Document NEoq80vyroZy4aQDV55Mzk53D
Tenneco Chemicals
A Tenneco Company
Turner Place, P.O. Box 365 Pitcataway, New Jersey 08854 (201) 981-5000
Organics & Polymers Division
January 11, 1977
.TENNECO,
Mr. Herbert A. Howlett, Chief Engineer Delaware River Basin Commission P.O. Box 7360 West Trenton, New Jersey 08628
Dear Mr. Howlett:
Under provisions of the Emission Standard for Vinyl Chloride, National Emission Standards for Hazardous Air Pollutants 40 CFR 61 - Part F, Tenneco Chemicals must install air pollution control devices and make significant mechan ical/procedural changes to reduce the amount of vinyl chloride (VCM) emitted to the atmosphere at its Burlington, New Jersey site. Hie major control devices include an "in-process-wastewater" stripper and a carbon adsorption system...
These units are of sufficient size and operating character that revision of the existing cooling water system is necessary, which will increase the temperature of the water wasted from the system.
As you know Tenneco operates a waste treatment facility at Burlington, Treated effluent from this facility is mixed with the cooling tower blowdown prior to discharge into the Delaware River. The treatment plant is operated under NPDES permit NJ 0004391.
An average volume of 2050 gallons per minute (gpm), or 4.6 cubic feet per second are discharged, with temperature regulated as follows:
Season
Temperature C (F)
Average
Maximum
Winter (Nov. - Apr.)
18 (65)
26 (79)
Summer (May - Oct.)
26 (78)
31 (88)
This limitation compares with, for example, that of Public Service Electric and Gas Company's Burlington generating station which discharges at temperatures of up to 116 F (their regulated maximum).
COLORITE 018072
Mr. Herbert A. Howlett
-2- January 11, 1977
It is estimated that the changes required will cause a 2.8 C (5 F) increase in the maximum discharge temperature of the effluent. We believe that such an increase Bhould have no significant effect on the temperature character of the River, based on temperatures and flows reported in the most recent U.S. Geological Survey "Water Resource Data for New Jersey - Water Year 1975." These data are sunsnarized in Exhibit I.
We will seek from EPA a modification of the temperature limits in our NPDES permit to the following
Season
Temperature C (F)
Average
Maximum
Winter
25 (77)
31 (88)
Summer
28 (83)
34 (93)
Ihis modification is required to allow the Burlington plant to be brought into compliance with the EPA Standard on Vinyl Chloride.
We request your approval of this proposal so that prompt action may be-- taken by EPA, permitting Tenneco to fulfill its obligations under the Clean Air Act. Should you have any questions concerning this request, please contact me.
Very truly yours,
TENNECO CHEMICALS
'.^C"J&uufa i/trtV
sj. P. Sandstedt
- Manager of Environmental Engineering
JPS:db
cc: Mr. Robert Reed New Jersey Department of Environmental Protection Bureau of Water Resources
bcc:
W. P. Anderson D. C. Coldiron N. J. Quist
P. R. Scarito T. T. Zuhl
COLORITE 018073
EXHIBIT I SELECTED DATA FROM USGS WATER RESOURCE DATA FOR NEW JERSEY
WATER YEAR 1975
Month/Year
10/74 11/74 12/74
1/75 2/75 3/75 4/75 5/75 6/75 7/75 8/75 9/75
Temperature C
Discharge ft . /sec
(At Burlingt on-Bristol Bridge) (at 1Trenton, N.J.)
Max. Min. Mean
Max. Min. Mean
18.5
8.5 13.0
19,900 5860 8570
15.0
4.0 10.0
18,000 5160 9254
6.5 3.0 4.0
69,000 8160 19700
5.5 0.5 3.0
36,200 8200 18640
8.0 1.0 4.0
88,000 9780 21510
10.0 2.0 6.0
52,600 11700 23460
15.0
4.0 10.5
44,800 10800 18120
24.0 14.0 18.5
26,800 8720 16840
HA NA NA
28,500 6630 14760
NA NA NA
30,100 5540 13750
NA NA NA
9,610 4770 6694
NA NA NA
46,600 3980 12170
COLORXTE 018074