Document NEkyqVRD77pzXgk4Xp0oVxvng
a)
UNION CARBIDE CORPORATION MAINTENANCE PROCEDURE
SEADRIPT PLANT - 510
PLAINTIFF'S EXHIBITS >
I
UC-P-134
MAINTENANCE DEPARTMENT
NO:_____________MP-I-6 PAGE:_________01 of 05 EPPECTIVE: 06-22-78 REVISION: 03-19-86
ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL, HANDLING & DISPOSAL
GENERAL
This is the plant procedure for the safe removal of asbestos-containing insulation material and compliance with OSHA 29 CPR 1910.1001. The purpose of this procedure is to ensure the safety and health of employees directly involved with performing the work and others, either in the immediate area or downwind, who may be exposed to residual dust/fibers. Insulation containing asbestos is no longer installed; the concern of this practice is the identification and control of old insulation containing asbestos.
STANDARDS
/
Permissible Exposure Limits:
... _ Asbestos dust concentrations must not exceed an 8-hour time weighted average (TWA) ef 2 fibers (longer than 5 micrometers) _per cubic centimeter of air. At no time may the "ceiling" concentra tion exceed 10 fibers Monger than 5 micrometers) per cubic
.`^centimeter of air.
WORKPRACTICES
A. Only specially trained and qualified persons meeting medical requirements of OSEA 1910.1001, J, medical examinations, shall be employed in removal or demolition of asbestos where the possible exposure could exceed permissible exposure limits, ref. "Standards. A", above and Medical Examinations on page 4.
B. When asbestos insulation is suspected, a qualified insulator will make a positive identification that an item is asbestos insulation covered and will mark it using the yellow and black stick on labels. The labels are Stores Items (63-486-160).
C. Demolition, removal or handling of asbestos-containing insulation shall be performed while the material is in a sufficiently wet state to prevent emission of airborne fibers exceeding exposure limits.
L-
030757
UNION CARBIDE CORPORATION MAINTENANCE PROCEDURE
SEADRIPT PLANT - 510 MAINTENANCE DEPARTMENT
NO:__ PAGE: EFPECTIVE: REVISION:
MP-I-6
02 Of 05 06-22-78 03-19-86
ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL. HANDLING t DISPOSAL
D. Caution signs and barricades shall be posted at all approaches to areas which may contain excessive concentrations of airborne asbestos fibers so that an employee may read the signs and take necessary protective steps before entering the area. The signs shall conform to 20* x 14" vertical format and state:
ASBESTOS/DUST HAZARD BREATHING ASBESTOS DUST MAY BE HAZARDOUS TO YOUR HEALTH
AVOID BREATHING DUST WEAR ASSIGNED PROTECTIVE EQUIPMENT DO NOT REMAIN IN AREA UNLESS YOUR WORK REQUIRES IT
(These signs are available in Stores, 463486-120)
E. An appropriate barricade, using yellow 6 black colored tape shall
be erected around the perimeter of outdoor areas as a supplementary, protective measure to discourage unauthorized entry.
F. In case of repair or transportation of an'object that is asbestos insulated, an adequate amount of insulation will be removed to allow safe repair Or transport. The exposed ends of asbestos insulation left will be coated before transporting or repair. The object will be prominently identified using labels as described in *B? (Stores item *63-486rl60)..
G. Transportation will be alerted when asbestos insulated"items are -to be transported, so that special precautions can be taken. Truck Drivers so *alerted* will carry special water spray cans to wet down spots or breaks that might occur in handling or transporting. The person requesting the truck will be responsible for "special" notification and will make sure the object is prepared as in (F) above.
H. Salvaged equipment with asbestos insulation will be taken to the asbestos removal site with insulation ON and be placed in the specially marked area. The equipment remover is responsible for providing a Work Request to remove and dispose of the asbestos insulation.
Major demolition removal will be done on site under controlled conditions.
L 030758
ONION CARBIDE CORPORATION MAINTENANCE PROCEDURE
SEADRIPT PLANT - 510 MAINTENANCE DEPARTMENT
NOs_____________MP-I-6
PAGE:
oT of' 05
EFFECTIVE: 06-22-78
REVISION: ~03-19-86
ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL, HANDLING t DISPOSAL
I. Bags & Labels: Special reinforced plastic bags are used by plant personnel for bagging and disposing of asbestos insulation. Stores item #14-103-602. Special labels for the bags are in Stores, item #64-486-160. The label states:
CAUTION CONTAINS ASBESTOS FIBERS
AVOID CREATING DUST BREATHING ASBESTOS DUST MAY CAUSE SERIOUS BODILY HARM
J. Removal - Insulation to be removed shall be wetted and placed directly into special plastic bags (Stores #14-103-602). A good practice is to place plastic sheeting below the job site, mist spray the insulation as required while removing and then dispose of the plastic sheeting along with the insulation. Stripped insulation must not be dropped or thrown to the ground. Dust tight containers, chutes, or special metal load luggers, must be used for lowering insulation.
When removing large amounts of insulation, thoroughly wetted insulation maybe placed in special open'topped metal containers (large load luggers).. This insulation must be kept wetted down and covered until disposed of. The container must.be made free of asbestos residue before reusing in the plant. A good practice is to line the container with plastic sheeting prior to loading and then dispose of the sheeting with the insulation.
K. Waste Disposal - Asbestos waste, scrap, debris, bags, containers, equipment, and asbestos-contaminated disposable clothing, consigned for disposal, which may produce airborne concentrations of asbestos fibers in excess of prescribed exposure limits shall be collected and disposed of in sealed impermeable bags, or other closed impermeable containers to an approved landfill. An order for waste removal must be obtained from the E.P. Department.
HOUSEKEEPING
All external surfaces shall be maintained free of accumulations of asbestos fibers, if, with their dispersion, there would be an excessive concentration. Special attention should be given to cleaning scaffolds used in demolition work.
030759
ONION CARBIDE CORPORATION MAINTENANCE PROCEDURE
SEADRIFT PLANT - 510 MAINTENANCE DEPARTMENT
NO i__
PAGE: EFFECTIVE: REVISION:
MP-I-6
04 of 05 06-22-?? 6S-19-86
ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL, HANDLING & DISPOSAL"
PERSONNEL PROTECTIVE EQUIPMENT
All personnel engaged in the removal of asbestos insulation are required to wear an approved respirator and approved protective clothing. In severe conditions it may be necessary to tape the wrists, ankles and neck of the protective clothing.
A. The approved respirators at the Seadrift Plant are: The 3M 8710, The North Half with 7500 B cartridge (purple color), the D.S. Safety Half Mask with 158-T-12 cartridges (purple color); the Nilson Full Face Mask Respirator equipped with R-ll cartridges; the Full Face Mask Supplied Air Respirator; and the Self Contained
- Breathing Unit (Scott-Air Pak) in emergency situations.
B. Coveralls, white paper (53-129-010) or yellow vinyl (63-380-112), overshoes or rubber boots and vinyl or rubber gloves are minimum acceptable protective clothing. Contaminated protective clothing will be disposed of in the same manner as asbestos materials.
NDUSTRIAL HYGIENE RESPONSIBILITY
Employee exposure monitoring will, be conducted as required by regulations. Ref . UC.C S.H. 256* OSHA Regulation. 29 CFR 1910.1001 and Federal E.P. Regulation 40 CFR 61.
MEDICAL EXAMINATIONS
Medical examinations for persons doing asbestos removal and/or demolition must be conducted in accordance with OSHA Regulation 29 CFR 1910.1001, J, 1 thru 6. Additional reference material may be found in OCC Corporation Occupation and Health Medical Manual, appendix 3, pages 2*3.
ASBESTOS REMOVAL NOTIFICATION/EPA Reg. 40 C.F.R. 61
When demolition or removal involves more than 160 square feet or 260 lineal feet of insulation containing more than one percent asbestos by weight, either in a single project or in a predictable series of projects over a course of one year that are additive to this amount it must be reported as follows.
L
030760
UHXOli CARBIDE CORPORATION MAINTENANCE PROCEDURE
SEADRIPT PLANT - 510 MAINTENANCE DEPARTMENT
NO: PAGft EFFEdriVfc: REVISION:
MP-I-6 SFoTTF 06-22-78 63-19-86
ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL. HANDLING ft DISPOSAL
A. The department in which the removal takes place notifies the Environmental Protection Department at least 10 days prior to planned demolition or as soon as possible after beginning an unplanned (finergency) project which exceeds the limits.
B. The Enviromental Protection Department notifies the appropriate Federal and State agencies.
TRAINING
All employees who may be exposed to airborne asbestos concentrations in excess of the exposure limit listed with or without the use of respirators must participate in a training program that includes these information topics:
A. Health affects associated with asbestos exposure.
B. Relationship between exposure to asbestos and smoking in producing
lung-cancer.
-
~. Nature'of operations which.could result in exposure to asbestos and necessary protective steps to minimize exposure including, as applicable, engineering controls, work practices, respirators, housekeeping and protective clothing.
D. Purpose, proper use, fitting instructions, and limitations'of the respirators used to' protect against asbestos fibers.
E. Review of all provisions contained in 29 CFR 1910.1001, Asbestos.
F. Training will be documented and recorded.
RECORD KEEPING
A. Applicable training and medical records for U.C.C. employees will be maintained by the location as required by applicable plant policies.
B. Applicable training and medical records for contract employees will be maintained by the contractor and will be available to UCC upon request.
OTHER:
For further information on asbestos removal and disposal refer to OSHA egulation 29 CFR 1910.1001, Federal E.P. Regulation, 40 CFR 61, UCC
>andard Practice, S.H. 256 and Occupational t Health Medical Manual,
Appendix 3.
030761
UNION CARBIDE CORPORATION TECHNICAL CENTER
P.O.BOX 8361 S. CHARLESTON, VY 25303
INTERNAL CORRESPONDENCE
To: See Distribution List
Date:
July 22, 1986
Orig. Dept HS&cA
Arm
Industrie! Hygiene
C.C. T. L Collins T. E. Hanning C. ?. Maxwell
Subject
Amenoa rentes Siansrc
On June 20985 OSKA amended its present standard 29 CFR 1910.1001 for Asbestos which hes gone into effect cn July 21,1986.
a summery of the changes in the health standard has been prepared by T. . Hanning of our Health. Safety and Environmental Technolor/ Group is attached for your review.
a significant difference in tne new standard is the oermissible exposure limit now reduced from 2.0 fibers per c.c. (f/c.c) to 0.2 f/ac. with an action level of 0.1 f/ac, 8-hour time-weighted average (TWA8). A ceiling limit of 10f/aa is no longer appIicaole in the amended standard.
The amended standard will result In a few changes tn now we handle asbestos containing materials. These changes are mainly relative to exposure monitoring techniques (Industrie! Hygiene responsibility), posting, training and protective equipment
We will provide guidance to those groups who are involved in handling asbestos containing materials. All questions relative to compliance with this standard me/ be addressed to this writer.
Attachment/ MAP
Manner A. Patel Technical Center Industrial Hygienist
Jo
C"
030762
UNr.'. -- r-.~ : 2- ^wnrCAATlwN
iNG.NE?iuG.
- ' "HCi-MCuCGY ScP'/iCSS C?;,S7J.'^T
"SALT*. SArST- ,-\S * ' TN'V.SN"i.L TECHNOLOGY
j - : .. VVSST viPOiNU
. o --
'J "
..
,, 0.
:/* s.`.` C A ."t C L M <* `i*'i W A1, i ps8A6/
TC: S. VI. Clark D. A. Scssslln
v. H. Connkoskl 2. A. Leonard 2. S. Leverton^ C. P. Maxwell ' 2. E. Neff T. ?. Raby
FROM:
T. E. Hanning
S::2utCT: final Rules for Octut:-'..'nr.l Censure
to Asbestos, Trefoil re, Ar.r:.:r'-.jl Alts,
and ^.ctAnollti fA-enr.r
-"A
1 JULi~m
* n r*i&
rt- O
lentTe-en:
Attached As a'prelAmAnary surmry of the changes between the ame-ded subject r.aalth standard and rna original -'.;b**stos standard as stated An Zt 1913.1001. The amended standard was sus i `-aisc by OSHA An the federal Reels =r. Cur.e 20. TS86 and win take e-'ect an Z- Ay 21 . 1986.
The Safety ar.d health Technology Manual health operating practice 2H-2S6 (Removal and Handling .'.toastContaining Insulation Material) will be revised to reflect the changes set forth in the amended OSHA standard.
Please cull If you have further questions or comments.
TH/jc
Attachments
T.fE. Hanning lx*. 5903
/
030763
Changes Between the Original and Amended Asbestos Occupational Health Standard
General
OSHA amends Its present standard (29 CFS 1910.1001) regulating occupational exposure to asbestos by developing two final standards that aoply to general industry and to construction because the differences In exposure and wort place conditions In general Industry and construction wort sites warrant separate treatment.
UCC activities would generally fall under the revised standard for general Industry.
OSHA has concluded that chemically modified asbestos should be regulated in the same manner as unmodified asbestos.
OSHA concludes that all forms of tremollte, anthophylllte and actlnollte should be regulated under the revised standards.
In the final standard the action level has been set at O'.l fibers per cubic centimeter (f/cc) which triggers the monitoring, medical, and employee Information and training requirements. This action represents no real change to the standard with regard to this provision, but merely clarifies OSHA's policy.
Permissible Exposure Limit
OSHA has reduced the current 2 f/cc permissible exposure limit (PEL) to an 8-hour time-weighted average (TWA) PEL of 0.2 f/cc. This lower limit should reduce the recorded mortality from lung cancer, mesothelioma, gastrointestinal cancer, and other types of cancer due to asbestos exposure.
Celling Limit
The amended standards do not designate a celling limit for exposure to asbestos. The original standard had a celling limit of 10 f/cc and was met througn engineering and work practice controls.
Exposure Monitoring
The table below lists the two exposure situations along with the monitoring frequency for each.
Exposure Scenario
Required Monitoring Activity
1. Below action level 2. At or above the action level
1. No monitoring required 2. Monitor exposure at least
every 6 months
-2-
030764
The emended standard requires the employer to collect airborne asbestos samoles using 25 mm diameter mixed cellulose filters and a 50 mra extension cowl. Samoles must be analyzed using a phase contrast microscope calibrated using a ohase shift test slide and equipped with a Walton-3eckett graticule. The filter samples must be prepared using acetone-trlacetln clearing solution and be counted In accordance with the *Aa rules contained In the NIOSH 7400 method.
Regulated Areas
The amended standard requires employers to Identify as regulated areas any locations In their wort places where there may be occupational exposures to airborne concentrations of asbestos above the PEL. The amended standard prohibits eating, drinking and smoking In these areas. Only authorized persons may enter regulated areas which must be clearly marked. The existing OSHA standard does not contain a provision for establishing regulated areas.
Methods of Compliance
The amended standard requires employers to Institute engineering and work practice controls to reduce the exposure of employees to or below the PEL. If the employer establishes that such controls are not feasible,, selected respirators may-be used to supplement the engineering'and work practice controls.
Respiratory Protection
Respirators may be used to limit employee exposure to asbestos In the following circumstances.
