment" . This guide is published by the Institute of Electrical & Electronics Engineers, Inc., 345 East 47th Street, New York, New York 10017. The following are significant precautions: A. Keep Dry During Handling: In handling, storing, sampling and inspecting askarel - - and in operat ing askarel transformers - - take every precaution to guard the askarel insulation from exposure to high humidity and moisture contamination. Keep 5, 30 or 55 gallon drums of askarel dry; lay stored driaas on their sides with the bung at the highest point from floor to keep water off the drum head (which can be sucked into the askarel by the drum "breath ing"). This precaution is not necessary when drums are stored indoors, vhlch is the preferred place for storage. To avoid leakage the drums used for askarel are of heavy construction. Sixteen gauge metal is used, with special rim seal and bung construc tion. The dr line should be drained as completely as possible and then flushed twice with kerosene type solvent to remove all of the askarel. Accumulated liquids and washings should be collected and should be in cinerated at high temperatures, e.g., about 2000F, to destroy the poly chlorinated biphenyls (PCBs). See Section A, VIII. Tank cars used to transport askarels are in exclusive service and not used interchangeably for other products. All cars must be unloaded through the top (dome fitting) either by pumping or with controlled pressure using dry air or dry nitrogen. If nitrogen has been used for HONS 075213 -7- unloadlng It is necessary to advise the shipper bo that when the car returns the nitrogen can be replaced with dry air before any one say enter the car. If the car is to be unloaded by pumping it will be necessary to use a dryer on the air intake line to remove moisture. All tank cars are fitted with steam coils, which are available for unloading under extreme low temperature conditions. Convenient handling and pumping temperatures and the related approximate viscosity ranges are given in Table III. Product Pyranol A13B3B-2 Inerteen 54201KA Xnerteen 54201CM Table III ` Unloading, Handling and Pumping Tomperature "C 15-^0*. 20-55 35-75 Approximate Viscosity SUS 100-40 100-1*0 100-1*0 B Use Ordinary Personal Precautions: Transformer askarel has been made, handled, and used for over 40 years. It can be handled safely with recommended precautions. If accidentally spilled on hands, no serious skin irritation will occur. However, liquid askArel has a solvent action (similar to paint thinner) on the fats and oils of the skin and prolonged contact may lead to drying and chapping of the skin. In case of contact, wash the skin with soap and water; remove and dry clean saturated clothing. Clean up spills with rags, sawdust or absor bent clay. Eye contact may result in painful irritation but no perman ent damage to tissues. If askarel gets in the eyes, flush with large amounts of water. As with all eye first aid, refer to a physician. To relieve irritation, physicians have used an opthalmic anesthetic solu tion as well as opthalmic cortisone acetate solution, or caster oil. HONS 075214 -8- Infrequent exposure to askarel vapors will not cause 111 effects. However, prolonged exposure to high vapor concentrations should be avoided. If hot askarel must be handled in a closed or confined area, provide the area with mechanical exhaust ventilation - - or - - wear an organic cartridge respirator approved by the U.S. Bureau of Mines. C. Precautions On Opening an Askarel Transformer; Askarels of various compositional types are used. Under arcing condi tions the gases produced, while consisting of predominantly non combustible hydrogen chloride, can yield varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askarels and celluloaic or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus. Mill, Avoid Envlroisnental Pollution Transformer askarels contain polychlorinated biphenyls (PCBs) which have been used in the United States and elsewhere over the past 40 years for many industrial and consumer applications. During the past several years evidence has accumulated to Indicate that PCBs are widely dispersed throughout the environment and that they can have adverse ecological and toxicological effects. The United States Government's Interdepartmental Task Force on PCBs, Com72-10419* in their March 20, 1972 report titled, "polychlorinated Biphenyls and the Environment", recommended restricting PCBs to use in capacitors and transformers. This report is distributed by the National Technical Information Service, U.S. Department of Commerce, Springfield, Virginia 22151. MCiNS 075215 -9- A document titled, "Guidelines for Hand ling and Disposal of Capacitor and Transformer Grade AskareIs, Containing Polychlorinated Biphenyls", has been prepared and is available from the American National Standards Institute, Conuittee Cl07, 155 East 44th Street, New York, New York 10017. The scope, objectives and the composition of this committee are: Scope: ANSI Committee C107 procedures and guides for safe use, maintenance and disposal of askarel and askare1-soaked materials used in electrical equipment. Objectives: 1. Source of technical Information and advice for Federal, State, local authorities and all others concerned. 2. Encourage development of suitable disposal facilities and keep all concerned informed. 3* Serve aa the advisory group for United States participation in international organisations: CEE, IEC, CIGRE. Composition: Organisations active in or represented by this ANSI comoittee include National Electrical Manufacturers Association, Electronic Industries Association, Institute of Electrical and Electronic Engineers, American Society for Testing and Materials; Electric Light and Power Association; Certified Ballast Manufacturers Association; Environ mental Protection Agency; Office of Environmental Affairs; General Services Administration; National Bureau of Standards; Department of the Army; Rural Electrification Administration; Division of Environ mental Research, TVA; American Public Power Association, Water Pollu tion Control Federation; Food and Drug Administration; National Fire Protection Association; Underwriters Laboratories; and several sec tions of the U.S. Department of Interior. The following are pertinent excerpts taken from the ANSI Guidelines for askarel transformers: HONS 075216 10- A A', Labeling Askarel Trandbrraers "All new askarel transformers should be .labeled: Caution The Insulating Liquid In This Transformer Contains Polychlorinated Biphenyls (PCBs). Care Should Be Taken To Prevent Entry Into The Environment. In Case Of Malfunction Or Leaks, Consult The Instruction Manual Or The Manufacturer. The transformer manufacturer should make similar warning labels available for use on previously installed transformers." $ Z. ' Disposal of Liquid and Solid Wastes "Disposal of askarel fluid and askarel-soaked materials must be accom plished by means in which there is no significant release of askarel to the environment. At present, disposal is accomplished by carefully controlled high temperature incineration of liquids and soaked software; and by controlled dry land-fill burial of apparatus and other hardware from which askarel has been previously drained and washed. "Present knowledge indicates that proper incineration should Involve a suitable Uance between dwell time and temperature in the incinerator plus oxygen availability and finally suitable scrubbers to remove HCl formed; e.g., (1) two-second dwell time at approximately 2000F and 37. excess oxygen in stack gas; (2) L-l*t second dwell time at 2700F and 27. excess oxygen in stack gas." The ANSI Guide lists the locations of facilities that conform with the above requirements. Monsanto has such an incinerator at the U. G Krummrich Plant, Department A-246, Sauget, Illinois 62201, whera arrangements can be made for scrap askarel liquid disposal for a modest fee, currently 3 cents per pound. For disposal of solid scrap a con trolled dry land-fill can be used where permitted by Federal, State and local regulations. C Z* Conditioning of New or Recycled Askarel Conditioning of new askarel or recycled askarel requires Fuller's earth treatment. The spent Fuller's earth in cartridges or bags when replaced should be allowed to thoroughly drain over drip pans to remove as much liquid askarel as possible. The cartridge units of steel mesh construc tion should be placed In the "Steel Contaminated with Askarel" container for disposition. Cloth bags filled with Fuller's earth should be placed in the "Scrap Burnable Askarel Waste" container for disposition. HONS 075217 -11- Teardown of Transformers for Repair or Scrap I.