Document NEnpZvmRyLpKNJ2bQEE2joKr8
788
CHAPTER 30
1958 Guide
ASHVE Research Report No. 1204--Entrainment and Jet-Pump Action of Air Streams, by G. L. Tuve, G. B. Priester, and D. K. Wright, Jr. (ASHVE Transactions, VoL 48, 1942, p. 241). -
ASHVE Research Report No. 1248-control of Air Streams in Large Spaces; by G. L. Tuve and G. B. Priester (ASHVE Transactions, Vol. 50, 1944, p. 153).
' ASHVE Research Report No. 1328--The Discharge of Air from a Long Slot, by Alfred Koestel and G. L. Tuve (ASHVE Transactions, Vol. 54, 1948, p. 87).
ASHVE Research Report No. 1366--Air Streams from Perforated Panels, by Alfred Koestel, Philip Hermann and G. L. Tuve (ASHVE Transactions, Vol; 55, 1949, p. 283). : ' .
A8HVE Research Report No. 1404--Comparative Study of Ventilating Jets from Various Types of Outlets, by Alfred Koestel, Philip Hermann, and G. L. Tuve (ASHVE Transactions, Vol. 56, 1950, p.
459).
- -- - `
ASHVE Research Report No. 1429--The Control of Air Streams from a Long Slot, by Alfred Koestel and C. Y., Young (ASHVE Transactions, Vol. 57, 1951, p. 407).
ASHVE Research Report No. 1476--Air Velocities in Ventilating Jete, by G. L. Tuve (ASHVE Transactions, Vol. 59, 1953, p. 261).
ASHAE Cooperative Research at Kansas State College
ASHVE Research Report No. 1327--Downward Projection of Heated Air, by Linn Helander and C. V. Jakowats (ASHVE Transactions, Vol. 54,1948, p. 71).
ASHVE Research Report No. 1475 (In Cooperation with the Industrial Unit Heater Association)-- Maximum Downward Travel of Heated Jets from Standard Long Radius ASME Nozzles, by Linn Helander, S. M. Yen, and R. E. Crank (ASHVE Transactions, Vol. 59, 1953, p. 241).
ASHAE Cooperative Research--General
. ASHVE Research Reports No. 857,911 and 966--Measurement-of the Flow- of Air Through Registers and Grilles, by E. L. Davies (ASHVE Transactions, VoL 36, 1930, p. 201; Vol. 37, 1931, p. 619 and VoL 39, 1933, p. 373).
ASHVE Research Report No. 1076--Air Distribution from Side Wall Outlets, by D. W. Nelson and D.J. Stewart (ASHVE Transactions, Vol.-44,1938, p; 77).
ASHVE Research Report No. 1092-r-The Flow of Air Through Exhaust Grilles, by A. M. Greene, Jr.
and M. H. Dean (ASHVE Transactions, Vol. 44, 1938, p. 387).
-
ASHVE Research Report No. 1155--The Performance of Stack Heads, by D. W. Nelson, D. H. Krans. and A. F. Tuthill (ASHVE Transactions, Vol. 46,1940, pi 205).
ASHVE Research Report No. 1165--Development of Instruments for the Study of Air Distribution in Rooms, by A. P- Kratz, A. E. Herehey, and R. B. Engdahl (ASHVE Transactions, Vol. 46, 1940, p. 351).
ASHVE Research Report No. 1206--Performance of Stack Heads Equipped with Grilles, by D. W. Nelson, D. H. Lamb and G. E. Smedberg (ASHVE Transactions, Vol. 48, 1942, p. 279).
ASHVE Research Report No. 1226--Performance of Side Outlets on Horizontal Ducts, by D. W. Nelson and G. E. Smedberg (ASHVE Transactions, Vol. 49, 1943, p. 58).
Other Papers Presented at ASHAE Meetings
ASHVE Research Report No. 1051--The Noise Characteristics of Air Supply Outlets, by D. J. Stewart and G. F. Drake (ASHVE Transactions, Vol. 43,1937, p. 81).
ASHVE Research-Report No. 1158--Dirt Patterns on Walls, by R: A. Nielsen (ASHVE Transac tions, Vol. 46, 1940, p. 247).
ASHVE Research Report No. 1361--Balancing Air Delivery of a System of Manifold Air Diffusers, by G. S. Dauphinee and Peter Argentieri (ASHVE Transactions, Vol. 55, 1949, p. 213).