1. Ourlng the Interval necessary to Install or Implement feasible engineering and work practice controls,
2. In work operations such as maintenance and repair activities or other activities which the employer establishes that engineering and work practice control procedures are not feasible.
3. In work situations where feasible engineering and work practice controls are not yet sufficient to reduce exposure to or below the PEL.
4. In emergencies.
These limitations on the required use of respirators are consistent with the requirements of the past asbestos standard and with good Industrial hygiene practice.
Protective Work Clothing and Equipment
The final standard makes a change from the current standard to respond to the evidence developed since 1971 that asbestos Is a potent human carcinogen. Protective clothing Is to be supplied to employees exposed above the PEL of 0.2 f/cc.
-3-
030765
The final standard provides that the employer ensure that all protective cloth In? Is removed at the end of each wort shift only In change rooms. The standard emphasizes the need to assure that contaminated clothing Is stored, cleaneo/laundered. or disposed of in a safe manner.
The final standard clarifies that the obligation Is on the employer to provide personal clothing at no cost to the employee.
The final standard also requires the employer to Inform those who handle the contaminated protective clothing of the potentially harmful effects of exposure to asbestos.
Hvolene facilities and Practices
The final standard like the existing standard reiterates the type of change room an employer must provide and the requirement that the employer prohibit the consumption of food and beverages In areas where there Is exposure to toxic substances. Unlike the existing standard, the final standard requires employers tor assure that employees exposed to asbestos during their work shift shower before leaving the. plant and do not leave wearing work clothing.
The final standard requires employers to provide persons working In asbestos areas with filtered air lunchrooms which are readily accessible. Employers must also assure that employees wash their hands and face prior to eating or smoking and do not enter the lunch room wearing protective clothing, unless cleaned beforehand.
Communication of Hazards to Employees
The final rule for asbestos requires that legible caution signs be posted at each regulated area where occupational exposures could exceed the PEL. Signs must also be posted at all approaches to areas containing excessive concentrations of airborne asbestos fibers. Signs must bear the following:
Oanger - Asbestos; Cancer and Lung Olsease Hazard - Authorized Personnel Only; Respirators and Protective Are Required
In This Area.
The final standard Is not substantially different from the present OSHA standard. The section on sign specifications simplifies the sign requirements and eliminates unnecessary detailed specifications (letter sizes and styles, spacing between lines) In favor of a more performance oriented approach.
-4-
030766
.
'he -.tended standard also requires - i\' - - materials. mixtu-es. .'=*. iris, and other product: cr.n:;::.-.q niestc: fibers. or their
: labeled -itn the appropriate
linger - Contains Asbestos .ter:; Avoid treating Oast; '.-:sr and '.an? Cl seise hazard.
~'-.t nev standard allows tvs except'.^:-: :o v-
zsr-z;
sheet: (HS2S) requirement;; no lace* or
` -t..here
labelling ane material : is required *.n those
* Asaestos fiber; have been modified by a bonding agent provided that the manufacturing can demon:tr--.ce that during any use the employee will remain below the act.-.n level; or
' Asbestos Is present In a product l.n concentrations les: than 0.1%. The new standard updates the existing-standard by providing that airborne concentration: .oust be fcept below the action level rather than the PEL.'
~'-z final standard requires employers to prov'da a training program for >"i *".;loy*es expected to be exposed to airborne asbestos at or above the
of 0.1 f/cc.
.''k! the existing standard vnlch
-^ct surfaces be
free of accumulation of asbestos fibers if, w'th their dispersion,
be en excessive concentration, the revised standard removes the
i.rr.a'.yhrase of excessive concentration. Specific provisions for house-
-eer
ire '.-.eluded In the final rule. Some of these are prohibiting the
olei:`.--t of iccestos dust with compressed air. dry-sweeping and dry clean-up,
and ; 'f. .s-i-g the accumulation of asbestos -aste on surfaces. OSHA
ant'd; :es tr.at compliance with this prevision will entail a regular
he..;-
ccnecule based on exposure conditions at a particular plant and
u>
ccp-ior ty for emergency cleanup of spills or other unexpected source of as:: re.
fleo i ", ~_ rve 111 ance
final standard requires that the medical surveillance program provide each affected employee with an opportunity for a comprehensive annual medic:1, examination. This does r.ot change the provisions of the existing st.In the final standard however, or;j.A believes it appropriate to trig-,-.-:- the ^epical surveillance requirements at the action level of 0.1 f/cc as e'.-.r.t-hcur TWA.
2LH-. has also revised the time within which the employer must conduct pre:lacr:T.=..c examinations after hiring employees. The final standard requires
that :.:-.ent medical examinations be given pr'or to the assignment of an
-tv.
1 ;; j job exposed to concentrations of ad-to-ne asbestos. The
-- .
permits the employer to conduct mec'crl examinations within
ays of the hire data.
030767
" The employer Is also required to hove medical examinations performed by or under the supervision of a licensed physician, provide the physician with a copy of this standard and all work practice Information performed by tno employer, and obtain a written signed opinion from the physician containing the results of the medical examination.
The final standard requires that x-rays be offered at S year intervals during the 10 years following an employee's first exposure to asbestos. After 10 years the employee's age category will determine the
frequency of x-ray testing.
Record Keeping
The final rule provides that records be kept to Identify the employee monitored and to reflect the employee's exposure accurately. The employer Is free to keep records the most effective way. The time period required for retention of exposure records Is thirty years. Employers must notify the Olrector In writing at least 3 months prior to the disposal of any records.
Appendices
Eight appendices are Included In this final standard.
Appendix
Status
A - Reference Method for Analyzing Air Samples for Asbestos
Mandatory
B - Asbestos Sampling and Analysis by NIOSH Method 7400
Mon-mandatory
C - Qualitative and Quantitative Respirator kit testing Procedures
Mandatory
0 - Medical Questionnaire Given to Employees Who May Be Exposed to asbestos
Mandatory
E - Interpretation and Classification of Chest Roentgenograms
Mandatory
F - Work Practice and Engineering Controls for Automotive Brake Repair Operations
Non-mandatory
6 - General Technical Information on Asbestos
Non-mandatory
H - Medical Surveillance Guidelines
Non-mandatory
TEH:Jc 07-10-86
51220
-6-
030768
UNION CARBIDE CORPORATION
Owmcsls and Plastics Dtastw
Pi. Bom 186
____
Port Lavaca. Texas 77979
INTERNAL CORRESPONDENCE
ro: A W. Kenne
2229
one. August 11. 1986
From: Safety
Cm to: M. L. Fox J. N. Permit
13 13
Subject: ASBESTOS RESPIRATORS
The new OSHA Asbestos Standard requires that powered air respirators will be provided to employees exposed to asbestos If they request them. I do not feel that we should provide powered air respirators for UCC employee use in the plant since we do not get involved with asbestos insulation removal. However, you may want to inform B&R of this new OSHA requirement so that they can provide them If requested.
Sincerely,
L 6. McMullen
030769
MOBILE DECON UNIT
Unit to be mounted on a 20' Tandem Axle Trailer with a Tongue
Mounted Leveling Jack, 2" Ball Hitch, 6 Plyrated Tires (no spare
required). The aluminum outer cover shall be primed and painted
to prevent corrosion. We may want to paint it here to assure an
adequate paint job.
The Unit should be 3 compartmented consisting of:
1. A Dirty Area with a built in negative air flow system of
adequate capacity to prevent contaminated air from
entering the clean area. This area should be lighted,
have storage space, benches, hangers for miscellaneous
items and a waste container for contaminated throw away
items. There should be a clothes washer and dryer
installed with the washer discharge water piped into the
shower holding tank and the dryer discharge ducted to
the inlet of the negative air flow system. There should
be several 110 volt electrical outlets and the walls and
floor should be constructed of materials that are easily
cleaned and waterproof. The access door to this area is
preferred through the back of the trailer. The access
way should have a retractable steps.
2. A Shower or Clean Up Area consisting of two showers, an
inline electrical hot water system capable of supplying
ample hot water for both showers and the wash machine.
Me will not operate the washer and showers simultaneously.
A waste water holding tank equipped with a pump to discharge
waste water through a dual filtering system. Final
filtration shall be 5 micron maximum.
030770
3. A Clean Area which is air conditioned, heated and lighted, has at least eight lockers for personal items and clothing that have hasp type locking devices. There must be adequate space for storage of protective clothing and respiratory equipment, gloves, filters, towels, etc. There should also be several 110 volt electrical outlets. Outside access to this area should have a retractable steps.
This Unit should be equipped to receive 220 volt power from a transformer we will mount in the tongue area. The Unit electrical wiring shall be circuit breaker equipped and the electrical wiring should be in conduit or be of heavy duty underground rated wire. The potable water connection will be a hose bib with a shut-off valve. The access doors must be locable.
030771
(%&yemreen VSAFETY SYSTEMS. INC
MOBILE DECONTAMINATION UNITS (NEGATIVE FORCE HIGH EFFICIENCY FILTERING SYSTEM) A CMfklcly tK-nmilirt
MDU-SC
PORTABLE HOT WATER UNIT
NEGATIVE AIR UNIT 030772
030773
*
CRIT REF
DATE
LOCAXIOR
06/06/94 PROD. ROOM 5. OF
259242
tl VEHT STACK
06/17/94 H.W. OF POLY BINS 259236
HP2 SUBTOTAL: 2
OH the JOB CIA SUM1ARY with %ASBEST054 in the description
01/01/94 to 06/30/94
TYPE
DESCRIPTION
CONDITION
MIT
WHILE ENPTYING CONTENTS OP ASBESTOS GASKET CAN I POUND SCRAP POLY IN BOTTOM
or CAN.
CONDITION
MIT
POUND PAPER AND PLASTIC TRASH IN AN ASBESTOS GASKET CAN.
04/17/94 BUILDING 353 247662
06/06/94 WILDING 354 259241
LP1 SUBTOTAL: 2
CONDITION
MIT
I NOTICED THAT AN EMPLOYEE WAS USING AN ASBESTOS BAG TO CARRY HIS TOOLS AND EQUIPMENT AROUND WITH HIM.
CONDITION
ran
WHILE CHECKING ASBESTOS CANS FOR GASKETS I NOTICED THE CAPS ON THE EYE BATH
WERE OFF.
01/19/94 SCREEN PACK BURNER 230582
06/17/94 SCREEN PACK BURNER 247676 LPlF SUBTOTAL: 2
CONDITION
MNT
"ASBESTOS GASKET ONLY" DISPOSAL CAN HAD LID OPEN. THE CAN SEEMED TO HAVE BEEN RUN INTO OR KICKED IN, THEREFORE NOT ALLOWING LID TO SEAL. THE CAN IS EMPTY WITH A NEW LINER.
CONDITION
MNT
FOUND WIRE AND TRASH IN AN ASBESTOS GASKET CAN.
06/06/94 G--500 REACTOR 246600
LP1R SUBTOTAL: 1
CONDITION
MIT
I FOUND NON-ASBESTOS INSULATION IN AN ASBESTOS GASKET CAN.
06/06/94 BUTYLS TANK FARM 259229
06/17/94 BUTYLS TANK FARM 259237
ODU SUBTOTAL: 2
CONDITION
MNT
I POUND METAL OBJECTS AND TRAHS IN AN ASBESTOS GASKET CAN.
CONDITION
MNT
I POUND FIBERGLASS INSULATION IN AN ASBESTOS GASKET CAN.
01/05/94 SEPARATIONS 255083
CONDITION
MIT
SAW SOME ASBESTOS ON THE FLOOR
01/24/94 FURNACE REPAIR SHOP 230352
CONDITION
MIT
THERE HAS AN ASBESTOS GASKET CAN WITH NO TOP ON IT
02/18/94 W. SIDE 246725
CONDITION
M9T
WHILE CHECKING SCAFFOLD I NOTICED SOME UNIDENTIFIED INSULATION ON THE DECK
WE SUSPECTED IT TO BE ASBESTOS.
02/22/94 N. SIDE BOILER 22 246727
CONDITION
MIT
FOUND WRAPPING SUSPECTED TO BE ASBESTOS HANGING FROM OLD TUBING
02/22/94 E. WALKWAY SECOND 230746 LEVEL
CONDITION
MIT
OUTSIDE CONTRACTOR WENT UNDER ASBESTOS BARRICADE.
030774
03/22/94 WEST Of MKP TANK 247854
04/29/94 E. Of 501 248590
OL2 SUBTOTAL: 7
CONDITION
nn
NOTICED SOME INSULATION ON THE GROUND, THAT COULD BE ASBESTOS.
CONDITION
wr
I NOTICED WAT APPEARED TO BE ASBESTOS INSULATION LAYING ON THE GROUND.
01/06/94 SOOTH SIDE WALKWAY 255113
CONDITION
HNT
ASBESTOS INSULATION ON WALKWAY. COULD NOT SEE WHERE IT CANE FROM.
01/31/94 SOOTH SIDE *1 OXIDE 193577
CONDITION
MNT WHEN I WAS DOING OUR MONDAY MORNING CLEAN UP I NOTICED SOME INSULATION ON THE GROUND. I WERT FOR A BETTER TOOK AND FOUND IT TO BE ASBESTOS.
OXI SUBTOTAL: 2
06/08/94 BUILDING 11 259231
FPU SUBTOTAL: 1
CONDITION
MIT
WHILE CHECKING ASBESTOS CAMS FOR GASKETS I FOUND ASBESTOS CAN HAD BEEN
THROWN IN METAL BIN.
06/06/94 WELD SHOP SPOT 24 246601
06/08/94 WELD SHOP 259235
SHOP SUBTOTAL: 2
CONDITION
MIT
I FOUND STYROFOAM IN AN ASBESTOS GASKET CAN WHEN CHANGING LINERS.
CONDITION
MWT
THE ASBESTOS GASKET CAN USUALLY LOCATED HERE WAS MISSING.
06/07/94 DECONTAMINATION 263085 TRAILER
CONDITION
MNT FOUND THAT SOMEONE HAS BEEN STEALING OUR WASHING LIQUID ITS NOT A GREAT LOSS BUT ITS STARTING TO HAPPEN MORE OFTEN TJHIS TIME WE HAVE RECOGNIZED THAT THIS INDIVIDUAL IS ALSO GOING INTO OUR DIRTY ROOM WHICH IS CONCIDERED CONTAMINATED WITH ASBESTOS UNTIL COMPLETELY CLEANED.
06/06/94 306 EAST 259230
CONDITION
MIT
I FOUND ASSORTED TRASH IN AN ASBESTOS GASKET CAN.
06/08/94 S. SIDE HIGH BAY 259238 AREA
CONDITION
MNT
FOUND AN ASBESTOS GASKET CAN WITH PLASTIC CUPS IN IT.
06/08/94 INSIDE CONTROL ROOM CONDITION
MNT
259234 02 UNIT
I FOUND PAPER TRASH INSIDE AN ASBESTOS GASKET CAN.