*". Drain all askarel from the unit either into a holding tank for reuse or into the drum labeled "Scrap Askarel" for disposition, then allow sufficient time for all the askarel to drain from the core and coils. b. Remove the core and coil assembly from the transformer and place It on the floor. Sufficient absorbent material should be placed on the floor to absorb any askarel fluid that still drips from the trans former. 3,j. place all materials in the appropriate salvage containers during the dismantling for later disposition. `A AH used materials. Including rags, sawdust, tape, etc., regardless of quantity, should be put into the appropriate containers for dis position. t jf* Transformer Disposal The ultimate disposal of an askarel-filled transformer may be accomplished in either of two ways. I, Complete drainage and dismantling with the proper disposal of the askarel liquid and askarel-soaked components as described above. il, Jti'. Disposition of askarel transformers by means of junk or scrap dealers should be avoided unless a transformer is first drained, followed by soaking of the interior with a suitable solvent, such as kerosene. Accumulated liquids and washings axe to be disposed of as described earlier. IX. Expected Service Life Manufacturers indicate that properly designed and installed askarel trans formers are expected to give trouble-free service for at least 30 years. Since their introduction in 1932, the manufacturers report finding the over-all failure rate to be less than 0.5% for all units under test and service conditions. The Edison Electric Institute's report (1956-1958) on their member utilities publishes the failure rate for askarel transformers as 0.13 per hundred banks per year. Mr. Frank M. Clark, who invented transformer askarels at the General Electric Company in the early 1930a, made the highly pertjbent comment based on his many years of experience with G.E. Pyranol (askarel type) transformers that-- MGNS 075218 -12- "The Important thing la to keep them dry -- otherwise leave them lone'*. . These words of wisdom became especially applicable In more recent years when welding shut rather than gasketing became the main method of sealing askarel transformers. These units are sold with the understanding that the liquid la in a normally hermetically closed system. X. General Characteristics of Transformer Askarel Fluid Appreciation of the following characteristics, as given in the IEEE Guide, leads to understanding the reasons for selecting dielectric breakdown volt age and moisture as the prime practical test9 to judge the quality of trans former askarel fluid. Also, due to these characteristics the power factor of transformer askarel will be normally much higher than the corresponding values for mineral oil. In comparison to mineral insulating oil, askarel la a relatively polar ma terial; l.e., its molecules are dipoles, free to rotate around their axes and responsive to orientation by electrical forces. Askarel also exhibits a much higher dielectric constant and capacitance than insulating oil, and these differences must be kept in mind when interpreting electrical test data. Because it is relatively polar, and possesses high solvency power, askarel la much more electrically sensitive than mineral oil to traces of extraneous soluble polar materials, and consequently the choice of constructional ma terials destined for use in askarel is very critical. This sensitivity is reflected in the power factor and resistivity (specific resistance) of the eakarel. It la important to note that, with the exception of water, the dielectric breakdown voltage of askarel is not generally adversely affected by many of the soluble polar materials to which its power factor and resistivity (spe cific resistance) are so sensitive. In fact, the dielectric breakdown volt age of askarel is somewhat greater than that of Insulating oil. Therefore, the values assigned these dielectric fluids in newly supplied transformers are 30 KV min. and 26 KV min., respectively. MGNS 075219 -13- Ab with Insulating oil, aakarel must be kept dry. It can pick up moisture free exposure to humid atmosphere. Under similar conditions of exposure, askarel can pick up nearly twice as much moisture when measured on a parts per nllllon weight basis. XI. Sampling Transformer Askarel Fluid The following precautions about sampling are quoted from the IEEE Guide. "Representative samples, whether of the complete contents or only pares thereof, are extremely important from the standpoint of evaluation of the quality of the product sampled. Obviously careless sampling procedure or contamination in the sampling equipment will result in a sample that is not truly representative. This generally leads to erroneous conclusions concern-' ing quality and incurs loss of time, effort, and expense Involved In securing, transporting, and testing the sample. It is strongly recommended that all of the procedures and precautions outlined In the latest revision of ASTM D 923 (Sampling Electrical Insulating Liquids) be followed. "Because of the high specific gravity (relative density) of askarel (greater than 1), water and some other impurities are most likely to be found at or near the surface. The top sample, therefore. Is considered to represent the worst condition." XII. Evaluation of Aakarel Received in New Equipment Some users of askarel equipment find it desirable to make "as received tests" on all equipment. It is quite common to use the dielectric breakdown voltage test and visual appearance as the most significant tests. If suitable equip* Bant and trained personnel are available additional information may be obtained from the power factor, color, and moisture content tests. In sampling askarel contained in apparatus extreme care must be exercised in order to obtain a representative sample. ASTM Method D 923 should be followed. New equipment with askarel exhibiting the following characteristics is con sidered acceptable: MONS 075220 -14 Dielectric Breakdown Voltage Color Condition - Visual Water content Power Factor at 25C 30 KV min. 300 max. (Straw color) Clear 35 ppm max. * ASTM Methods D 877 D 2129 D 1702 D 1533 D 924, D 150 The power factor of askarel taken from new transformers, reactors and accessory equipment can reflect the presence of moisture, dissolved polar compounds, or other contami nants and may vary with the type of equipment from which the sample was taken due to the