ASHVE Research Report No. 1362--Air Distribution and Draft, by John Rydberg and Per Norbfiek
(ASHVE Transactions, Vol. 55,1949, p. 225).
>
ASHVE Research Report No. 1471--Room Air Distribution Research for Year 'Round Air Condition ing, Part I--Supply Outlets at One High Sidewall Location, by S. F. Gilman, H. E. Straub, A. E: Herehey. and R. B. Engdahl (ASHVE Transactions, Vol. 59, 1953; p. 151).
- ASHVE Research Report--Room Air Distribution Research-for Year 'Round Air Conditioning, Part II--Supply Outlets at Three Floor Locations, by H. E. Straub and S. F; Gilman (ASHVE Trans* actions, Vol. 60, 1954, p. 249).
Miscellaneous Articles
Measuring Air Distribution and Grille Performance in Air Conditioning, by G. L. Tuve (ASHVE
Journal Section, Heating, Piping <fc Air Coriditioning, November 1937, p. 700).
Air Discharge from Narrow Slots, by F. F. Stevenson (Heating, Piping & Air Conditioning, May 194L P308, and June 1941, p. 368. Discussed by J. R. Fellows and D. W. Nelson, loc. cit., September 1941, p. and 559).
Vertical Air Distribution in Tall Buildings, by Sturm (Heating, Piping <fc Air Conditioning, June 1947, P; 69 and September 1947, p. 93).
Efficient Air Distribution in Theatre. (Heating, Piping and Air Conditioning, Question of the Month-
August 1947, p. 107; September 1947, p. 113; November 1947, p. 103).
-
Test Every Air Conditioning System, by L. T. Avery and J. Black. (Heating and Ventilating, Jub
p- 96).
Balancing an Air Conditioning System, by L. R. Phillips. (Refrigerating Engineering; July 1950, p. it
What is a Draft? (Heating, Piping <fc Air Conditioning, Open for Discussion. May 1951, p. 67, July 1951, J>-
71, Sept. 1951, p. 69, January 1952, p; 113, March 1952, p. 73).
*n
Seven Questions on Ducts and Grilles. (Heating, Piping & Air Conditioning, Question of the Month. May
1952, p. 106 and July 1952. p, 111).
.
Air Distribution Studies, by R. V. Maxtelli and H. O. Scarlett (Heating, Piping <fe Air ConditioningQ ?' ` vember 1952, p. 77. Discussed by W. O. Huebner, loc. cit. Jan. 1953, p. 119 and by the Authors, MarcRL.,,,'
p. 85).
. . CHAPTER 31
AIR DUCT DESIGN
Pressure Changes, Friction Losses, Circular Equivalents .of Rectangular Ducts, Dynamic Losses, Pressure Losses in Elbows, Pressure Losses in Divided-Flow Fittings, Losses Due to Area Changes, Duct Design Methods and Ex amples, High-Velocity Duct Design, Duct Construction Details, Heat Losses from Ducts ...
IN THE design of air duct systems, the objective is to provide a system that, within prescribed limits of noise and space available for ducts, efficiently transmits the required flow rate of air (cfm) to each space while maintaining a proper balance between investment and operating cost. When the heating, cooling or ventilation load is established, the total flow
rate of air required can be determined by methods shown in Chapters 12 and 13. The problem is then to distribute the supply air properly among the spaces.
PRESSURE CHANGES
Ductwork imposes resistance to air flow which must be overcome by the
expenditure of mechanical energy; this energy is ordinarily supplied by a fan. The portion of the air flow rate from the fan that is transmitted to a particular space is governed by the law that the loss in total pressure from the fan outlet must be the same along each air path. This also holds for
the return-air system except that the loss in total pressure refers to the fan
inlet. In air conditioning and ventilating work the pressure differences are ordinarily so small that the equations for incompressible flow can be applied. Additional simplicity is obtained by considering ,the air to be at
the standard density of 0.075 lb per cu ft.
At any cross section in a duct the total pressure H is the sum of the
static pressure P and the velocity pressure Hv . Thus, '
H = P + H, `
Pressures are considered in units of inches of water.
sure is then given by
.. . !
(1 y
\4005/
where V is defined by the equation
(l) The velocity pres-:
(2)
where
VQ A
(3)
T -- mean velocity of flow, feet per minute. Q -- air flow rate, cubic feet per minute.
-- cross-sectional area of duct, square feet.
crews sp^f^ Pressure H is a measure of the total mechanical energy at a ction. In any duct system, the total pressure,always decreases in
789 :