UNSP SUBTOTAL: 4
GRAND TOTAL: 25
030775
CRIT REF
DAZE
U3CAZION
07/38/94 N. SIDE OP DOCK 259495 FROM PIPERACK
BDK SUBTOTAL: X
ON the JOB CIA SUTIARY with %Asbstost in the description
06/01/94 to 12/31/94
TYPE
DESCRIPTION
CONDITION
WIT
I POUND SODA CANS AND TRASH IN AN ASBESTOS GASKET CAN.
06/06/94 PROD. ROOM S. OF
259242
11 VEST STACK
06/17/94 B.W. OF POLE BINS 259236
HP2 SUBTOTAL: 2
CONDITION
HIT
WHILE EMPTYING CONTENTS OP ASBESTOS GASKET CAN I POUND SCRAP POLY IN BOTTOM
OP CAN.
CONDITION
MNT
POUND PAPER AND PLASTIC TRASH IN AN ASBESTOS GASKET CAN.
06/06/94 BUILDING 354 259241
LP1 SUBTOTAL: 1
CONDITION
MNT
WHILE CHECKING ASBESTOS CANS FOR GASKETS I NOTICED THE CAPS ON THE EYE BATH
WERE OFF.
06/17/94 SCREEN PACK BURNER 247676
LP1F SUBTOTAL: 1
CONDITION
MNT
POUND WIRE AND TRASH IN AN ASBESTOS GASKET CAN.
06/06/94 G-500 REACTOR 246600
LP1R SUBTOTAL: 1
CONDITION
WIT
I FOUND NON-ASBESTOS INSULATION IN AN ASBESTOS GASKET CAN.
06/06/94 BUTYLS TANX FARM 259229
06/17/94 BUTYLS TANK FARM 259237
ODU SUBTOTAL: 2
CONDITION
WIT
I FOUND METAL OBJECTS AND TKAHS IN AN ASBESTOS GASKET CAN.
CONDITION
WIT
I POUND FIBERGLASS INSULATION IN AN ASBESTOS GASKET CAN.
09/06/94 N.W. CORNER OF 260415 COOLING TONER
09/07/94 GAS-2 MAINTENANCE 261935 SHOP
OL2 SUBTOTAL: 2
CONDITION
WIT
EXPOSED INSULATION WHIOI IS MARKED ASBESTOS.
CONDITION
WIT
SOMEONE PUT TRASH IN AN ASBESTOS CAN.
06/08/94 BUILDING 11 259231
PPU SUBTOTAL: 1
CONDITION
MNT
WHILE CHECKING ASBESTOS CANS FOR GASKETS I FOUND ASBESTOS CAN HAD BEEN
THROWN IN METAL BIN.
06/06/94 WELD SHOP SPOT 24 246601
CONDITION
MNT
I FOUND STYROFOAM IN AN ASBESTOS GASKET CAN WHEN CHANGING LINERS.
030776
06/08/94 MELD SHOP 259235
12/13/94 BUILDING 165 266013
SHOP SUBTOTAL: 3
CONDITION
nrr
THE ASBESTOS GASKET CAN USUALLY LOCATED HEBE HAS HISSING.
CONDITION
MIT
PARTS OF ASBESTOS GASKET ON FLANGE FACE OF VOLATE.
06/07/94 DECONTAMINATION 263085 TRAILER
CONDITION
MIT FOUND THAT SOMEONE HAS BEEN STEALING OUR WASHING LIQUID ITS NOT A GREAT LOSS BUT ITS STARTING TO HAPPEN MORE OFTEN TJH1S TIME HE HAVE RECOGNIZED THAT THIS INDIVIDUAL IS ALSO GOINS INTO OUR DIRTY ROOM WHICH IS CONCIDERED CONTAMINATED WITH ASBESTOS UNTIL COMPLETELY CLEANED.
06/06/94 306 EAST 259230
06/08/94 S. SIDE HIGH BAY 259238 AREA
06/08/94 INSIDE CONTROL ROOM
259234
02 UNIT
CONDITION
mr
I FOUND ASSORTED TRASH IN AN ASBESTOS GASKET CAN.
CONDITION
mr
FOUND AN ASBESTOS GASKET CAN WITH PLASTIC CUPS IN IT.
CONDITION
mr
I FOUND PAPER TRASH INSIDE AN ASBESTOS GASKET CAN.
07/10/94 SOUTH or 02 UNIT 260317
CONDITION
mr
POUND TRASH IN ASBESTOS CAN.
NOT FOR TRASH.
THE ASBESTOS CAN ARE FOR ASBESTOS GASKETS ONLY
UNSP SUBTOTAL: 5
GRAND TOTAL: 19
030777
*
CRIT REP
DATE
LOCATION
01/23/95 BLDG. 165 267470
NIT SUBTOTAL: 1
04/19/95 OLEFINS 267293
0L2 SUBTOTAL: 1
GRAND TOTAL: 2
Oil th* JOB CIA SUtlAKY with tAsbastos* in th* description
01/01/95 to 12/31/95
TYPE
CONDITION
MNT
ASBESTOS GASKET OH FLANGE.
DESCRIPTION
CONDITION LEE YAKLIN
NIT
Found asbestos tubing wrap in domestic trash can.
030778
I
OUT RET
DATE
LOCATION
05/19/89 B327 105144
CSD SUBTOTAL: 1
ON the JOB CIA SIMtARY with 4ASBESTOS8 in the description
01/01/89 to 12/31/89
TYPE
DESCRIPTION
CONDITION TOMAS ROSARIO
CSD
Builiding 327, sro using asbestos sheet to cover the awning ceiling.
some building in EMS are using it for cover on outiside of building.
Also,
08/11/89 OOCXFRONT MARINE 143913 TERMINAL
DIS SUBTOTAL: 1
CONDITION
ROBIN LCM1AN
DIS
Insulators reaoved asbestos insulation froa acetic acid unloading pot on 8/7
and 8/8. On 8/11 I went down to the systen and found asbestos pieces in
area that had not been cleaned up and properly disposed of.
04/10/89 138260
05/08/89 COGEN 115761
08/03/89 MWT BLDG 154556
08/10/89 148687
08/16/89 148651
12/19/89 155082
ENS SUBTOTAL: 6
CONDITION LOUIE XRAMER
MNT
Asbestos gaskets on floor of Maint shop in ENS.
CONDITION GORDON BEATTY
MNT
8* asbestos gasket on the ground.
CONDITION MIKE HARD
MNT
Asbestos gasket storage area is dirty.
CONDITION LOUIE KRAMER
MNT
Asbestos gaskets in bucket on floor of Maint. Shop.
CONDITION LOUIE KRAMER
MNT
Roll of asbestos gasket material under shed.
CONDITION LOUIE KRAMER
MNT
Asbestos gasket stuck to flange on pad of Maint. work area.
04/06/89 101 B 132522
08/14/89 148693
HP1 SUBTOTAL: 2
CONDITION RICK DOLEJSI
MNT
Paper trash in asbestos can.
CONDITION LOUIE KRAMER
MNT
Asbestos gaskets on the floor in work area.
04/05/89 SHOP 134219
05/10/89 B560 133089
05/15/89 SHOP 134224
HF2 SUBTOTAL: 3
CONDITION RICHARD THOMPSON
MNT
Noticed asbestos naterial left on work table.
CONDITION ANDREW VASQUEZ
MNT
Could not find a container to dispose of asbestos gaskets in shop.
CONDITION DIANE THOMPSON
SHF
Asbestos gaskets on floor of shop.
04/04/89 138264
04/06/89 353 142223
CONDITION LOUIE KRAMER
MNT
Asbestos gaskets hanging froa storage racks, second level of Building 341.
CONDITION VAN SHRADER
MNT
Observed a person cutting Garlock 900 asbestos gasket with tin snippers.
The gasket material wasn't moistened with water and person had no respirator
030779
04/13/89 149122
04/07/89 INST. WORK SHOP 142047
06/02/89 138218
06/02/89 138219
06/02/89 138220
06/19/89 148664
08/09/89 148685
09/12/89 FRECURSER UNIT 121639
12/18/89 MNT SHOP 155066 12/18/89 NR SHOP 155068
LPl SUBTOTAL:: 12
on.
CONDITION
IRA riLLMORE JR
KMT
Equipment uid air handling room at B353 being usad as a storaga room,
including two larga rolls of asbestos gasket material.
CONDITION TOMQE HOLT JR
MNT
I found an asbastos gaskat, by tha telephone in tha shop.
CONDITION LOUIE KRAMER
NR
20* asbastos gaskat in fibar drum that was full of othar typas of trash
locatad undar 1750 raactor.
CONDITION LOUIE KRAMER
NR
Asbastos gaskat hanging on storaga rack on tha aast sida of sacond laval B341.
CONDITION LOUIE KRAMER
HR
Usad asbastos gaskat on valva dalivary/storaga rack locatad north wast
comar of LF1 block.
CONDITION LOUIE KRAMER
HR
Naw and usad asbastos gaskats laft on work banch in Maint. shop LP1.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskat on workbanch in Maint. Shop.
CONDITION ANN THOMASON
MNT
Garlock asbastos gaskat fro* haxana siava at pracursar unti thrown down on
tha ground.
CONDITION LOUIE KRAMER
NR
Asbastos gaskats in 10 Qt. galvanizad buckat.
CONDITION LOUIE KRAMER
MNT
Cabinat drawer opan exposing asbastos gaskat aatarial.
04/03/89 LP1R 142386
07 08/11/89 BLOCK 12 156814
10/17/89 345E, G-MDC 146568
10/31/89 2ND LEVEL CAT BINS 156677
LF1R SUBTOTAL: 4
CONDITION CRAIG STRAK0S
MNT
Found two 899 asbastos gaskats laying on grating.
wash water lines.
Construction was removing
INCIDENT
JESSE TIJERINA
LP1
In tha process of revising utility drops to comply with plant policy, 75#
steam utility drop piping broke upstream of isolation valve. The utility
drop piping fell to the ground. Several pieces of insulation broke off and
fell to the ground. Portions of the insulation on tha piping were asbastos.
CONDITION JAMES MEISCHEN
HR
Has cleaning up work area and noticed two asbastos gaskats laying beside an
I-beam.
INCIDENT
JOHN OSWALT
SHT
Discovered maintenance removing asbestos from pipe in area.
had not notified myself or Tech, staff of this area.
These workers
06/13/89 148799
11/26/89 GROUND LEVEL 14 2
149280
COMP
LP2 SUBTOTAL:: 2
CONDITION MARK SCHROLLER
NR
Asbestos gaskets laying on table in control room.
CONDITION
GEORGE DANDY
SHT
The drua located on the ground level between the 81 a 82 compressor marked
for asbestos material and gaskats only has baan usad for other material.
Tha bottom of tha dura is rusted out and tha lid is missing. Material is in
a reinforced plastic bag and contained.
12/12/89 B1 CAFETERIA
CONDITION DAVID LUGO
MNT
030780
150180 MISC SUBTOTAL: 1
Pound a 3/8* drinking water lina used to sarvica icemaker with asbestos taping.
03/30/89 STORES 139108 04/17/89 SKEETHKS RACK 138989
05/31/89 140-1 148917
06/07/89 140-1 148909 07/10/89 140-1 148901
08/22/89 510 SIOUXS 153760
08/30/89 B9 158716
10/30/89 B-140-1 158742
NS) SUBTOTAL: 8
CONDITION CARL BOSIER
WD
Employee noticas asbastos material was removed from it's plastic containar.
CONDITION EPRAIN GUERRA
fWD
1 roll of 1/6' 10'xlO' coda 428794-113 is not protactad with a shaat or
labalad with tha containars asbastos tag.
CONDITION CARL BOSIER
MV3
Asbastos gaskat notarial not in plastic containar, had baan raaovad.
CONDITION CARL BOSIER
MMD
Asbastos aatarial not in it's plastic protactiva covar.
CONDITION CARL BOSIER
H4D
Found asbastos gaskat aatarial shaat laft unwrappad not in plastic containar
to containar asbastos dust fibar.
CONDITION
WILLIAM INFANGER
PPU
Notica insulatad pipas ovarhaad of kaypunch oparator at tha antranca.
pipas appaarad to ba asbastos.
Tha
CONDITION CARL BOSIER
WD
Noticad wood that had containad asbastos gaskat, but was raaovad, parsonnal
raaoving gaskat laft scrap boards, cardboard with nails in upright position.
CONDITION CARL BOSIER
WD
Asbastos shaating aatarial was not in plastic wrap or containar to contain
asbastos dust fibars.
03/30/89 ASB WASH PAD 117126
' CONDITION WILLETT NEILL
MNT
Found asbastos gaskats on wash pad.
04/03/89 140-2 SOUTH 135445
-CONDITION
KEITH HAHN
MNT
two hosas with 1504 flangas wara found on tha south sida of tha Ttl shop
without a shipping tag, no work request, and 2 asbestos gaskats on the
flangas.
03/30/89 SPRAY GAS COOLER 2 135902
CONDITION
BSR
I assigned 2 nan to scrape asbastos gaskats, without Baking sura they had baan trained in tha hazards of AsB dripolene and without Baking sura they usad tha facilitas at B304 to prevent contamination of their clother and boots.
03/30/89 ASB DRIP PAD 127586
CONDITION
BSR I noticad a couple of gaskats possibly asbastos, plant poly requires that tha reaoval of all asbastos ba dona with special precautions by trained individuals. Halliburton whoa is working on ths pad should ba informed about tha situation.
03/31/89 380 135916
CONDITION
BSR
Want to clean out asbastos gaskat cabinet and found used and broken up
gaskets laying on tha top of tha cabinet and on tha floor under it.
04/07/89 141097
LANDFILL NON HAZ PIT
CONDITION
ED HEISOLD
MNT
Truck hauling roll off bins to landfill had bad sida on box. Tha box broka
open at tha bottom along sida of Bin casuing plastic bag to tear open when
unloading Bin exposing asbastos contaminated fum brick to tha air.
04/18/89 B306 138245
CONDITION LOUIE KRAMER
MNT
20* asbastos gaskats on floor in storage area of Maint. Shop B306.
04/20/89 INSTRUMENT SHOP 127655
CONDITION LUPE RODRIGUEZ
MNT
Vee--ball valve/body was sant to tha instrument shop.
(contains asbastos) had not baan removed.
Valve flange gaskats
03078 J
04/24/89 B160 138238
CONDITION LOUIE KRAMER
NR
Asbastos gaskets stuck to pip* flangas on pip* schadulad to go to salvaga.
04/24/89 B101 135912
CONDITION
BAR
Can full of asbostos and ragular trash without a disposal bag insida of can.
Can was claarly narkad asbastos gaskats only.
04/25/89 MELD SHOP 147438
CONDITION BOYD BLAKE
MNT
A coaprassor aufflar was brought to tha Wald Shop with a asbostos gaskat
still on tha glanga.
04/24/89 B101 135912
CONDITION
BAR
Can full of asbastos and ragular trash without a disposal bag insida of can.
Can was claarly narkad asbastos gaskats only.
04/24/89 HELD SHOP 147437
CONDITION LARRY HERRON
NR
Mufflor nanway had a gaskat laft on, gaskat was asbostos notarial.