different ratios of liquidto-solld insulation and to the high solvency power of the askarel. Given an acceptable water content and dielectric breakdown voltage of the askarel as indicated above, a high power factor seldom impairs the serviceability of the askarel within rather broad limits and is Indicative of the degree of extraneous soluble polar materials pres ent. Recognizing the possibility of a wide range of power fac tors being recorded for askarel in new equipment, it is difficult to establish a single limit which would be ac ceptable to both suppliers and users for all applications. However, as a broad guide, power factors up to about 10% at 25C and 60 cycles per second (hertz) do not in general indicate any abnormal contamination providing that the other criteria (water content, dielectric breakdown volt age, etc.) are met. Much higher power factors may indi cate excessive contamination or the misapplication of the solid materials used in manufacture in contact with the aakarel and ahould be investigated. XIII. Dielectric Breakdown Voltage - Moisture Relationship The dielectric breakdown voltage of aakarel is highly sensitive to excess moisture; not sensitive to ordinary dissolved polar materials. While the dielectric breakdown voltage can also be lowered by severe arcing, askarel turns noticeably black or has particles of sooty carbon floating In it if arcing haa occurred. Then the transformer should be repaired and the askarel replaced If the dielectric breakdown voltage is checked periodically and decreases significantly - - this Indicates moisture pick-up, arcing, or both. When the dielectric breakdown voltage haa dropped to 26 KV or less, an analysis for water is necessary. If water is found in excess of 40 ppm at room temperature, its source should be located and corrections made. M0NS 075221 -15- When the moisture content approaches 125 ppm (saturation level at room tem perature)* the dielectric breakdown voltage of askarel drops below the value required for efficient insulating. The moisture content should not be allowed to rise over 70 ppm, sampled at operating temperature. If the moisture con tent is found to be in a satisfactory range and the dielectric breakdown voltage is low, the transformer manufacturer should be consulted. Table IV shows the relationship of dielectric breakdown voltage vs. moisture and Table V indicates the approximate water solubility limits in askarel and mineral oil. TABLE IV Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel and Mineral Oil Vater Content (PPM) 0 20 1)0 60 80 110 Breakdown Voltage (ASTM1 Askarel Mineral Oil 70 KV 55 47 4o 38 10 50 KV 39 30 26 22 5 TABLE V * approximate solubility of water in transformer ' ASKAREL AND MINERAL OIL c. --30 --20 --10 0 10 20 30 40 Tempers tore P, --22 --4 14 12 10 68 K 104 Amount of Water (PPM) Dissolved Askarel Mineral Oil 88 Id 10 21 13 41 20 *5 33 94 58 121 85 170 130 XIV. Turbidity . .may be the visual sign of undissolved water, or may indicate dirt. Ooudineas may also result from cold precipitation of tin tetraphenyl "scavenger" that was used in the earlier pyranol transformers. This scaven ger begins to come out of solution around 15F above zero. To redissolve it requires heating to 150-200F and agitation. MOMS 075222 -16- High dielectric breakdown voltage will quickly indicate that any turbidity present is not moisture; that the insulating efficiency of the askarel is still excellent. However, if the dielectric strength is below 26 KV> mois ture should be determined, using the Karl Fischer method (ASTM D1533-60). The dielectric breakdown voltage test for askarel serves primarily as an Indicator for moisture. It Is by far the most important maintenance test for transformer askarel. XV. Check Points for Maintaining Askarel Insulation A. General Considerations: Modern askarel transformers with welded construction or silicone or Vlton* gaskets (hand hole-cover, switch and terminal compartment covers) and with properly constructed bushings require little or no maintenance. With properly constructed transformers, annual or semi-annual visual inspection and dielectric breakdown voltage test of the askarel fluid should suffice for routine maintenance checking over many years of serv ice. However, many askarel units were installed in the early 1930s - - before the development of some of the better modern gasketing materials and before improved designs were developed for sealing out moisture. Such early units should be, and can be, modernized. Leaky or deteriorated gaskets should be replaced. If the askarel has become contaminated, it should be reconditioned. At the same time, a general clean-up of the unit and possible reflnlshing may be desirable. If it is not convenient to take an old transformer out of service for general repairs, leaky gaskets can be sealed temporarily by painting over the leaky area with epoxy cement. A survey of users indicates a good number of early-built askarel trans formers (over 20 years old) are kept in continuous service in critical Installations by the following steps (instead of modernization). ^Trademark of E. I. Dupont DeNemours & Company, Inc. HGNS 075223 ! -17- The operating units are equipped with compound pressure gauges for read ing pressure above and below atmospheric. Positive pressure is maintained on the shell by introducing nitrogen at 2 to 3 pounds above atmospheric. Regular workmen In the area dally record the temperature and pressure. If a eudden pressure drop is noted more nitrogen is introduced and the gaskets are checked for leaks with soap solution. Leaks are sealed by applying epoxy cement. B. Modern Sealing Procedures: Transformer purchasers should specify the following modern techniques for sealing: ! Welding Construction: Covers, radiator connections, switch and terminal housings, instrument connections, etc. should be welded. 2. Bushing Connections: A number of bushings have been developed to obtain a proper seal for the electrical connection through the tank vail. They are classified as follows: A) Welded Type - (Bushing flange welded to tank wall) I .sri Cast resin bushing with a molded seal to the bushing stud and external stainless steel or copper flanges. Rolled flange bushing with the metal to porcelain seal at the cap and flange made by being rolled into grooves In the porcelain over silicone rubber rings. The seal between the cap and stud is made by welding. Porcelain or glass bushings with metal to glass or metal to porcelain aeals. ft Z) Bolted Type - (Bolted to tank wall) I ,/4'. Cast resin bushings with either cast or metal flanges con taining recessed gasket grooves. AS. porcelain or glass bushings with flanges containing recessed grooves or gasket stop. The gaskets may be either of rectangular or circular cross-section, usu ally 1/A inch thick. Bushings with recessed grooves are suitable to use with cork, cork-nitrile rubber combinations or nitrile rubber as well as gasket materials such as silicone or Vlton. HONS 075224 -18- 3. Snail Size Connections: When not possible to veld, snail size connection seals should be made with Flexitallic***stainless steel rings. The surfaces must be machined and parallel. The filler between the steel laminations of the Flexitallic ring should be either silicone or Viton. 