04/24/89 TfcX 134204
CONDITION JOSEPH DAILEY
NR
Hhilo ranoving a safaty valva from sona aquipnant that is out of sarvica,
savaral asbastos gaskats all around tha araa.
05/08/89 PIMP REPAIR SHOP 144610
CONDITION
BAR
Want to onpty asbostos gaskat can, found can full without asbostos disposal
bag insida.
05/26/89 LP1 135509
CONDITION BOB KALICK
NR
Bolts, nuts, loosa objacts, torn asbastos insulation, on top of pantana
coluan.
06/05/89 REPAIR SHOP 121959
CONDITION DAVID DENTLEK
HR
Asbastos gaskat was laft on punp flanga.
06/08/89 INST SHOP 146472
CONDITION BURL HENSLEY JR
MNT
A 3-way valva caaa to tha shop to ba ovorhaulad, had asbastos gaskats on tha
flangas.
06/23/89 NTT 150507
CONDITION BOB TATE JR
MNT
Sonaona laft a pipa spool with an asbostos gaskat stuck on flanga at WTF-low
truck loading spot.
08/01/89 PF RIG SHOP 154520
CONDITION MIKE WARD
MNT
Asbastos storaga naads claanup.
08/01/89 REPAIR SHOP 154519
CONDITION MIKE WARD
MNT
Asbastos storaga araa naads claanup.
148522 TU
CONDITION BOB TESQt
MNT
Asbastos cabinat contains nisc. aatarial and dirty.
08/15/89 TAI SHOP 138508
CONDITION BOB TESCH
MNT
Gaskats in various cabinats ara thay asbastos?
08/17/89 PROJECTS CREW SHOP 148663
CONDITION LOUIE KRAMER
NR
Asbastos packing in parts storaga bin in projact craw shop.
08/09/89 MAHR. STORAGE BLDG CONDITION
BAR
146576
Found chunks and piacas of asbastos on pad.
08/21/89 PROJECT (SEW SHOP 154617
CONDITION MIKE WARD
MNT
Asbastos storaga cabinat naads claanup.
09/01/89 LAYDOWI TARO 154771
CONDITION LOUIE KRAMER
MNT
Asbastos gaskat on 8" drillad flanga in HP2 storaga rack.
09/01/89 LAYDOWH YARD 154772
CONDITION LOUIE KRAMER
MNT
Asbastos gaskats on pallat south sida of alactrical storaga containars.
09/01/89 LAYDCMI YARD 154768
CONDITION LOUIE KRAMER
NR
Asbastos gaskats stuck to vacuua sats on pallat in ODU.
09/01/89 LAYDOWN YARD 154761
CONDITION LOUIE KRAMER
MNT
Asbastos gaskats stuck to valva flangas north sida of LP araa.
030782
09/18/89 INST SHOP 110567
09/18/89 REPAIR SHOP 152882
09/28/89 REPAIR SHOP 152883
10/19/89 LAYDOHi YARD 150569
10/10/89 PROD ROOM 150863
10/17/89 154955
11/01/89 INST SHOP 110557
11/08/89 163 S 155125
12/06/89 REPAIR SHOP 156325
12/06/89 REPAIR SHOP 156326
: 40
03/21/89 GEU 114693
04/06/89 GEU 114694
04/05/89 135365
04/14/89 135501
05/04/89 GEU 138227
05/04/89 138228
06/07/89 150690
06/13/89 150687
07/10/89 BUTYLS 146547
07/20/89 B367 156705
07/10/89 B367 156706
08/15/89 148650
08/15/89 148694
CONDITION GLENN WISE
MNT
Slid* gat* valva came to shop with asbastos gaskat on flanga.
INCIDENT RAYMOND HILL JR
MNT
Pound asbastos gaskat on pump flanga that was dalivarad to rapair shop.
CONDITION RAYMOND HILL JR
MNT
Asbestos gaskat was laft on pump flanga.
CONDITION BUD DAVIS
MNT
Found asbastos gaskat on haat exchanger in laydown yard exposed.
CONDITION FRENOIIE CORMIER
MNT
I found a 1 t 3 inch flaxitallic asbastos filled gaskat on top of tha
pollster water box.
CONDITION MIKE WARD
MR
Asbastos gaskat storage area needs cleanup.
CONDITION GLENN WISE
MIT
Valve cane to shop with asbastos gaskets still on flange surfaces.
CONDITION LARRY KNEBEL
MNT
Found asbastos gaskets on fuel valva, sent to Inst. Shop from 0L2.
CONDITION DARRYL LYNCH
MNT
Punp was sant to rapair shop with asbastos gaskat still on flange.
CONDITION RAYMOND HILL JR
MNT
Asbastos gaskat still on discharge flanga of punp.
CONDITION DICK SCHNEIDER
MNT
Found asbastos gaskat on pipe construction removed,
CONDITION DICK SCHNEIDER
MNT
Found asbestos gaskat on the pad.
CONDITION BB BROWNING
MNT
Asbastos gaskat was laying on the ground by refining column calandria.
CONDITION BOB KALICH
MNT
Found asbastos gaskets on th* ground and in structure.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskets on concrete pad in Maint work area.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskets tiara in regular trash can in ODU Maint. Shop.
CONDITION BB BROWNING
MNT
Used asbastos gaskat was laying on th* ground.
CONDITION BB BROWNING
MR
Foudn asbastos gaskat laying beside th* work bench.
INCIDENT
WAYNE JACOBS
SHF
Hhil* removing asbastos in tha ODU area an outside contractor had an
epileptic saisur*.
CONDITION LEE YAKLIN
MNT
Sheet of asbastos gaskat material in dumpster.
CONDITION LEE YAKLIN
MNT
Maint shop cage needs sign on cage warning that asbastos gaskets are stored
inside cage.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskat scraps on east sawar pump.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskets on the ground.
030783
09/18/89 GEU 150634
09/18/89 GEU 150628
10/18/89 150604
10/20/89 150551
11/29/89 150540
12/11/89 150531
12/18/89 MORE AREA 155069
12/18/89 GEU 155070
QOU SUBTOTAL: 21
CONDITION BB BROWNING
WT
An asbestos gasket was laying on the ground.
CONDITION BB BROWNING
wr
L*borar found a valva that had insulation raaovad off it and appaarad to ba
asbestos material laying on the ground.
CONDITION BB BROWNING
tffTT
Found asbestos gasket laying on ground whare equipment had been scraped.
CONDITION BB BROWNING
MNT
Asbestos gasket laying on tha ground.
CONDITION BB BROWNING
mr
Found a asbestos laying in unit trash barrel.
CONDITION BB BROWNING
HIT
Asbestos gasket was stuck to a pipe flange.
CONDITION LOUIE KRAMER
HR
Asbastos gaskat on pad.
CONDITION LOUIE KRAMER
MNT
Used asbestos gaskets on grating at switch station.
04/18/89 138244
04/18/89 138243
04/18/89 138241
05/02/89 CONTROL ROOM 142303
08/17/89 306 SHOP 155201
OL1 SUBTOTAL: 5
CONDITION LOUIE KRAMER
NIT
Asbestos gaskets scattered on the ground by the Methanol tank on the east
side of 41 Olefins.
CONDITION LOUIE KRAMER
MNT
Two plastic sacks of bolts and asbestos gaskets on the ground my Methanol
tank located on the eastside of 41 Olefins.
CONDITION LOUIE KRAMER
MNT
Asbestos gaskets on ground and on pallets inside fenced in area across road
south side of 41 Olefins.
CONDITION DARRELL BAILEY
NIT
While waiting for operator to issue HWP noticed what appeared to be asbestos
insulation uncovered above panel board.
CONDITION ERNEST DEHOYOS
MNT
Found metal lugger bin with instruaent tubing still wrapped with asbestos
tape wrapping.
04/07/89 COMPRESSOR BUILDING 146281
CONDITION ERNEST GARCIA
NIT
As you walk inside the NE door of the compressor building ther is a steam
drop with asbestos insulation that is exposed.
04/12/89 81 PRECOOLER - TOP 146300 LEVEL
CONDITION
ERNEST GARCIA
NfT
Found sob 1/2* pipe on the top level of 41 Precooler.
this, is that the pipe had asbestos insualtion on it.
What' s so bad about
04/18/89 FURNACE AREA 146336
CONDITION BILL FOX JR
HIT
While preparing to transport two motor valves to the instruaent shop, I
suspected that they had asbestos gaskets on the flanges.
04/18/89 OLEFINS FLARE 138248
CONDITION LOUIE KRAMER
MNT
Asbestos wrapped around insulation on ground by flare separator pot.
04/18/89 138250
CONDITION LOUIE KRAMER
HIT
Asbestos packing in Maint storage rooa north end of coopressor building.
04/18/89 138249
CONDITION LOUIE KRAMER
MNT
Bulk asbestos gasket material in storage cage in 42 olefins Maint shop.
05/02/89 422 BOILER
CONDITION LOUIE KRAMER
HIT
030784
136233
05/10/89 SPRAY GAS POOLERS 146384
05/12/89 SEPARATIONS 137541
06/21/89 SEPARATIONS 117156
07/05/89 SEPARATIONS 117154
07/17/89 148679
08/18/89 SEPARATIONS 156513
09/25/89 500N 156770
11/03/89 MAINT SHOP 162416
11/06/89 B500 117130
11/15/89 WEST or BLDG. 500 162429
12/11/89 B500 162439
: 18
Used asbastos gaskats on concrata pad.
CONDITION TED NELSON
MNT
Asbastos gaskats in donastic trash barral.
CONDITION JERRY DELGADO
MWT
Asbastos gaskats on ground by 12 C2H2 still.
CONDITION JERRY DELGADO
MNT
Asbostos gaskats insida trash can locatod north and saparations.
CONDITION ERNEST GARCIA
MNT
Asbastos insulation on tha ground. Had fallan out of piparack.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskat scrap aatarial laft on work banch in #2 Olafins Maint.
Shop.
CONDITION LARRY KCHALIK
SHT
Insulation on piping around II drip still is datarioratad badly and falling.
Sosa insulation is on abandonad piping and aay contain asbastos.
CONDITION
LEE YAXLXN
MNT
Racaivad a larga ordar of gaskats froa storas, many diffarant itaas with
savaral asbastos gaskats includad with non-asbastos gaskats. No warning as
to contants and asbastos gaskat not individually wrappad.
CONDITION WILLETT NEILL
MNT
Asbastos gaskat (usad) on tabla in Maint. Shop.
CONDITION WILLETT NEILL
MNT
Found savaral asbastos gaskats on tha ground naar aftar coolars araa.
CONDITION WILLETT NEILL
MNT
Found asbastos gaskat on ground.
CONDITION WILLETT NEILL
MNT
Found asbastos gaskats on pallat.
04/12/89 81 BIOCE 138254
04/14/89 B120 133873
04/13/89 130363
04/25/89 UNIT 150791
05/10/89 140945
07/10/89 12 148670
07/11/89 *2 148673
07/11/89 *2 148674
07/12/89 12 148675
81 07/08/89 144852
CONDITION LOUIE KRAMER
MNT
Asbastos gaskat on pallat with IGT parts storad in naw building at II
Glycol.
CONDITION BUDDY PERKINS
MNT
Found asbastos shaat in stora room.
CONDITION CHARLIE ZIRKELBACK
MNT
Saw 2 Flaxitalic gaskat on north nail rack of OXI that appaarad to ba
asbastos fillad.
CONDITION
RICK CURTIS
OXI
Cabla trays hava what looks lika asbastos insulation shaats undar than.
insulation is not ancapsulatad andis braaking off in savaral placas. ~
Tha
CONDITION ALEX MARTINEZ JR
MIT
Construction knockad off sona asbastos insulation fron cabla trays.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskat laft on top of pre-haatar locatad north and of air building.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskats on top convartor laval grating.
CONDITION LOUIE KRAMER
MNT
Asbastos gaskats on pad undar FI & F2 convartors.
CONDITION LOUIE KRAMER
MNT
Torn up asbastos gaskats on ground by BAC pracoolar.
INCIDENT
B4R
Construction insulation craw was stripping insulation froa 8" staaa lina
0307*5
that was still in sarvica. Upon seeing tha insulation Gan. Foraaan inquired whether insulation night contain asbestos. After performing an eapirical test, a good possibility was that insulation contained asbestos fibers.
07/30/89 82 148683
CONDITION LOUIE KRAMER
MNT
Asbestos gasket stuck to blind flange located on pallet of blind flanges
north side of 82 Oxide.
07/17/89 140937
CONDITION MARTY MARTINEZ
MNT
Asbestos insulation ws knock off. Cable tray between B2 and B3 scrubbers.
08/06/89 82 PURIFYING COLUMN 153624 AREA
CONDITION
RJ TRIPP
SHF
Found some asbestos on the pad. A lot of damage has been done to the unit
cable tray shields during hte recent shutdown. Small chunks of this
material has fallen to the ground level.
08/04/89 140599
CONDITION PAUL MOYA JR
SHF
Several small pieces and some dust of asbestos insulation were found on pad
west of B1 converter.
08/08/89 82 148684
CONDITION
LOUIE KRAMER
MNT
DMU from 82 oxide shutdown left on the ground north end of Air Compressor
Building, has an asbestos gasket stuck to the flange.
09/27/89 140910
10/26/89 LAYDCMIYARD 140893
CONDITION MARTY MARTINEZ
MNT
Found asbestos gasket laying on ground under south pipe rack Oxide I.
CONDITION MARTY MARTINEZ
MNT
Equipment was sent to laydown yard with asbestos insulation.
10/25/89 STORAGEBUILDING 154781
CONDITION LOUIE KRAMER
MNT
Trash can with asbestos gasket scraps located in south end Oxide storage
buidling.
OXI SUBTOTAL: 18
10/30/89 136706
FLE SUBTOTAL: 1
CONDITION ANDREW ENGELS
PLE
Instructor for safety training - Asbestos Awareness.
04/04/89 POLYPROPYLENE 132306
CONDITION TOM TOLER
MNT
Found three asbestos gaskets stuck on the flanges that were removed from
service and temporarily stored.
05/18/89 132562
CONDITION TOM TOLER
MNT
Asbestos gasket still on flange that had been removed from service.
06/15/89 5 PRESS BLOWER 134339
CONDITION JAMES MORGAN
SHF
Line insulated with waht was labeled asbestos, casing was missing in several
places and the insualtion was deteriorating.
07/25/89 132703
CONDITION ARMANDO GARCIA
KIT
Found several asbestos gaskets hanging on ladder rack. ( used)
08/02/89 JOINT BLDG 154538
CONDITION MIKE WARD
MNT
Asbestos storage cabinet not labeled, and dirty.
08/23/89 MAINTENANCE BUILDING CONDITION MIKE HARD
MNT
154631
Asbestos gasket storage cabinet - no label - not clean.
10/12/89 SOUTHSXDE MIT BLDG 154931
CONDITION MIKE WARD
MNT
Asbestos gasket storage cabinet needs cleanup.
12/19/89 155085
CONDITION LOUIE KRAMER
MNT
Several 4" asbestos gaskets under workbench FPU unit.