4. Gaskets for Hand-Hole Covers: Modern design specifies silicone gaskets. Such gaskets must be retained in a groove. The groove preferably is machined into the flange or cover. However, it can also be formed by welding concentric steel strips to the flange or the cover. Generally the gaskets should be 5/16 to 1/2 in. thick for covers, depending on the depth of the groove or stop. A rectangular cross-section Is usually used. The silicone material should be Dow-Corning No. 50 Silastic*'* or equivalent. This is a low compression set material. For best sealing 20-25% compression is recommended, with ample clearance In the groove or stop to allow for this compression. No cement is required. With reasonable care the gasket is re movable without damage and is reuseable. Silastic 50 is slightly swelled by askarel which contributes to the tightness of the seal. It is not deteriorated by askarel fluid or vapors. It resists weathering and it is thermally stable and flexible at all operating temperatures. It Is an excellent moisture barrier. NOTE: Dow-Corning, Midland, Michigan will supply a list of Silaatic 50 gasket fabricators to all transformer manu facturers or users. They will also furnish technical data. See Appendix K: Seals, Properties and procurements. C. The Older Sealing Arrangements: The older type gaskets consist of either cork or cork-nitrile rubber combinations or straight nitrile rubber. * Trademark of Flexitallic Gasket Company ** Trademark of Dow Corning HONS 075225 -19- 1. Cork-Nitrile Combinations: Covers for the main tank, hand-holes, witch and terminal chambers, relief diaphrams, etc., are held in place by studs welded to the flange or by bolts. The gaskets are cut with openings and placed over the bolts. Often Shellac (Westlnghouse Style No. 1150419, or General Electric Company's Clyptal* 1276) is used to cement the cork to the flanges. The following is recommended for sealing with the cork - - nitrile rubber combination: Use Armstrong NC~757 cork-nitrile material or equivalent. The gasket can be cut from a single sheet or by scarfing strips of the material. A convenient method for joining strips is to make a Keystone Type joint. For this purpose, Uestlnghouse, Sharon, Pennsylvania, offers their gasket cutter Style No. 328 B614 GOl, (about $15). The joints - and also the gasket - should be cemented to the flange, using one of the above cements. Excess cement should not be allowed to reach the Interior of the transformer. After installation and bolting, the outside edge of the gasket should be coated thoroughly with epoxy cement to increase weather resistance. This epoxy cement Is a paste to which a curing catalyst is added ianediately before use. Typical are: a. Epoxy Patch Kit #1-C Hysol Corporation, Olean, New York b. Scotchcast** Resin #4 Minnesota Mining & Manufacturing Company St. Paul, Minnesota c. Adhesive A-l and Activator Type B Armstrong Products Company Argonne Road, Warsaw, Indiana d. Adhesive 9860-1, Synthetics Organic Company, Cleveland, Ohio, used with activator diethylene triamine (Carbide and Carbon Chemical Company) * Trademark of General Electric Company ** Trademark of Minnesota Mining & Manufacturing Company MOMS 075226 -20- 2. Straight Nitrile Rubber: when straight nitrile rubber was originally used, invariably the gasket was recessed in a groove. This was to prevent gasket flow and to protect the material against excessive compression. Although this type seal was not cemented, the nitrile rubber gasket is not reuseabie. Since grooves or stops have already been provided for the nitrile rubber seal. Silastic 50 can be easily substituted and is recom mended. This conforms with modern practice. XVI* Periodic Fluid Inspection and What Checkpoints Mean On a regular schedule - - at six, nine, or twelve-month Intervals - - make e simple visual inspection of your sskarel insulation and run a dielectric breakdown voltage check. A. Visual Inspection; Aakarel is a clear, faint-yellow liquid. After long-term use this color may gradually intensify to light brown. The fluid should remain claar and free from turbidity or cloudiness. Any color change - - such as to a green, red or blue cast - - indicates extraction of impurities (color materials) from the solid insulation. If a distinct foreign color pick-up is noted, check the complete range of electrical characteristics and notify the transformer maker. Black ening of the askarel may indicate an arcing condition. Other coLor changes alone are not danger signals since the dielectric breakdown voltage is not likely to be impaired. B. Dielectric Breakdown Voltage If the dielectric breakdown voltage has decreased significantly from the last inspection, or if it has gradually decreased below 26 KV range (at 25C)-----RUN A CHECK FOR MOISTURE. Use ASTM D1533 (Karl Fischer Method). The dielectric breakdown voltage of askarel is the major Indicator to Che operating efficiency of your liquid Insulation. Besides the visual inspection tests, dielectric breakdown voltage is the only test necessary to run on a routine basis. Well-sealed askarel transformers have service records of 25 to 30 years on the original askarel. HONS 075227 -21- XVII, Inspection checklist fl X* If karel is clear - even Chough darkened to light brown, has no sediment or turbidity, has dielectric breakdown voltage over 26 KV - give it the inspection "OK". j X* If askarel is clear, but has foreign color of blue, green, red. . . it is "extracting color" from Internal materials. This is not, of Itself, an operating hazard when the dielectric breakdown voltage stays over 26 KV and moisture remains low. However, this rare occurrence calls for checking into the condition of the interior construction and consulting the transformer maker. However, when sampling the fluid care should be taken to avoid getting color Into the askarel from paint that may be Inside or outside of the sample valve. C If the moisture content is found to be above 70 ppm at operating tempera ture, then sampling should be done at more frequent intervals to establish a possible trend, particularly on outdoor installations. D /X, If askarel is clear, but dielectric breakdown voltage drops to 22 or lower KV* and moisture rises over 80 ppm when sonpled at operating tem perature. . .the askarel is ready for simple "refining". If the moisture ia near the saturation level (about 125 ppm at room temperature) a thorough inspection should be made for water droplets in the transformer tank, and even for "globules" of water floating on the askarel surface. If found, the transformer manufacturer should be consulted for recondi tioning both the transformer and the fluid. / askarel is dark brown to black, If black particles of carbon are seen, and dielectric strength is low. . .the askarel has been broken down by arcing. It cannot be refined and should be removed and Incinerated under proper conditions. (See ANSI Committee C 107 report on Use and Disposal of Askarel and Askarel-Soaked Materials. 155 East 44th Street, New York, New York 10017). If any of these four simple Inspection tests appear out of the ordinary or the relationship between appearance and test values is abnormal, con tact your transformer supplier for a complete analysis. Whenever a sample is to be shipped to Monsanto, please follow the direc tions shown under; "SAMPLING ASKAREL". HQhS 075228 -22- XVIII. Contamination in Transformers Moisture, particulate matter and arced decomposition products are known to be serious contaminating influences on transformer askarel. The power factor test normally used for the detection of contamination in mineral oil filled transformers is of little use for this purpose In askarel filled transformers, due to the extreme effect of extraneous soluble polar materials. This increase in power factor as illustrated in TableVI has no adverse effect on dielectric breakdown voltage. TABLE VI EFFECT OF COMMON INSULATION MATERIALS ON POWER FACTOR AND DIELECTRIC STRENGTH (HEAT AGED 96 HOURS IN ASKAREL AT 100*C.) . Material Immersed Hone (control)...................... .............. Black varnished doth........................... Copper................................................. Frcssboard........................................... Manila paper............................. ......... Phenol formaldehyde resins.................. ... Shellac.................................................. Iron...................................................... Synthetic rubber.................................. Askarel After Exposure Power Factor. Percent at 60 eye., 100*C. Dielectric 25*C. 35 KV 42 40 37 39 1.6 41 36 39 39 Similarly, trace contaminants from commonly used construction materials can lower the volume-resistivity of askarel, without affecting its di electric breakdown voltage. This is shown in Table VII. TABLE VII EFFECT OF COMMON INSULATION MATERIALS ON VOLUME . RESISTIVITY OF ASKAREL Volume Resistivity x 10' ohm-cm 1 Sample (at I00C., 500 Volts DC., 0,1* cap) 1. New askarel before heat aging................................... 2,000 2. New askarel after heat aging 96 hours at IOOaC,........ 1,900 3* After heat aging with 1 jq. inch specimens of: a. Phenolic resin tap changer material....................... 1.200 b. Paper...................................................................... 750 C Grade A press board (tan)..................................... SOO d. Grade A press board (gray)................................... 500 . c. Grade A press board, laminated strip.................... f. Cotton wrapping................................................... 400 300 g. Glyptal 1276 cement, cured 46 hrs. at 1 IO*C......... 100 HONS 025ZZS -23- While trace contamination easily lowers volume resistivity from high levels, it is important to note that heavy contamination (as when arced) does not lower the resistivity below the order of 10? ohm-cm. at 100C. The different behavior of askarel vs, mineral oil in these respects can be summarized as follows: High power factor and low volume resistivity in transformer mineral oils are commonly regarded as "danger signals" that the oil has deteriorated and broken down chemically or ex cessive moisture is present. This is NOT TRUE of askarel liquid Insulation unless the di electric breakdown voltage is low or the moisture content is high. Manufacturers of askarel type transformers point out that it is quite well known that askarel transformers with initial power factor of the askarel fluid in excess of 50X at room temperature and 60 Hz are giving satisfactory service life. However, there needs to be assurance that both dielectric breakdown voltage and moisture are at satisfactory lev els and do not show adverse trends. XIX. ASTM Method For Investigating The Compatibility of Transformer Insulation and Construction Materials in Aakarels This methodises the change of electrical and/or chemical characteristics of transformer askarel resulting from its controlled exposure to insula tion and construction materials, in order to evaluate their immediate major "contamination" effect on the askarel fluid. Delayed or long time contamination effects may not be detected. The method also utilizes various physical tests on the insulation and construction materials after controlled exposure to the askarel to de termine the compatibility of these materials with transformer askarel. Properly proportioned specimens of the insulation or structural materials are immersed in refined askarel for 168 hours at 10CHh1C in a forced draft oven. Changes in electrical and chemical properties of the trans former askarel are compared against a control sample of the askarel treated in the same manner, in absence of the test specimens. 2 In process of publication by ASTM, as of this writing. MOMS 075230 -24 Dissipation factor (ASTM D 924) change is one of the criteria used. The askarel fluid is refined by absorbtive treatment to a dissipation factor level of 0.05 max. at 100C and 60 Hz and 0.01 max. at 25C and 60 Hz. Corresponding values of the askarel fluid after heating 168 hours at 100C in absence of a test specimen are 0.075 and 0.02 respectively. The maxi mum dissipation factor levels suggested for the askarel after heating in presence of the test specimen are 0.20 at 100C and 60 Hz and 0.04 at 25C and 60 Hz, XX. Refining Askarel for Re-Use A. Filtering Through Dry Blotter Paper to Remove Moisture and Extraneous Particles; Most operators prefer portable refining apparatus, such as a plate press fitted with a dolly, available from Sparkier, Mundelein, Illinois or General Electric Company, Pittsfield, Massachusetts; or the earthen cartridge filter type available from Industrial Filter Corporation, Lebanon, Indiana. Filter paper liners for the plate press are available from Carl Schleicher and Schuell Company, Keane, New Hampshire and manufacturers of filter presses listed above. The filter paper must be dried Immediately before use. For best re sults, spread the paper for maximum surface exposure in a hot air circulating oven and heat it for 4 to 6 hours at 110C. Clrculata the eekarel hot (but not over 40C) through the filter fitted with the dry paper liners. After filtration the dielectric breakdown voltage of the askarel ahould be 35 KV minimum. 1. Precautions: Filtering should not be done when the relative tupaldity exceeds 75%. 2. Any flexible hoses and gaskets on the refining equipment should be lined with or made of materials that will not be softened by contact with askarel fluid. (Materials lined with Siiicone, Viton or Teflon*or flexible metal materials are suitable.) ^Trademark of E. I. Dupont DeNomours & Company, Inc. . TABLE VIII GUIDE TO RATE OF DISSOLVED WATER REMOVAL DY FILTERING ASKAREL THROUGH A PAPER TRESS Panes Through Paper Press 0 1 2 3 4 5 6 Water in Asharel PPM 115 35* 22 18 10 -25- B. Disposal of Solid Wastes: The ANSI Guide states that, "All solid wastes which have been saturated with askarel should be disposed of by the following procedure: 1, The saturated wastes should be placed into leak-proof containers and transported to a supervised dry landfill site meeting State requirements. Alternatively, they can be disposed of by incin eration in State-approved facilities. 2. Solid absorbents used for spills can be disposed of uncontained in the supervised dry landfill site; transport to the site should be in closed containers. Alternatively, incineration can be used in accordance with par. B (See Section 4 for facilities) C. If the solid insulation of the transformer requires drying, consult the transformer manufacturer or an apparatus service shop, as in such case oven drying is preferred. D. Earth Treatment for Maximum Improvement of power Factor and VolroeResistivity: We question whether pumping and filtering the fluid solely to achieve a change in power factor or volume resistivity alone is Justified in today's ecological climate regarding PCBs. We recommend that in these situations the original transformer manufacturer be contacted. 