FPU SUBTOTAL: 8
GRAND TOTAL: 151
030786
8
OUT REF
DATE
LOCATION
05/03/90 H3C WASH FACILITY 163682
04/30/90 INSIDE BLDG. 3S0 139363
DIS SUBTOTAL: 2
ON the JOB CIA SUM1ARY with kAsbestos* in the dascription
01/01/90 to 12/31/90
TYPE
DESCRIPTION
CONDITION LOUIE KRAMER
MNT
8' asbestos gasket on the ground just outside KX wesh facility.
CONDITION
WES ZEPLIN
DIS
Found asbestos gasket material in regular trash can. Also suspect other
gasket in can night be asbestos. Also suspect asbestos gaskets are being stored with asbestos - free gaskets.
01/19/90 CHF STORAGE CAB 116031
CONDITION WILLIE BROMf JR
MR
Asbestos gasket stored in cabinet, also oily rags.
03/28/90 21 & 22 BOILERS 168761
CONDITION JOHN SIMONS
MR
Busted lines of asbestos all around boilers.
04/25/90 COGEN 164028
CONDITION EDDIE STEVENS
MNT
Asbestos gasket laying on ground by NR valve.
04/23/90 SW CORNER 11 STEAM
155406
PLANT
INCIDENT
BAR
Pipefitter working on steam tracing laak removed insulation wrap from tubing. Wrap was asbestos tape. Fitter was unaware of the wrap being asbestos.
05/02/90 12 FIRE WATER PUMP 168594 TURB
CONDITION RANDY LAMPREOJT
MNT
Noticed staaa piping going to 82 fire water pump turbine had asbestos
insulation on it.
07/25/90 SOUTH OF BLDG. 327 168731
CONDITION ROBERT GOSSETT
MNT
Found 4 pieces of 3/8" copper tubing wrapped with insulation (some asbestos)
in natal lugger bin.
ENS SUBTOTAL: 6
04/16/90 KP1 132708
09/23/90 SOUTHEAST DOOR AND
174171
WALKWAY
HP1 SUBTOTAL: 2
CONDITION TOM TOLER
MNT
Found asbestos gasket on second level of additive bldg that had been left
after a job.
CONDITION
ROBERT MORGENROTH
SHF
Two 'out of service' steaa lines leaking asbestos insulation into area.
Lines were started taking out of unit about 1 year ago, but never finished
removing.
09/25/90 BUILDING 11 186902
HF1PF SUBTOTAL: 1
CONDITION ARMANDO GARCIA
MIT
Two blind flanges in back of pickup truck with asbestos gaskets still stuck
on then.
11/08/90 KR2 195127
76 11/08/90 HF2 196059
CONDITION
BLR While removing asbestos gaskets in cell block no. 1, operator entered barricaded area and clinbed up to where I was working to check on flanges I was scraping.
ACCIDENT
BAR I had my asbestos tools in ny bucket, I took out ay pouch and ny knife fellout; at that point I reached in ny bucket to retrieve the knife not
030787
11/16/90 KPII 195101
BP2 SUBTOTAL: 3
noticing y hook knife. It cut ay thuab ont ho first joint.
CONDITION
But
Outsido contractor aaployso walkad through an asbestos barricade.
02/05/90 G3 BLENDER 142403
CONDITION JAMES MEISOffiN
MNT
Two used asbestos gaskets laying by G3 blender.
02/20/90 G17 142402
CONDITION EDDIE MOYA
MNT
Pipe with exposed asbestos insulation at oil pit.
05/10/90 BLOCK 12 157251
CONDITION JERRY FYKA
SOT
There is what appears to be asbestos wrap on tubing leads going to a couple
of instruments just south of the main C2H4 header emergency valve.
06/12/90 NOT OGMFOUNT HC-2 166484 AREA
CONDITION FAT DUNLAP
MNT
A flange on the 6001b. steaa header has a bad leak, and it blew off the
insulation material which is asbestos. Insulation.
08/04/90 G-17 COOLER ROOF 173482 AREA
CONDITION JOHN BRADLEY
NIT
While removing old walkways I found an asbestos gasket.
08/08/90 BULK 25 173478
CONDITION VAN SHRADER
MNT
While clean up unit grounds I found three asbestos gaskets on ground.
08/13/90 345 EAST 173477
CONDITION JAMES MEISCHEN
NIT
Found 1 1/2* pipe that had been removed from pipe rack with 2 asbestos
gaskets still on the flanges.
09/12/90 G-1750 173463
CONDITION JAMES MEISCHEN
MNT
I was taking measurements for a sketch when I found an asbestos gasket on a
beam.
10/01/90 PENTANE COLUMN 173363
CONDITION DONNIE MAREK
MNT
While working on pentane column I noticed some exposed asbestos insulation.
10/17/90 LP1 186261
CONDITION
BLR The insulators had put up a barricade tape saying "danger, asbestos'. hte area that they had barricaded off was very small and the wind was blowing slightly.
But
12/02/90 ODU OLD POLY REACTOR CONDITION JOHN BRADLEY
MNT
104607
Found exposed asbestos in pipe rack at old Poly-0Is reactor.
LP1 SUBTOTAL: 11
02/28/90 B344 148994
04/16/90 LPI CAT AREA 168468
04/20/90 BLOCK 25 BLDG 444 149001
04/26/90 G5 REACTOR 168439
05/07/90 TOP OF G 1750 168493 REACTOR
06/20/90 E/W PIPE RATE WEST 171855 SIDE BLD 1
10/03/90 LFl REACTION 191798
CONDITION LARRY CA5DORPH
MNT
Asbestos gaskets laying on the ground.
CONDITION CRAIG STRAKOS
MNT
Found flex asbestos gasket left over from other job.
CONDITION LARKY CASDORFH
NIT
Found large number of asbestos gaskets stored in storage bldg 444.
CONDITION PAT DUNLAP
MNT
A 75 sb steam line that is insulated with asbestos insulation has the outer
covering missing and pieces of asbestos are falling off.
CONDITION DONNIE MAREK
NIT
Found three asbestos gaskets on top level. They were deteriorating.
CONDITION CHERYL ENGELS
LP1
1/2* steam supply lines for steam tracing are very rusty, leaking, insulated
with what may be asbestos and in one case (within reach) uninsulated.
CONDITION
BUI
The analyzer tubing servicing G-1750 has several spots of asbestos wrap
which are frayed and open to the atmosphere.
030788
LP1R SUBTOTAL: 7
08/16/90 CONTROL ROOM 170683
LF2 SUBTOTAL: 1
CONDITION CORN!LIU FANELLX
MNT
Whle cleaning out filing cabinet in control room, cum across an asbestos
gasket and a steel choker. Neither belongs in the control room.
03/19/90 SAT FENCE 155344
MX5C SUBTOTAL: 1
CONDITION
BfcR Abandoned 6" acetylene line no. 29 has exposed asbestos insulation. This line goes through the north fence and open ended. Exposed area is on south side of fence.
02/15/90 B140-1 159897
10/18/90 MEZ-1 185931
(M3 SUBTOTAL: 2
CONDITION CARL BOSXER
HID
Pound roll of asbestos sheeting materiel unwrapped.
CONDITION JOE DELGADO JR
HID
round a pile of asbestos bags on floor partially in walkway.
01/17/90 REPAIR SHOP 156389
CONDITION DARRYL LYNCH
MNT
Asbestos gasket was left on multi-port valve.
01/22/90 B148 162783
CONDITION
B&R
Pound valve from surlus with an asbestos gasket stuck to the outlet flange.
01/22/90 BAR HASH PAD 155183
CONDITION LOUIE KRAMER
MNT
Two sections of 4" pipe have asbestos gaskets stuck to flanges.
01/24/90 REPAIR SHOP 156423
CONDITION DARRYL LYNCH
MNT
Pump was sent to shop with asbestos gasket on the flange.
01/30/90 DOCK 162614
CONDITION SENE WILLIAMS
MNT
Asbestos gasket on the ground of loading area of dock.
02/09/90 504 S HAILRACK 162504
CONDITION LEE YAXUN
MNT
New and used asbestos gaskets on the ground and on the rail rack.
02/08/90 REPAIR SHOP 153004
CONDITION DARRYL LYNCH
MNT
#2 gs sent compressor cylinder in to have liner bored, asbestos gasket was
left on one of the flanges.
02/16/90 82 GAS 150876
CONDITION ROYAL MAREK
MNT
Pound 12 flanges where coolers have been permanently removed with asbestos
gaskets still on them.
03/02/90 122 BOILER 168501
CONDITION GEORGE HEINS JR
MNT
Pound asbestos gasket hanging on south end of boiler and mise.
ground;
trash on
03/02/90 S OP MAIHT. BLDG. 161245
CONDITION MIKE WARD
MNT
Asbestos waste storage area dirty.
03/02/90 H SICE AIR BLDG. 161240
CONDITION MIKE WARD
MNT
Asbestos gasket in asbestos trailer not in bag.
03/05/90 PROJECT CREW STORAGE CONDITION LOUIE KRAMER
MNT
155169 YARD
Several asbestos gaskets on the ground.
03/05/90 PROJECT CREW STORAGE CONDITION LOUIE KRAMER
MNT
155168
YARD
Asbestos gaskets in shutdown trailer.
03/15/90 REPAIR SHOP 153088
CONDITION RAYMOND KILL JR
MNT
Gasket was left on suction flange of pump. (Asbestos>
03/18/90 TANK 2963 155453
CONDITION
BfcR
Fab cloth on asbestos insualtion, ground level has deteriorated on 3 lines
030789
and valves exposing asbestos.
03/08/90 SALVAGE YARD 155460
INCIDENT
FRED BERGER
MOT
Contractor was raaoving traps from a surplus coluan, and tha strip gasket
atarial on tha traps looked lika it may ba asbastos.
03/29/90 B148 162185
CONDITION IRA FTLLMORE JR
MOT
Fickad up bar of asbastos gaskat natarial that had blown off a truck.
03/28/90 REPAIR SHOP 153178
CONDITION
DAVID DEOTLER
MOT
Asbastos packing was put in trash can naar hand wash araa.
ba put in can aarkad for asbastos disposal.
Asbastos is to
04/11/90 T 4 I KRAY TRAILER 148493
CONDITION BOB TESCH
MOT
Top of asbastos gaskat box has othar natarial storad.
04/20/90 BLD 140*2 SOOTH 162668
CONDITION
ANN THOMASON
MOT
Spara cooprasson on trailar was brought froai laydown yard for anargancy usa.
Gang box on trailar was opanad aftar arrival by T & I aachanic, loosa and
brokan asbastos gaskats wara insida.
04/26/90 STANDARDS ROOM 160301
CONDITION
OIARLIE JAHN JR
MOT
Transaction temp calibrator was sant to tha standards rooa for RM. A length
of theraocouple load wira was insida tha instruaent casa. Tha insulation
appeared to ba asbastos, a saaple was analysed and it tasted positive as
asbastos.
04/26/90 MEZZ AREA OF INST
160300
SHOP
CONDITION CHARLIE JAHN JR
MOT
Found roll of thermocouple lead wira containing asbastos insulation.
05/07/90 LP1 159768
CONDITION KEN DORRIES
MOT
Noticed asbastos insulation on tubing in pit by G 1750 reactor.
05/14/90 REPAIR SHOP 169262
CONDITION MIKE WARD
MOT
Asbastos storage cabinet is dirty.
06/01/90 INSTRUMENT SHOP 179221
CONDITION ROLAND VILLAFRANCA
MOT
While taking apart 2" jamesbury valve noticed that valve had asbastos
gaskats material still on valve.
06/14/90 REPAIR SHOP 180504
CONDITION MIKE WARD
MOT
Asbastos storage araa not cleaned.
07/03/90 12 OLEFINS COMP.
163694
BUILDING
CONDITION LOUIE XRAMER
MOT
20* asbastos gaskat hanging on Pag board in Mint,
bldg, no asbastos hasard sign.
araa 82 olefins coop,
07/03/90 LPPE I MAIOT. SHOP 163689
CONDITION LOUIE KRAMER
MOT
Asbestos waste disposal drum in naint. shop at Lppe I was uncovered.
07/05/90 NEST FIELD 173700
CONDITION DON HARKED
MOT
Found asbastos gaskat laying on road to barge docks.
07/03/90 GEU 163691
CONDITION LOUIE KRAMER
MOT
Turn up asbastos gaskat on grating at switching station in GEU.
07/03/90 82 OLEFINS COMP.
163694
BUILDING
CONDITION LOUIE KRAMER
MOT
20* asbastos gaskat hanging on Peg board in naint.
bldg, no asbastos haxard sign.
araa 82 olefins conp.
07/02/90 BUILDING 148 175847
CONDITION
JOSEPH DAILEY
MOT
Found asbastos gaskat in Northwest corner of building.
feat froa an asbastos can.
This was 20 to 25
07/02/90 85 HOT WATER PUMP 170438
CONDITION ERNEST GARCIA
MOT
This pump has exposed asbastos on piping.
07/02/90 85 COOLING WATER 170439 PUMP
CONDITION ERNEST GARCIA
MOT
This pump has piping with exposed asbastos.
07/11/90 VACUUM DEGASSING 170492
CONDITION ERNEST GARCIA
MOT
South vacuum degassing pump discharge pipe has insulation exposed.
asbestos.
Could ba
030790
08/02/90 MAXNT. 177317
LAYDCMf YARD CONDITION LOUIE KRAMER
MNT
Two 8" asbestos gaskets stuck to pip* flanges in ODU equipment storage area
in ant. laydown yard.
08/02/90 mt. LAYDCMf YARD 177309
CONDITION LOUIE KRAMER
MNT
Asbestos gaskets inside column skirt located in Oxide equipment storage area
in amt. laydown yard.
08/10/90 175703
BLDG. 163 HYEKOTEST STATION
CONDITION
ANN THOMASON
MNT
Needs clean up - beans used as catch all. Countertops piled up. face
shield on top of asbestos disposal can. Trash cans full. Red rags
scattered.
08/05/90 WELD SHOP 147809
CONDITION TOMflf TUCKER JR
MNT
Head sent to weld shop froa field with asbestos gaskets.
08/27/90 GEU 176429
CONDITION BB BROWNING
MNT
found 2 snail asbestos gaskets laying on the ground.
08/27/90 ODU 176434
CONDITION BB BROWNING
MNT
An asbestos was stuck to a flange on soae old pipe that had been removed
froa the unit.
09/05/90 OLEfIKS ftl 177329
CONDITION LOUIE KRAMER
MNT
Used asbestos gasket on pad in No. 1 Olefins.
09/14/90 BLDG. 148 STORAGE 177347 AREA
CONDITION LOUIE KRAMER
MNT
Used asbestos gasket on exposed flange on out of service s. S. piping in
storage area of building.
09/25/90 POLYPROPYLENE 177326
CONDITION LOUIE KRAMER $N blind fig. pickup.
MNT with asbestos gasket stick to it in back of maintenance
09/25/90 SCAFTOLD YARD 184420
INCIDENT
BLR Asbestos insulation truck. employees could fall out.