1. Procedure: The askarel liquid should be relatively dry prior to the follow ing earth filtration. As a coating on the filter paper surface use finely divided Attapulgus clay or Fuller's earth dried and activated by heating for 12 hours at 300-350F immediately prior to use. The amount of earth used should be 0.1 to 0.2 percent by weight on the weight of the askarel to be treated. Askarel weighs about 12.5 pounds per gallon. To deposit the earth evenly, stir one-third of the earth with a small portion of askarel in a clean container. Pump the mixture through the filter and follow with two more one-third portions. Then circu late askarel taken from near the top of the transformer, pass it hot (not over 55-60C) through the earth-coated filter and feed back through the bottom transformer outlet. Continue circulation until the fluid is clear and test shows that the electrical properties are fully restored. HONS 075232 -26- 2 Effect of Earth on Removal of Scavengers Only slight and insignificant loss by selective absorption of tin tetraphenyl and epoxides occurs when askarel is refined by treatment with 0.1 to 0,2 percent by weight of earth. To re move significant amounts of the scavengers requires repetitious treatment with much larger mounts of earth. 3. Table IX - - Approximate Relationship Showing the Insignificant Effect of Power Factor and Volume-Resistivity on Dielectric Breakdown Vo of Trans former Askarel Power Factor (60 eye.) lOCTC 25^- Volume Resistivity n 109 ohm-cm (at 100*C, 500 Volts _DC, 0.1" gap) Breakdown Voltage 25C, 0.1' 2* 55* 15* 20-25* 40-50* . *0.05* 01 . *0.7* 20 1500 500 100 60-70 25 35 KV 35 35 35 35 XXI. Cleaning Arced Transformers If a unit has arced so that the askarel is no longer fit for use, a thorough cleaning of the unit is necessary before refilling with new askarel Insulation and returning it to service*. Follow this procedure: A. Drain out all dark, carbon-contaminated askarel. Arrange to have the serap fluid incinerated under proper conditions. (See ANSI Connlttee C107 report.) B. Carefully Jbrush carbon deposits from internal parts and insulation, using e soft bristle brush making sure that insulation is not damaged. C. Flush thoroughly using new askarel - not an oil, not a cleaning sol vent . D. Flush a second time with fresh askaxel; drain; then fill to the proper level with new askarel. E. Energize transformer to warm the fluid for 2H to 46 hours; then circulate the askarel through a , filter, returning It to the unit filtered and ready for use. *Thls assumes that the cause of aTclng has been established and corrections made. When severe arcing occurs, major repairs are usually necessary and the unit rebuilt. This procedure can be applied for flushing out the re paired units. HONS 075233 27 XXII, Sampling Askarel Take a sample as close to the top of the liquid surface as possible. Many large askarel transformers have a built-in sampling tube near the surface for convenient sampling. Then, to make sure that your sample truly represents your askarel insulation, take another sample from the bottom. If additional sampling tube connections are contrived on the valves for easier sampling, make the tubes of clean glass, stainless steel, aluminum or tin for rigid types; and silicone, or Viton or Teflon tubing for flexible types. Use NEW containers for the askarel sample. A new and thoroughly pre dried small-mouth quart glass bottle fitted with a Bakelite*screw cap with aluminum or tin cap liner is recomnended for quick, on-site testing. (If complete analysis is to be made, a 5-pint si2e sample is required.) Be sure that the new bottle does not stand open to collect dust or mois ture, Rinse the sample bottle and cap lining two or three times with askarel from the transformer, then fill it. If the sample will be tested promptly, a clear glass bottle can be used. If sample is to be stored indefinitely, use an amber glass bottle or wrap clear glass with aluminum foil. A. Select a dry day. Do not sample insulation on a warm, moist day when humidity exceeds 75%, and . . . B. Make sure that the askarel is at least as warm as the surrounding air. (Cold liquids can condense moisture from humid air.) C. When sampling askarel from transformers, it is best to take the sam ple when the unit la warm and operating at average or maximum load, especially for a check on moisture as reflected by a dielectric breakdown voltage test. Sampling the warm askarel more truly rep resents its condition during operation. Experience shows that water will migrate from a transformer's solid insulation to the askarel liquid and vice versa, depending on tem perature. Therefore, when the transformer is hot, the moisture is most likely to be found in the liquid. This accounts largely for periodic variations in dielectric breakdown voltage. For example. ^Trademark of Union Carbide Corporation HONS 075234 -28a relatively high dielectric breakdown voltage may be found during winter months and a relatively low dielectric breakdown voltage dur ing the simmer months on samples taken from Che same unit. When testing has been completed, the remainder of the fluid sample should be destroyed by high temperature incinceratlon described in Section VIII. MGNS 075235 -29Section B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS X. INTRODUCTION High voltage leads are usually connected to askarel or mineral oil-filled network transformers and power centers through terminal chambers and witches. In some cases terminal chambers are not used, and the high voltage leads are connected directly to the switch terminals. They may be filled with either askarel or mineral oil. Switches are usually ro tary or drum type fitted with a revolving block and porcelain unit as the principal element arranged for three-phase service. Askarel transformers with attached switches have been in use for about 30 years. When they were first introduced, the availability of insulat ing and gasketing materials was rather limited and even the best materials at the time had no service history. As a result, inadequate gasketing materials such as cork, nitrile rubber, and nitrile rubber-and-cork particles were used. While satisfactory for a limited period of time, these materials cannot be depended upon for the expected long life of the equipment. HQNS 075236 -30 The terminal chamber Is usually above or below the switch - compartment and separated by a steel wall through which the bushings are Inserted. When bushings are properly selected . and correctly Installed, there Is no leakage from one com - partment to the other. With poor bushing seals, and the . ' terminal chamber above the switch, potting compounds or cable ' ' oil can seep Into the askarel. When the terminal chamber - ' la below the switch, askarel can drain Into the terminal *` i. " ' . chamber. '. . II. SOURCES OP CONTAMINATION \ ' There are three possible sources of contamination for askarel ` In switches and terminal chambers; they rank In this order ' of frequency: (l) water entering through poor gaskets; (2) decomposition products from arcing when switch Is used . . to break magnetizing current; (3) entrance of pothead or cable compounds through leaky bushing seals. ! ' Unlike an askarel transformer where the amount of contami. nant is likely to be very small (probably only trace amounts) in relation to the volume of askarel fluid -- in switches or terminal chambers with faulty seals, the amount of contamlnation can be relatively large. HONS 075237 -31- . Experience has shown that, based on the number of Installed askarel-swltch units, the percentage of failures Is extre mely small. When Investigated, It has been found that most failures originate In the switch chamber. Water Is the Chief source of contamination. However, heavy contamination of askarel with petrolatum and asphalt material, due to leakage, have caused a few failures. Petrolatum Is used frequently for filling terminal chambers. When either cable oil or petrolatum seeps Into askarel, no