The benches in back of this truck are too high,
09/26/90 164 AREA 196270
CONDITION
BLR Deficiencies of asbestos deron trailer ----- 1) Soae oily substance bleeding through walls, ceilings, etc. 2) Walls and ceiling bulgeing out 3) Neg. air machine pulls dust through receptacles door 4) Door leaks whne it rains S) floors sweat under nat 6) Water runs out froa bottoa of walls
10/24/90 BUILDING 160 WEST 183251
47
CONDITION
BLR Chain link fence on the west side of bldg. 160 has been repeatedly bumped and pushed by pallets causing hte fence to separate froa the poles. This in turn pushes asbestos equipment away froa fence into the path of personal trying to enter van box.
02/08/90 GEU 157916
04/20/90 AMINES 164510
05/17/90 164554
05/30/90 164491
05/29/90 164474
06/04/90 N. SURT UNIT 164468
07/20/90 ODU ACETATE UNIT 164451
CONDITION JOEY MXTSCHERLING
MNT
Numerous asbestos gaskets on ground where old piping was removed.
CONDITION WALLY WILLIAMS
MNT
found asbestos gaskets on ground in amines.
CONDITION BB BROWNING
MNT
A half of an asbestos gasket was laying on the ground.
CONDITION BB BROWNING
MNT
Old asbestos gasket was on pipe flange laying in aetal lugger bin.
CONDITION BB BRCWNING
MNT
Lid that goes to the asbestos gasket container was left off the barrel.
CONDITION BUD DAVIS
MNT
Exposed asbestos gaskets on vessel stored North of surf unit.
CONDITION BB BROWNING
MNT
Picked up a 1 1/2" asbestos gasket laying on the ground.
030791
07/20/90 ODU 360 WEST 164450
CONDITION BB BROWNING
MNT
Picked up a 4" asbestos gasket by crude column.
07/30/90 HAUfTEKANCE/ODU 164446
CONDITION BB BROWNING
MNT
An asbestos gasket was laying on tho ground whoro piping had boon removed.
08/01/90 ROADWAY SOUTH OP 367 CONDITION BUD DAVIS
MNT
176447
2" 150# usod asbestos faskel lying in way.
08/01/90 ODU 176440
CONDITION DICK SCHNEIDER
KIT
Small asbostos gaskot was laying on tho ground.
09/05/90 GEU 176408
CONDITION DICK SCHNEIDER
KIT
Pound a 1 1/2" asbostos gaskot laying on tho pad.
10/02/90 ODU 177343
CONDITION LOUIE KRAMER
MNT
Asbostos gaskot stuck to flang of pump storod by oast road into ODU.
10/02/90 ODU 177344
CONDITION LOUIE KRAMER
KIT
Asbostos gaskots stuck to flangos on piping locatod by sido of oast road
into ODU.
09/27/90 WEST SIDE OP ODU 181516
INCIDENT
BAR
Thoro was some piping and tubing connoctod to column No. MK3- 701 that will bo removed fron tho unit whilo scaffold crow was working on column for asbostos crow, thoy noticod a pioco of pipo that had asbostos on it was noxt to tho coluan and had exposed insulation on it so thoy callod no.
10/03/90 360 NORTH 176475
CONDITION BUD DAVIS
MNT
Found 10" asbostos gaskot lying on ground.
10/02/90 PIPERACK 176483
11/07/90 UNIT 176396
CONDITION
B&R
Found asbostos gaskot in tho wobb of a boaa.
CONDITION BUD DAVIS
MNT
Pound half of asbostos gaskot lying undor hoat exchanger.
11/09/90 ODU 176395
CONDITION FELIX GARZA JR
MNT
An asbostos gaskot was stuck to a pipo flango.
12/09/90 ODU 194164
CONDITION CECIL SHAFER
MNT
Noticod MEA strippor hoad was insulatod with uncovorod asbostos.
Approxiaatoly 1/2 tho aroa of tho hoad was uncovorod.
20
01/23/90 EAST SIDE 155182 12/29/89 PIPE RACKS 148294
01/30/90 SETTLING BASINS 162430 01/31/90 #21 BOILER 117145 02/06/90 159741 02/09/90 306 162553
02/09/90 COOLING TOWERS 162525
CONDITION LOUIE KRAMER
MNT
Section of 2" SS pipo by tho road, has asbostos gaskots stuck to flango.
INCIDENT
CONST Tho BAR instrument department was hanging cable tray when a piece of fire protection was broken off tho existing cable tray, tho unit informed mo tho broken fire protector was made of asbostos. There wore no signs warning employee about asbostos in tho pipo rack.
CONDITION WILLETT NEILL
MNT
Asbestos gaskets in area.
CONDITION WILLETT NEILL
MNT
Asbestos gaskot on ground near vacuum tower.
CONDITION DAVID LUGO
KIT
Scrap copper tubing, asbestos, cardboard boxes on the ground.
CONDITION
LEE YAKLXN
MNT
Scrap metal dumpster conains half used can o NOver-Sees, 1 quart plastic
bottle of unknown liquid, bottles of Sherlock leak detoctor, asbostos
gaskets, paper and plastic trash, new bolts and U-bolts.
CONDITION LEE YAKLXN
MNT
Asbestos gaskot hanging on piping at #3 cold water pump.
fire extinguisher cabinet at open top tank.
Also, on top of
030792
02/09/90 11 GAS UNIT 102560
CONDITION LEE YAKLIN
MNT
Asbestos gaskets throughout unit, new and used on ground.
02/09/90 VD PIT PFO 162545
CONDITION LEE YAKLIN
MNT
Asbestos gaskets laying everywhere.
02/09/90 SEPERATIOKS MIT 162495 CABINET
CONDITION LEE YAKLIN
MNT
Asbestos gasket and asbestos packing in cabient has no warning label on
outside of cabient.
02/09/90 PFO DIKED AREA 162537
CONDITION LEE YAKLIN
MNT
New and used asbestos gasket inside diked area.
03/01/90 501N 162579
CONDITION LEE YAKLIN
MNT
Ordered 2 gaskets froe stores, then received one contained asbestos.
Sasket was not wrapped, nor had warning label.
03/14/90 SETTLING BASINS 162433
CONDITION WILLETT NEILL
MNT
Found asbestos gaskets in area.
03/19/90 162597
CONDITION JOHN SHANNON JR
MNT
Scrap asbestos gasket material left on table in SOI N. shop.
04/17/90 SETTLING BASINS 162436
CONDITION WILLETT NEILL
MIT
Found asbestos gasket laying on ground at IS basins.
04/17/90 TREATED WATER TANK 171927
CONDITION JOHN SHANNON JR
MNT
Asbestos gaskets on ground.
04/17/90 E BUTADIENE PUMP PIT CONDITION JOHN SHANNON JR
MNT
171943
11 GAS
Asbestos gaskt hanging on handrail.
04/17/90 S OF ANALYZER BLDG 171922
CONDITION JOHN SHANNON JR
MNT
Slip blind with asbestos gasket under pump.
04/18/90 84 COMP 171912
CONDITION RUDY RAMIREZ
MNT
Asbestos insulated line suction 114 compressor blowing asbestos to air.
04/24/90 SEPARATIONS 170399
CONDITION ERNEST GARCIA
MNT
Found asbestos gasket in domestic trash barrell.
05/11/90 ELECTRIC SHOP,
170383
B-501N
CONDITION HOSS NEILL
MNT
Found pieces of asbestos gasket in trash can.
07/02/90 PFO 170437
CONDITION ERNEST GARCIA
MNT
Found asbestos gaskets lying around PPO unit.
07/23/90 COOLING TOWERS 170465
CONDITION WILLETT NEILL
MNT
Found asbestos gaskets on ground at treated water storage tank.
07/19/90 SEPARATIONS - NORTH
170470
SIDE
CONDITION JERRY DELGADO
MNT
Found large amount of asbestos insulation on ground in front of bldg.
Asbestos fell through pipe rack to ground due to hard rain.
503.
08/17/90 WEST SIDE, B-400 183538 ANALYZER
CONDITION
ERNEST GARCIA
MNT
West side of Bldg. 400 has exposed asbestos on 3/S* SS tubing lilies/
Tubing appears to be out of service, but the asbestos insulation is exposed
and is on the verge of falling out of the pipe rack.
09/11/90 BUILDING 501 SHOP 183513
CONDITION BUTCH HODGES JR
MNT
Found asbestos gasket on work table.
09/12/90 500 N 183509
CONDITION
LEE YAKLIN
MNT
Gasket purchased on a field requisition. Gasket received was asbestos, not
wrapped and no warning. Gasket is supposed to be purchased from
Cooper-Bessemer only. No substitute. Could have been left over from an old
Corpus Christ! gasket contract.
09/14/90 *1 GAS 183502
CONDITION WILLETT NEILL
MNT
Found asbestos gaskets on ground.
10/02/90 FURNACE ANALYZER
183276
BUILDING
CONDITION ERNEST GARCIA
MNT
Noticed steam leak above lock boxes on west side of analyzer bldg,
roof. Leak appears to be piping insulated with asbestos.
on the
030793
10/31/80 PPO HIGH STRENGTH 192970 SEWER PUMP
12/10/90 12 OLEFINS 177350
0L2 SUBTOTAL: 31
CONDITION ERNEST GARCIA
MNT
2* piping located south of high strength savor pump has axposad asbastos
insulation. Tha insulation is falling off tha pip*.
CONDITION LOUIE KRAMER
WIT
Two 1 1/2* nav asbastos gaskats on storaga rack in bldg. 504
02/14/90 140065
CONDITION BUDDY PERKINS
MNT
Found usad flax asbastos gaskat in araa.
02/21/90 140061
CONDITION BUDDY PERKINS
WIT
Saall piacas of asbastos broka off cabla trays.
04/16/90 1ST 140044
CONDITION ERNEST GARCIA
WIT
Exposad insulation, lookad lika asbastos.
05/04/90 OXIDE LOADING HACK 163605
CONDITION LOUIE KRAMER
WIT
Usad asbastos gaskat on tha ground at oxida loading rack.
04/26/90 B1 HX 140471
CONDITION DEAN STRAIN
OXI
Loosa asbastos froa cabla tray on pad at aast sida of B1 haat exchanger.
05/17/90 140014
CONDITION JIM FLEEMAN
MNT
While housekeeping inspection found wire, debris, asbestos, etc. in area.
discarded
05/17/90 170132
CONDITION JAMES PORTER
OXI
During inspection, two large pieces of asbestos insulation was laying on the
ground.
07/11/90 OXIDE I 173697
CONDITION BUDDY PERKINS
MNT
Pound 2 asbestos gaskets laying on ground had been there for jl long time.
07/21/90 B--3 HEAT EXCHANGER 173077
CONDITION BRUCE WOODS
SHF
Noticed asbestos insulation open to atmosphere between sample stream boxes
*5 and <12 on the southwest end of B-3 heat exchanger.
10/09/90 OXIDE 173663
CONDITION BUDDY PERKINS
MNT
Found asbestos gasket that came down from pipe rack during the wind and
rain.
10/25/90 OXIDE i 170070
CONDITION BILL VINCENT
MNT
Asbestos gasket stuck to a pipe flange.
11/07/90 OXIDE ii 194096
CONDITION MARTY MARTINEZ
MNT
Fond asbestos insulation that fell off froa under cable tray.
11/15/90 OXIDE ii 194093
CONDITION MARTY MARTINEZ
MNT
Construction parsonnal knocked ovar SOM asbastos insulation whila working
in pip* rack.
11/15/90 OXIDE ii 170053
CONDITION
BILLY WALKER
WIT
I found savaral larga piacas of asbastos notarial in tha pips rack. Thasa
piacas wara brokan off tha bottoa of cabla trays. Also thara is fina
particlas blowing in tha wind.
11/15/90 OXIDE ii 100169
CONDITION
BSR Noticad asbastos barricada that-wasn't complata. situation, I noticad it had baan aaltad into.
Aftar chacking out tha
12/02/90 SOUTH SIDE SCRUBBER 147953 HATER PUMP
CONDITION
CONST Contractor was sant in to ramova asbastos froa cabla trays at night. Wa showad up tha naxt aoming whan job was said to ba coaplata. Asbastos was still laying in araa.
12/12/90 OXIDE UNIT 194000
CONDITION BUDDY PERKINS
MNT
Found asbastos gaskat on ground by mono column.
OXI SUBTOTAL: 17
030794
05/14/90 PFO DIKED AREA 170380
pro SUBTOTAL: 1
09/27/90 OL2 183834
PLE SUBTOTAL: 1
01/30/90 MAINT SHOP 161166
04/16/90 BUILDING 19 132736
06/01/90 MAiirr. shop
163726
POLYPROPYLENE
08/07/90 EAST OF ANALYZER
186950
BLDG.
12/02/90 ODU 194166
FPU SUBTOTAL: 5
01/16/90 NEAR PAINT SHOP 150808
06/05/90 CORNER 5TH fi F
163688
STREETS
ROAD SUBTOTAL: 2
04/25/90 SEMICON 132803
05/15/90 SEMICONS 132947
06/10/90 CARBON BLACK
132828
BUILDING SEKICON
SCO SUBTOTAL: 3
07/31/90 RACK 3 135930
11/29/90 INST. SHOP 163861
11/29/90 OXIDE 193982
11/29/90 W/S 193976
CONDITION LEE YAKLXN
MNT
Trash can on south aast comar with asbastos gask.ts.
CONDITION FAT PETRISKY JR
PLE
Insulation marked "danger asbastos* has tha cover tom away exposing
insulation.
CONDITION HIKE MAUD
MOT
Asbastos storage cabinet is dirty.
CONDITION ARMANDO GARCIA
MIT
Found six asbastos filled flax tuba gaskats in Betel lugger bin.
CONDITION LOUIE KRAMER
HOT
Asbestos gaskets stuck to spargers that are leaning against south outside
wall of poleprpylena aaint. shop.
CONDITION ANDREW VASQUEZ
MNT
Found abandoned line with asbastos insulation deteriorating, east of
analyser building.
CONDITION CURTIS MARTIN
MNT
Found asbastos gasket laying on ground.
CONDITION ANN THOMASON
MOT
Found asbastos gasket laying in roadway.
CONDITION LOUIE KRAMER
MNT
2' used asbestos gasket on the street comer of Sth and F streets.
CONDITION CECIL SHAFER
MNT
Renoved manway flange on carbon black transporter and found the gasket to be
asbastos impregnated material.
CONDITION
CECIL SHAFER
MNT
Opened tranporter at 5* blind flange, found gasket to be made from material
containing asbestos. Checked transporter on line 2 and 3 and found same
type of material.
CONDITION CECIL SHAFER
MNT
REMOVED 12 AND 13 CARBON BLACK TRANSPORTER MANWAYS AND FOUND THE GASKET TO
BE MADE OF ASBESTOS MATERIAL.
CONDITION
BAR
Found 3/4* pip south of rack 3 in ditch with asbestos insulation exposed and
loose asbestos in white rocks.
CONDITION CHARLES SAMEY
MNT
Valve came into shop for repair (TV 1853 D) with asbestos gasket on flange
surface.
CONDITION ROGER HOCHGRABER
MNT
Was ask to cut bolts on B.O.U. reactor, insulation dust was flying
everywhere. Found out next day tha insulation was asbestos.
CONDITION GLENN BEGO
MNT
Head brought to shop still had asbestos gaskets attached.
030795
SHOP SUBTOTAL: 4
01/12/90 BSfil 152265
SQA SUBTOTAL: 1
GRAND TOTAL: 16S
CONDITION JEROME JANAS
SQA
Asbestos board in us* in th* HP2 lab in us* as an apparent h*at insulation pad for th* tap* extruder axtrudate.
030796
* ON the JOB CIA SUtMARY
with kasbestost in the description 01/01/91 to 06/30/91
CHIT RET
DATE
LOCATION
TIPE
DESCRIPTION
03/23/91 N/S PIPE RACK S. OF CONDITION
CONST
169511 THE BLACK
While talking with By supervisor I observed a sub contract employee Moving
about in the pepe rack. He was wearing a half face respirator with purple
cartridges. He was not wearing any protective clothing or fall protective
equipment. There were approximately 12 to IS other employees stripping
asbestos with full protective gear and full body harnesses.
03/19/91 COGEN 198609
CONDITION
DIS
JOINED JOB IN PIPE RACK ALREADY IN PROGRESS. FOUND PIPE INSULATION
CONTAINING ASBESTOS, REMOVED BUT NOT ENCAPSULATED.
04/02/91 B-W PIPE RACK
173346
341-343 LP1
CONDITION JOHN BRADLEY
MPT
Noticed large steam line probably had Asbestos Insulation and it was worn
and exposed.
04/30/91 EAST/WEST PRECURSOR
195345
SOUTH 360
CONDITION FRED BERGER
MNT
Construction sandblaster was blasting pipe in piperack. Blast stream
accidently hit insulated lake knocking asbestos insulation off.
DIS SUBTOTAL: 4
02/07/91 321 NORTH 173186
CONDITION JOHN SIM*)NS
MNT
Someone unloaded asbestos pipe in unit.
*1177015-6.
Tag on pipe reads ( Tie in (A8 DRW.
02/12/91 HATER TREATING 173165
CONDITION ROBERT GOSSETT
MNT
Found asbestos insulation exposed on soda ash tank piping nad also some
insulation laying on ground.
03/17/91 EAST OF OXIDE 1 179979
CONDITION MIKE WARD
MNT
Person not wearing respirator in asbestos area.
04/17/91 *21 S 122 BOILER 179913
CONDITION MIKE WARD
MNT
Asbestos not picks up yet.
04/17/91 NORTHEAST OF BLDG.
173285
327
CONDITION GEORGE HEINS JR
MNT
Found two asbestos gaskets in lugger bin.
04/19/91 SOUTH OF BLDG. 500 194553
CONDITION AL HARTMAN
MNT
Found asbestos gasket on the ground.
04/25/91 199474
BLOCK 9, *3 GEN AREA AND B.324
CONDITION
RANDY MADDUX
MNT
After doing a visual inspection of the *2 gen., I exited by the North
stairwell near Bldg. 324, when-1 wes almost to grade level, I noticed that
I was inside an area barricaded with asbestos tape.
04/30/91 02 UNIT 168517
CONDITION GEORGE HEINS JR
MT
Found 21 asbestos gaskets in tool box in 02 unit.
ENS SUBTOTAL: 8
-
02/14/91 OOU WASTE WATER 194058 PUMPS
EVP SUBTOTAL: 1
CONDITION DON HARNED
MNT
Found two asbestos gaskets on ground at OOU waste water pump station.
04/16/91 NORTH OF G.E.U. 195046
CONDITION
MNT WENT TO PUT ASBESTOS IN RED TRAILER. IT HAD NOT BEEN LINED WITH POLY.
WHEN OPENING LID ON TRAILER FOUND THAT
030797
GEU SUBTOTAL: 1
04/16/91 EAST OF SHOP 179922
04/16/91 EAST OF SUB D 179921
HF2 SUBTOTAL: 2
CONDITION KIKE WARD
MIT
Gasket storage cabinat (containing som asbestos) not claan.
CONDITION KIKE WARD
HOT
Gaskat storaga cabinat - asbastos labal about to COM off.
01/02/91 BLDG. 341 HEZZAZINE CONDITION HIKE ADKINS
MIT
173339 AREA
Locatad piping thrown in scrap luggar with asbastos wrapping on it.
01/23/91 LP-1 173956
CONDITION MASK SCHROLLER
MOT
Found asbastos gaskat laying on railroad tracks in front of Bldg. 353.
02/12/91 0-1750 17(002
CONDITION VAN SHRADER
MOT
While correcting jobs on housekeeping inspection list I found two asbastos
gaskets hanging on a valve wheal on catalyst feeder level.
02/06/91 LF1 REACTOR G-5 200000
CONDITION CRAIG STRAKOS
MOT
Foudn asbastos gaskets laying on structure on reactor.
03/04/91 BLDG. 341 177364
CONDITION LOUIE KRAMER
HOT
Two 10" asbastos gaskets on floor in front of storaga cabinets by cage
locatad in bldg. 341.
03/04/91 BLDG. 341 177366
CONDITION LOUIE KRAMER
MOT
No asbastos labal on Mtal cabinat used to store asbastos gaskets on the
third level of bldg. (341.
03/04/91 BLDG. 341 177365
CONDITION LOUIE KRAMER
MOT
Approx. 24" asbastos gaskat hanging on a halve on nitrogen header 3rd level
of bldg. 341 by 1750 reactor.
04/09/91 2ND LEVEL WEST SIDE 17(075
CONDITION JOHN BRADLEY
MOT
Exposed asbestos looking West in pipe rack between RX- control room and 344
structure. 2 lines.
04/18/91 LF1 190756
CONDITION JOE ESTRADA
MIT
Noticed an asbestos gasket in trash can.
only.
Trash can was for regular trash
05/01/91 G-5000 178015
CONDITION JOE GONZALEZ JR
MOT
While cleaning around G-5000, found about 12, 30* asbestos gaskets.
05/14/91 GS REACTOR 205223
CONDITION MIKE ADKINS
MIT
Found asbestos gaskets that were not disposed of properly.
LF1 SUBTOTAL: 11
02/06/91 HOT COMPOUND - 4 199987
04/03/91 EAST OF HC-5 MIXER 173347
LP1F SUBTOTAL: 2
CONDITION JOE GONZALEZ JR
MIT
Found asbestos gasket on pad by HC-4.
CONDITION JOHN BRADLEY
MOT
Noticed condensate line had asbestos insulation. (I Think)
04/23/91 BLDG. 347 OLD LAB
199946
BLDG.
LP1LB SUBTOTAL: 1
CONDITION JOHN BRADLEY
MOT
Noticed pieces of asbestos in old furnace.
01/09/91 173331
WEST OF G-5000 PURGE GIN
CONDITION
VAN SHRADER
MOT
Found three large asbestos gaskets on floor East of the G-5000 purge bin.
Both rupture disk on this vessel were blown several weeks ago. It appears
personal on this job did not clean up after job was collate.
030798
01/33/91 REACTION CONTROL 173304 ROOM
02/05/91 BLOCK 12 REAR 1739S2 NITROGEN SIEVE
LF1R SUBTOTAL: 3
CONDITION DONNIE MARIK
MNT
I found six asbestos gaskets in operations/ shift fittors spar* parts
cabinet.
CONDITION JEFT DIETZEL
MNT
Reaoved a pressure regulator from a nitrogen line in order to work on the
regulator. I noticed that the flange gaskets used were asbestos.
05/29/91 STORES 208122
06/07/91 140-1 208127
MtD SUBTOTAL: 2
CONDITION CARL BOSIER
MID
round a sheet of asbestos gasket material left unwrapped.
CONDITION CARL BOSIER
MMD
Discovered a sheet of asbestos gasket material that was not wrapped.
01/16/91 GAS 2 SEPERATIONS 191808
02/05/91 320 WEST 147016
02/21/91 G.E.U 191815
02/22/91 #2 STEAM PLANT 191816
04/24/91 3 TURBO GENERATOR 168676
04/17/91 353 S SECOND FLOOR
195059
POLY F
05/10/91 GARAGE WORK BAY 195394
05/17/91 NORTH FIELD BARGE
191566
DOCKS
06/13/91 SALVAGE YARD 196399
06/17/91 PLANTWIDE 196390
MIT SUBTOTAL: 10
CONDITION
MNT STEAM PIPING TO THE BASE OF THE NUMBER ONE AND TWO C2H2 ABSORBER COLUMNS IS ENSULATED WITH, WHAT I SUSPECT IS ASBESTOS INSULATION. THE FABRIC COVER COVERING THIS INSULATION IS DAMAGED IN SEVERAL PLACES AT BOTH COLUMNS, LEAVING THIS INSULATION OPEN TO THE ATMOSPHERE.
CONDITION
MNT
PIPE LAYING BESIDE DUMPSTER HAS ASBESTOS ON IT.
ASBESTOS IS LAYING ON THE GROUND.
SOMEONE HAS MOVED IT AND
CONDITION
MNT
I FOUND A LARGE DIAMETER ASBESTOS GASKET IN THE UNIT TRASH BARREL.
CONDITION
MNT I WAS riELD MEASURING PIPING ON THE *21 IBO TANK FOR AN UP COMING SHUTDOWN. I ENCOUNTERED QUITE A BIT OF TUBING WITH ASBESTOS WRAP FOR INSULATION. THE COVERING OVER THE ASBESTOS WRAP IS NON EXISTANT IN MANY PLACES LEAVING THE ASBESTOS OPEN TO THE ATMOSPHERE.
CONDITION
CHARLIE ZIRKELBACK
MNT
Asbestos barrier tape exists on #3 Turbo Generator platform stairs on south
side but not on north side. Either tape should be removed on south side or
south should be taped off also.
CONDITION
MNT
WHILE REMOVING ASBESTOS TRANSITE FROM THE BUILDING I NOTICED TWO EMPLOYEES
ENTERING OUR BARRICADED AREA WITHOUT THE PROPER PROTECTIVE EQUIPMENT.
CONDITION DARWIN BROWNING
MNT
Lid missing from asbestos waste drum.
ACCIDENT
MNT WHILE WORKING INSIDE THE BASKET I LEANED OVER TO STRIP ASBESTOS INSULATION, THE STORAGE TANK HAD ACETIC ACID DUST BUILD UP, CAME IN CONTACT WITH DUST AND HAD A BURNING SENSATION.
CONDITION
ton DUMP HOPPER FROM BARGE DOCK MAINTENANCE HAS SMALL SPOOL PIECE STILL BOLTED UP AND BOTH OPEN END FLANGES HAS ASBESTOS GASKET ON THEM. ALSO ONE (1) ALUMINUM FLANGE HAS ASBESTOS GASKET ON IT.
CONDITION
MNT NEED TO PUT SOME KIND OF HANDRAIL ON BACK OF PAINT TRUCK WW969 AND ASBESTOS CREW TRUCK, STEPPING OFT TRUCK UNTO BUMPER WITH WET BOOTS OR MUD ON BUMPER COULD CAUSE YOU TO SLIP AND FALL CAUSING INJURY TO YOUR BODY.
01/09/91 BLDG. 367 194180
04/19/91 AMINES 184758
CONDITION BUD DAVIS
MNT
Two used asbestos gaskets lying on table in shop.
CONDITION WALLY WILLIAMS
MNT
A piece of 1/2" steam tracing pipe with asbestos insulation fell out of
030799
05/01/91 AMINES 174735
05/16/91 BTC COLI** 174731
06/17/91 OIDflCALS 360 NEST 174701
ODU SUBTOTAL: 5
structure to second level in amines.
CONDITION HALLY WILLIAMS
MNT
Asbestos insulation on floor in anions unit foil out of pipe rack.
CONDITION BARNEY CARROLL
MNT
Personnel working inside plastic enclosure with "Danger - Do Not Enter,
Asbestos Hazard* signs on entrance door.
CONDITION BB BROWNING
NET
Pound a part of a asbestos gasket laying on the ground.
10 03/28/91 OLEFINS I 188511
OL1 SUBTOTAL: 1
INCIDENT
NATHAN BEDEE
OL2
Without notifying unit personnel or obtaining required HWP, naintenance crew
of Oxide assessment team entered HWP area of Olefins I to renove pieces of
ORS column. This area had already been deemed unstable and off-limits to
all except asbestos crew. They entered area with potential ignition source
and began using jacks in piperack jeopardising safety of personnel. (HWP
High injury potential - violators maintenance)
02/10/91 REACTION WALKWAY
196203
SOUTH END
CONDITION
MNT
CONSTRUCTION WAS WORKING IN THE PIPE RACK AND KNOCKED SOME ASBESTOS OUT OF
THE RACK.
02/07/91 GAS II (NOl
193055
C2HZSTILL)
CONDITION
MNT
EXPOSED ASBESTOS ON 3/4" LINE RUNNING VERTICA ON THE NORTH SIDE OF NO.
C2H2 STILL.
1
02/07/91 AREA NORTH OF 13 168162 C.T.G.
CONDITION RED SUMS
ENS
Some person had put a piece of piping with a swant out and insulation on
piping is asbestos.
03/10/91 EAST OF 201 173014
CONDITION DAVID HOLDER
SHF
Asbestos trailer needs to be removed from unit and stored elsewhere.
bean in unit for several months.
Has
04/19/91 SEPARATIONS 194570
CONDITION
JERRY DELGADO
MNT
Found "asbestos" gaskets on ground.
sight and not put in proper place.
These gaskets were just left on job
04/19/91 501 NORTH 194572
CONDITION LEE YAKLIN
MNT
Found asbestos spiral wound gasket overlayed with grafoil tape in scrap
metal dumpster.
04/23/91 207535
815 COMPRESSOR BLDG. 500
CONDITION
JOHN SHANNON JR
MNT
Suction pipe has asbestos insulation. This has been identified and marked
previously. The problem lies in the cover, it is deteriorated and the
asbestos is exposed to the atmosphere.
04/23/91 COMPRESSOR BUILDING CONDITION BUTCH HODGES JR
MNT
207509
Found asbestos gasket on ground near compressor building.
03/27/91 INSTRUMENT AIR
207518
FILTERS S. 501
CONDITION WILLETT NEILL
MNT
Asbestos tubing wrap on tubin gat instrument air filters is unwrapped with
fibers exposed to air.
04/23/91 115 COMPRESSOR BLDG. 207535 500
CONDITION
JOHN SHANNON JR
MNT
Suction pipe has asbestos insulation. This has been identified and marked
previously. The problem lies in the cover, it is deteriorated and the
asbestos is exposed to the atmosphere.
03/18/91 SEPARATION AREA 207520
CONDITION WILLETT NEILL
MNT
Found asbestos gasket in lugger bin.
04/24/91 COMPRESSOR BUILDING CONDITION JW BLAND JR
MNT
207523
Found used asbestos gasket on work table in compressor building.
04/24/91 SETTLING BASIN
CONDITION JAVIER VILLARREAL
MNT
030800.