great harm results. The fire resistance will be somewhat decreased and power factor of the askarel will Increase with an accompanying drop in resistivity. While highly undesir able, it Is doubtful that failure of the unit results. Where asphaltic compounds are used In place of petrolatum, the danger is Increased somewhat because asphaltic contamination may cause excessively high dielectric losses in the askarel. When the terminal chamber Is below the switch chamber, the potting compound can be contaminated by askarel If the bush ing seals are leaky. This is undesirable because the askarel Will Increase the power factor and conductivity of the potting compound or cable oil and develop heat from dielectric loss. If this mixture is drawn Into the cable insulation, a cable failure Is likely. This again emphasizes the importance of tight bushing assemblies. HONS 075238 -32- III. SEAUNO SWITCHES AND TERMINAL CHAMBERS Proper bushing construction, use of Silastic seals and . welding wherever possible is highly desirable (as covered In Section A). Where an elastomeric seal is to be used In contact with both askarel and petroleum oil, DuPont's . Vlton is suggested. Por new equipment the user should specify these modern . sealing arrangements to keep out contaminants and minimize . Maintenance. - IP. ASKAREL USED UNDER MILD ARCING CONDITIONS , The IEEE Guide for Transformer Askarel calls attention to . the following: _ ' ! ' "Askarel is used, to some extent, in apparatus where it is subjected to light Intermittent arcing, such as in self-contained induction regulators, where operating switches are con- tlnually producing slight arcs, in transformer deenergizing switches, etc. Under normal eonditlons, deterioration of the askarel is very Slight. However, improperly adjusted or defec tive switches in this type of apparatus can produce excessive and prolonged arcing and ac cellerated deterioration of the askarel. It is recommended that when askarel is used under these conditions, checks of the liquid, espec ially for moisture and dielectric breakdown voltage Bade more frequently than when it is used only as a cooling and Insulating fluid. Deteriora tion of this type is indicated by a blackening of the liquid. It can usually be reconditioned as previously described. Special attention should be given to maintaining the scavenger at the appropriate concentration." HONS 075239 -33' MAINTENANCE FOR ASKAREL FILLED SWITCHES A. Switches used for grounding after power source has been de-energized will not undergo arcing. B. Switches Interrupting magnetizing current will be sub Ject to arcing; the amount of decomposition will depend on power interrupted, time and frequency of operation. As a general rule, the liquid should be checked after ' 5 to 10 operations. . 1. On newly Installed switches, cheek the askarel at 3, 6 and 12 month intervals; if found satisfactory, check once annually thereafter. With proper atten- . tlon to the gasketing of covers and bushings, exper- lence will probably indicate that less frequent in . apeotlon is warranted. '; . . . 2. Check askarel for: . a. Dielectric breakdown voltage (ASTM D877) :_Tt should ' . voltage ' ; be 26 KV minimum. If dielectric breakdown/is low, confirm presence of water by Karl Fischer method . ASTM D-1533. Filter to remove moisture. Me- lectrlc strength should then be 30 KV minimum. b. Presence of carbon from arcing: Fluid should be .. relatively free of carbon. If badly arced and very black, replace fluid. If only minute amounts of carbon are present, filtration is recommended. Check power factor of liquid (should not be over 5jt at 25C. and 60 cycles). Flush out switch chamber with several gallons of fresh askarel before refilling. HONS 075240 34- ; . 3. If there is discoloration, high power factor, detectable change in specific gravity or refrac tive index, or if fluid flashes below 250*F, there is a possibility of seepage of potting com pound into the switch compartment. In this case, oorrect any leaky bushing seals with proper re placements and fill with new askarel. ... Jl. If terminal chamber is below switch, check potting compound for presence of askarel (can usually be detected by odor or by an increase in specific gravity). If askarel is present, correct any leaky bushing seals with proper replacements, and renew compounds. .' 5, Examine cover gaskets visually. Deterioration can be detected by swelling and cracking of the exposed edge. In cases of severe deterioration, liquid seepage is usually present. 6. Check for leakage at packing gland of switching shaft. If leaking, repack with a Silastic ring type gasket. . VI. ASKAREL UNDER EXCESSIVE TEMPERATURE OR FAULT CONDITIONS I The IEEE Guide also points out that, "Chlorobenzenes used in transformer askarels begin to boil *GNS 0 75241 -35et temperatures of about 205C, under atmospheric con ditions. If the material is heated to such high tem perature In a sealed system, pressure develops. Pres sure will also develop In the system If the askarel is arced sufficiently to generate copious hydrogen chloride gas.*~-' "Therefore, It is recommended that wherever possible, sealed askarel filled equipment be provided with pressure relief devices. These devices must be large enough to provide immediate relief at a definite pressure, and to prevent further build up of pressure if decomposition continues. It must be remembered that the presence of devices of this sort does not necessarily preclude the rupturing of containing vessels, since pressure build up can be extremely rapid under violent arcing conditions." HONS 075242 -36- SECTION C ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO Transformer users not wishing to make their own fluid analyses can obtain the service from Monsanto. Simply contact Monsanto and specify what analyses are wanted. You wilt be sent the proper-sized'sample container fitted with a proper label. When you re ndve this, carefully ' take your sample (following the procedure for sampling in this guide). Send the container to Monsanto's laboratory. Charges listed include sample container, shipping, handling and laboratory costs. Types of Analyses Available Analysis I) . .' ROUTINE MAINTENANCE CHECK . Total Charge: $25,00 " To determine the general condition of the fluid and find whether further analysis is neces sary. (one-quart sample required) Properties Tested Color and Condition Dielectric Breakdown Voltage Moisture . *; ' . ; -' . You will be notified of the results of this tesL If further testing is indicated, and you want a complete analysis, you will be sent a five-pint sample container. This sample will be used for the following series of tests: Analysis 2) - COMPLETE ANALYSIS Total Charge: $55.00~ ' (a) To determine the extent of fluid contamination, (b) earth refinement to determine what degree of restoration of electrical and insulating properties is possible, (c) check test to lee how the fluid responded to earth treatment. a) Complete Analysis: to determine the extent of contamination Properties Tested Color and Condition Specific Gravity Refractive Index Water Free Chlorides .. . Acidity Dielectric Breakdown Voltage Power Factor, Dielectric Constant, and Resistivity MENS 075263 -37- 6) Earth Refinement Response: Consists of treatment for 2.3 hour's at 50-60*C. with 0.1 to 0.2 percent by weight of properly conditioned Attapulgus clay and then filtration through dry filter paper. Analysis After Laboratory Earth Refinement: properties Tested . ' Refractive Index Water .. Free Chlorides Acidity : Dielectric Breakdown Voltage . Rower Factor, Dielectric Constant, and Resistivity . . . You will be notified of the results of this test series on your sample. Then aftei refining j/our entire transformer fluid fill you can check on the results by requesting the following analysis: ' Analysis 3) . Analysis after earth refinement \ . Total Charge:$35. ooO"h*s charge will not apply when analyses 1 and 2 have already * been made.) To determine whether the entire lot of the askarel fill responded to the same extent as the Utbbratory sample, (five-pint sample required) Properties Tested Color and Condition Refractive Index .. Water. Free Chlorides Acidity .......... .... Dielectric Breakdown Voltage Rovirer Factor, Dielectric Constant, and Resistivity . . , ' "ft> arrange for'die tests described above Write to the following address: RaulG. Benignus Monsanto Company fOO North Lindbergh Blvd. ' St. Louis j Missouri 63166 ' Sample's to bef tested should be dearly marked for identification and sent directly to: htonsanlo Chemical Company ,W. G. Krummrich Laboratory . Sauget, Illinois 62201 ' Attention: R. Kuster . ' MOhS 075244 & -38T. APPENDICES APPENDIX A -- Askarel Stability and Composition of Arc Formed Gas Askarel Insulation Is one of the most Inert, chemlcally-stable heat resistant, non-corrosive liquids known. It will not break down, oxidize or sludge when exposed to air and high tempera tures, 150*C. or even somewhat higher. Arcing, however, will break down the compound to liberate some hydrogen chloride and small amounts of carbon. ' APPROXIMATE COMPOSITION ABC FORMED GAS FROM TRANSFORMER ASKAREL BLENDS ASTM TYPES D AND F (INERTEEN 54201KA AND PYRANOL A13B3B-2, RESPECTIVELY) Oaa Amount oarbon monoxide................................................................. 0.3 percent carbon dioxide........................................................ 0.3 oxygen............................... 0.6 Inert gases............................................................... 1.5 hydrogen chloride..................................................97.3 (note the absence of phosgene) This arc-formed gas from ASTM Type D and Type F transformer askarels is non-flammable and non-combustible. For all practical purposes, the amount of gas liberated from askarel under a given set of arcing conditions is about 100 cubic centimeters per kilowatt-second. MONS 075245 -39- APPENDIX B___________________________________________________________ _ SOLUBILITY OP GAS IN TRANSFORMER ASKARELS . .ASTM TYPES D AND F Percent of Gas By Volume ' Corrected to: `' Carbon dioxide Air Nitrogen Hydrogen chloride1 2'jcC 760 mm 25*C lOtTC 'Jlfy 5-7 6.0 57? 5.9 5.8 37.8 50.9 0*C. 760 mm 25*5 lQ0oC - 5.8 5.0 5-5 5.4 "" 1) in absence of scavenger ' .' APPENDIX C . EFFECT OP TEMPERATURE ON DIELECTRIC BREAKDOWN VOLTAGE OF ASKAREL Temperature C -60 -4o -20 0 20 4o 60 80 Dielectric Breakdovm Voltage ASTM D877 67 KV ........... . 63 57 55 50 . 5 48 55 HONS 0752A6 -40- APfENDIX I) oQoOo O^ rOv oOi O O cu Temp.'C COMPARISON OP THE APPROXIMATE'VISCOSITY IN SAYBOLT UNIVERSAL SECONDS OP TRANSFORMER . ASKARELS AND MINERAL OIL . Pyranol A13B3B-2 IJOOC? 100 70 45 3? 34 30 10-C Mineral Oil 1,000 150 fe 49 40 34 30 Inerteen 54201 KA 578o0" % IS 36 33 APPENDIX E THE DENSITY OP INERTEEN 54201 KA 7336-9 AND TRANSFORMER PYRANOL A13B3B-2 Approx. Density gm/cc. . Temp. 0 20 AO 60 80 *C ' Inerteen 54201 KA 1.574 . 1.552 1.529 - . 1.507 1.485 Pyranol A1333B-2 . T7577 1.555 1.532 1.510 1.488 APPENDIX p . The thermal conductivity values of transformer Pyranol A13B3B-2 at 27C and 58C are 26.2 and 25.8 x 10-5 calories centimeters-1, degrees centigrade-1, second-1, respectively. Or, approximately 0.06 BTU per (hr.;(sq.ft.)(F.) per foot. This same approxima tion appliesto Inerteen PPO (7336-9). . APPENDIX 0 ". Heat Capacity . Over the temperature range of 25* to 125*C the specific heat of transformer askarel is close to 0.30 calories per gram per degree. . APPENDIX-H ' - ; \` Coefficient of Expansion The average coefficient of expansion of transformer askarel over the temperature range 20 to 100*C is 0.0007 cc/cc/*C. One gal lon would increase to 1;056 gallons on heating from 20 to 100C. MGNS 073241 -41- APPENDIX i;I .- Fire Resistance Aakarels of various compositional types are used. Under arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride can yield varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askarels and celluloslc or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitro gen through the askarel and flushing the gas space with dry nitrogen before any work Is performed on the apparatus. APPENDIX J - Seals, Properties and Procurement Dow Coming Corporation, Midland, Michigan with Districts at Atlanta, Boston, Chicago, Cleveland, Dallas, Los Angeles, New York City, Washington, D.C. and Toronto has available Bulletin 09-019, August 1962 entitled "Siiastlc Design Data". This lists the gasket fabricators throughout the country from whom the ' "Silastic 50" gasketing can be purchased in sheet, extrusions or molded shapes. Generally Silastic 50 sheet goods are stocked by local die cutters, hence, c.ould be generally purchased locally. Usually small quantities of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other elastomers. SONS 075248 -42- Hhere the gasket Is extruded for fitting into a machined groove or between gasket stops, Dow-Cornlng advises use of scarved Joint. This joint Is then cemented using Dow Coming's Silastic 140 (clear) or their RTV 731 (white) mate rials, which air cure. . Bow Corning points out that the local "rubber" fabricators purchase the Silastic 50 In billet form. This Is worked on a roll mill In preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure the Silastic 50 for 24 hours at 480*F. : SPECIFICATIONS* ' ASTM D676-. ASTM D4l2 ASTM D412 ASTM D395 Color........................................................White Specific Gravity at 77F..............1.20 0.02 Hardness, Shore A. Scale..............45 to 60 Tensile Strength, psi, min.......... 800 Elongation, percent, min...............250 Compression Set after 22 hrs... . at 300*F, percent, max.................. 30 All physical properties measured on 0.075 inch thick samples Bolded 5 minutes at 240*F, and oven cured 24 hours at 480F. HONS 075249 43- APPENDIX K Caution Label The following or equivalent caution statements should be fixed on all containers of transformer askarels and the transformers themselves; This product contains Polychlorinated Biphenyls (PCBs). Care Should be taken to prevent entry into the environment through spills, leakage, use, vaporization, or disposal of liquid or oontalners. Avoid prolonged breathing of vapors or mists. Avoid oontact with eyes or prolonged contact with skin. If skin contaot occurs, remove by washing.with soap and water. Following eye contact, flush with water. In case of spillage onto cloth ing* the clothing should be removed as soon as practical, skin washed, and clothing laundered. HONS 075250 1 jwn from the experience of maker* and users of askaicJ transformers and it la believed witt be helpful. HoUitnn herein shall be construed as applying to other than askarel Insulation. Data and maintenance suf.gcstions herein do not apply to the other components f the transformer. All operating and maintenance suggestions recommended by the manufacturer of the transformer should also be carefully followed. Because these maintenance directions apply only to the askarel insulation, Monsanto disclaims any liability for damage to property or injury to persons rising from transformer operation, I *1# uii ,, MGNS 075251