207538
05/16/91 SEPARATIONS 202854
06/20/91 SEPARATIONS UNIT 202770
01*2 SUBTOTAL: 15
found asbestos gasket on ground.
CONDITION LEE YAKLIN
WT
round asbestos gasket in domestic trash can.
CONDITION JERRY DELGADO
MNT
Found loose asbastos insulation on ground. Probably fall through piparack.
12/08/90 OXIDE II 184494
CONDITION
B&R
Observed three outside asbestos abatement workmen working in piperack
without being tied off. Violation of elevated work policy PSH-IV-6.
01/17/91 196073
12 PIPELINE PUMP STM PIPE
CONDITION
MNT TWO INSULATORS STRIPPED TWO 90 DEGREE ELBOWS WHEN THEY NOTICED ONE OP THE 90'S HAD ASBESTOS ON IT.
01/24/91 OXIDE I 194074
CONDITION BUDDY PERKINS
MNT
found asbestos gaskets on ladder rack that were left after shutdown.
02/08/91 SPOT 4 LUGGER BIN 132655
CONDITION
MIT
FOUND TUBING WITH ASBESTOS WRAPPING IN METAL LUGGER BIN.
02/11/91 12 GLYCOL 200621
CONDITION LILA FOSTER
SHF
Found loose asbastos hanging in piperack above FC aake pumps.
03/28/91 OXIDE BLOCK 199832
CONDITION JANICE SIMON CLARK
SAP
Saw person inside asbestos barricade without a respirator on.
04/27/91 REACTION 196741
CONDITION SYLVESTE MOSLEY JR
SHF
While touring unit, found some scaffold crew working around asbestos removal
operation.
04/25/91 PIPERACK SOUTH OF 195347 OXIDE I
CONDITION
FRED BERGER
MNT
Asbestos insulation was knocked out of overhead piperack and was on the
ground. One insulated line appearred to be severly damaged from being
stepped on.
04/25/91 SUBSTATION El AND E2 ACCIDENT 169643
CONST While performing electrical demolition activities at substation E-l and E-2 at Oxide II, six BtR Braun Const, electricians were possibly exposed to an unknown amount of asbestos fibers. The insulation was allowed to free fall to the ground and as it hit obstacles on the way down it formed a visible cloud of dust that drifted well outside of the barricade that was erected in an approximate twenty foot area at the base of the column.
04/30/91 MAIN NORTH/SOUTH 172115 UNIT PIPERACK
CONDITION
DEAN STRAIN
OXI
While checking on asbestos removal progress in unit discovered two workers
standing in middle of span of cable tray passing equipment from outside of
the cablet tray to the other. HWP states to avoid walking or climbing on
the cable tray. Standing on the tray will damage it or cuase it to break
resulting in the worker falling through the tray.
05/08/91 OXIDE II 196890
CONDITION
MIT
BAILS OF ASBESTOS WERE NOT PROPERLY BARRICADED.
05/24/91 OXIDE II STRIPPING
148118
STILL COL.
CONDITION
CONST Removed metal weather barrier from stripper still. Insulators put on job to remove metal misunderstood Gen. Foreman' s work detail about job and removed metal jacket leaving asbestos insulation exposed. We immediately called B&R Safety inspector and insulation superintendent, also a UCC operator involved.
06/18/91 STRIPPING STILL 206936
CONDITION
RUDY SOTO
SHF
While asbestos removal people were enclosing area around stripping still
with plastic, discovered vent valve with nitrogen venting inside enclosed
area.
0X1 SUBTOTAL: 13
01/03/91 3RD STREET
CONDITION BILL SPELLACY
PPU
030801
160367
01/21/91 BEHIND THE P-1 174544 ANALYZES BLDG.
04/11/91 KAINT. BLDG. 179942
04/18/91 P-1 187312
04/22/91 BLDG. 11 187250
05/16/91 BLDG. 101 161954
05/22/91 P-1 CONTROL ROOM 161926
06/07/91 P-1 CONTROL EAST
201023
DOOR
8
04/18/91 INSTRUMENT SHOP 195812
04/05/91 82 GAS 179524
04/20/91 INSTRUMENT SHOP 19S824
05/16/91 REPAIR SHOP 162961
SHOP SUBTOTAL: 4
GRAND TOTAL: 91
A 4' long section of pipo covorod with asbestos insulation laying in tha roadway.
CONDITION
JAKES MORGAN
SHF
While looking at linos in tha aast-vost pipa rack, I noticad a lino bahind
tha analyzer that appaars to ba out of service. The insulation was Barked
asbestos and the jacket on the end was off and the insulator appeared to ba
enabling. Along tha entire length tha insulation appears in siailar
condition.
CONDITION MIRE WARD
MNT
Open asbestos storage.
CONDITION CURTIS MARTIN
MNT
Found asbestos gasket on first landing of structure.
CONDITION ANDREW VASQUES
HIT
Disposnig asbestos gaskets in proper container found designated container
full of trash nixed with asbestos gaskats.
CONDITION BILL 5PELLACT
PPU
Approachined within a faw feet of asbestos reaoval work because tha job site
was not properly barricaded off.
CONDITION
BILL SPELLACY
PPU
A large piece of asbestos siding aaterial was found laying loose inside a
wall during wall repairs. No one recognized this naterial and it was pulled
out and laying on the control rooa floor.
CONDITION
MNT
Coming up the stairway noticad that the subcontractors asbestos barricade
was down on tha floor.
CONDITION LARRY KNEBEL
MNT
A valve cane in from the 02 unit with a gasket attached.
some asbestos fibers.
These gaskets have
CONDITION DARRYL LYNCH
MNT
While taking piping off of 113 Gas Turbine noticed that it had asbestos
gasket.
CONDITION JOE GARZA
MNT
Noticed gaskets on M/V flanges to be asbestos.
CONDITION RICHARD REYES
MNT
Gasket storage cabinet in repair shop has some durable gasket material.
Some repair shop personnel were told that his is asbestos free.
308o2
CUT REF
DUE
LOCATION
11/15/91 HYDRO METHANE 166903 COMPRESSOR
11/15/91 HYDRO-METHANE 16(103 COMPRESSOR
EHS SUBTOTAL: 2
ON the JOB CIA SIM4ARY with tAsbestost in the dascription
07/01/91 to 12/31/91
TYPE
DESCRIPTION
CONDITION AUGIE RIVERA JR
MNT
Noticad asbastos gaskets on top landing of compressor.
CONDITION AUGIE RIVERA JR
MNT
Noticad asbastos gaskats on top landing of conprassor.
10/08/91 TANK PARM 212094
GEU SUBTOTAL: 1
CONDITION JOEY MITSCHERLING
NR
Pound two asbastos gaskats on tha ground in tank fan.
08/05/91 HP2 211456
11/18/91 TANK VENT 135751
HP2 SUBTOTAL: 2
CONDITION
MNT
I HAS LOOKING OVER A JOB LOCATED AT THE CHEMICAL RAIL CAR LOADING RACK IN
HP-2 AND FOUND POUR ASBESTOS GASKETS LYING ON THE PAD.
CONDITION RICHARD REYES
MNT
Tank vant was sant in for routina naintananca and still had asbastos gaskat
attachad to it.
07/01/91 G-5000 REACTOR 208993
07/26/91 1750 REACTOR 206750 08/15/91 G-5 REACTOR 209017
LP1 SUBTOTAL: 3
CONDITION VAN SHRADER
MNT
I found four usad asbastos gaskats of assortad sisas on tha raactor catalyst
faadar laval.
CONDITION COLLIN WENDEL
MNT
Found asbastos gaskat laying on top of two drums.
CONDITION JAMES MEISCHEN
MNT
I put a safaty valva back on tha raactor. Whan I was picking up tha araa, I
found an asbastos gaskat laying on tha grating.
09/16/91 HOT COMPOUND 208971
LP1P SUBTOTAL: 1
CONDITION EDDIE MOYA
MNT
Found asbastos gaskats laying on tha ground and not in propar placa.
08/22/91 ISNTRUMENT SHOP 209664
LP1R SUBTOTAL: 1
CONDITION JEFF DIETZEL
MNT
I found a 2* asbastos gaskat in storaga cabinet inside of shop araa.
10/30/91 140-1 208166
MID SUBTOTAL: 1
CONDITION CARL ROSIER
MID
On my routina check of work araa I noticad that a roll of asbastos gaskat
material had bean removed from tha plastic bag.
07/19/91 2ND FLOOR UNDER ROOF CONDITION
MNT
192253
E. OF G--1
A PIECE OF ASBESTOS TRANSITS HANGING FROM ROOF TOP
07/24/91 BOILER 21-22
CONDITION
MIT
030803
196796
07/29/91 SIS 12 LDXDCMI IMS 171536
WHILE I WAS DEINSULATING SOKE ASBESTOS WRAPPING OFT A TUBING LINE AT BOILER 21-22, I FOUND A LEAK.
CONDITION
WT
THERE IS A GANG BOX IN THE IAYD0MN YARD THAT IS FULL OF ASBESTOS GASKETS. THEY NEED TO BE DISPOSED Or PROPERLY.
01/09/91 BLDG. 345 SILICA 171506 SHED
CONDITION
MNT
ASBESTOS CREW HAS CALLED TO BLDG. 345 SILICA SHED TO CLEAN UP TRANSITS THAT
WAS BROKEN OUT BY AN OUTSIDE CONTRACTOR.
01/19/91 14AUMAS WEST OP SRV 171513 MAZER PUMP
CONDITION
MNT
ASBESTOS INSULATION WAS KNOCKED OR FELL FROM THE PIPE RACK. INSULATION FITTING NEEDS TO BE REMOVED.
THE REMAINING
01/27/91 PAINT SHOP SANS 209450 BLAST BOOTH
CONDITION
MNT
Send blast booth recieved a flange that had asbastos gaskat rasidua left on
it.
09/05/91 BLDG. 164 209436
CONDITION
MIT
UCC PERSONNEL BROUGHT HEAD TO GET SANDBLASTED.
GASKET IN IT.
IT CONTAINED SOKE ASBESTOS
09/12/91 360 M. GASKET CKA 177510
CONDITION
MNT
WHILE DISPOSING OF ASBESTOS GASKETS OUT OF CAN AT O.D.U. I NOTICED THAT THE CAN ALSO CONTAINED *9 WIRE AND PIECES OF WOOD. THIS CAN IS CLEARLY MARKED "ASBESTOS GASKETS ONLY".
09/10/91 DECON TRAILER EAST 177654 OP PAINT SH
CONDITION
MNT WHILE WORKING AT THE ASBESTOS DECONTAMINATION TRAILER I NOTICED THAT THE PLYVTOOD BOARDS CURRENTLY BEING USED TO LEVEL THE TRAILER WERE ROTTED OUT CAUSING THE TRAILER TO SHIFT AND TILT.
09/19/91 GAS X 171537
CONDITION FRED BERGER
MNT
Crows foot connactor on water hose to asbastos dacon trailer did not have
safety pin.
09/24/91 OXIDE II 204574
CONDITION
MNT
ASBESTOS LAYING ON GROUND EAST SIDE OF IGT UNDER PIPE RACK.
09/30/91 HP-2 172495
CONDITION
MNT
NOTICED ASBESTOS WORKER NOT WEARING CUT PROOF GLOVES WORKING ON COOLER HEADS
REMOVING GASKETS.
09/26/91 MELD SHOP 177619
CONDITION
MNT
ASBESTOS CANS HAVE TRASH IN THEM.
10/07/91 HP-1 117349
10/01/91 2ND FLOOR POUT F
172534
EAST SIDE
CONDITION CURTIS MARTIN
MNT
Found asbestos gasket in unit.
CONDITION
ran
ASBESTOS GASKET CAN HAD PAPER TRASH INSIDE.
10/01/91 NORTH PIPE RACK ODU 209319
CONDITION
MNT
NOTICED ASBESTOS OlEW MEMBER OF OUTSIDE CONTRACTOR INSIDE BARRICADE TAPING
BAGS OF ASBESTOS WITH NO PROTECTIVE GLOVES
10/09/91 CORNER OF "G* AND
172530
2ND STREET
CONDITION
MNT
WHILE WALKING BACK TO BLDG. 521 Z NOTICED SOME INSULATION ON THE GROUND.
STOPPED TO LOOK AT IT AND FOUND IT TO BE ASBESTOS.
I
10/06/91 NORTH PIPE RACK ODU 209319
CONDITION
ran
NOTICED ASBESTOS CREW MEMBER OF OUTSIDE CONTRACTOR INSIDE BARRICADE TAPING BAGS OF ASBESTOS WITH NO PROTECTIVE GLOVES
10/21/91 NORTH FIELD TANX 217665 FARM
CONDITION
ran
HAS WORKING IN HIGH PIPE RACK, WHEN WE CAME DOWN I NOTICED A LARGE PIECE OF
ASBESTOS LAYING ON THE GROUND.
10/29/91 12 COOPER-BE5SD1ER 200511
CONDITION
RICHARD MARXS JR
M7T
While analyzing 12 cooper, notiec the exhaust manifold leaking through the
insulation batween 2L and 3L power cyliinders. Thera is small piaces of
insulation scattarad on the piping, catwalk, and on top of the heads.
Considering the age of this conprassor, the insulation could be asbastos.
030804
11/01/91 165 SANDBLAST 147330
CONDITION
MNT
WENT TO 165 TO PICK UP 6' PIPE. ON ONE Or THE FLANGES THESE WAS AN ASBESTOS
11/06/91 360 W. AMINES 212073
CONDITION BB BROWNING
MNT
Found a 4' asbestos gasket laying on tha ground.
11/05/91 INSIDE BLDG. 164 209552
CONDITION
MNT
REPAIR SHOP BROUGHT OVER DIRTY PUMP WITH ASBESTOS GASKET STILL ON.
BEEN PARTIALLY SCRAPED BUT NOT ALL THE WAY OFT.Z
IT HAD
11/14/91 BLD. 209501
164 PAINT SHOP
CONDITION
MNT INDIVIDUAL BROUGHT VALVES 6 PIPING TO SANDBLAST SHOP TO GET SANDBLASTED t PAINTED. UPON INSPECTION OF MATERIAL FOUND ASBESTOS GASKETS STILL OH PIPING 6 FLANGE.
11/26/91 CORNER OF SECOND 6 G CONDITION
MNT
213201 STREET
ASBESTOS INSULATION FOUND ON THE GROUND UNDER PIPE RACK.
MR SUBTOTAL: 25
09/03/91 ODU MAINTENANCE SHOP CONDITION LOUIE KRAMER
MNT
207862
Asbastos gasket scraps on work tabla ODU maintenance shop.
09/03/91 GEU MAINTENANCE WORK CONDITION LOUIE KRAMER
MNT
207864 AREA
Usad asbastos gaskat on pad in aaintananca work araa in GEU.
09/03/91 MR. WORK AREA AT 207865 GEU
CONDITION LOUIE KRAMER
MNT
Asbastos scraps on top of storaga cabinet GEu aaintananca work araa.
09/30/91 AMINES 212096
CONDITION WALLY WILLIAMS
MNT
Found 3 used asbestos gaskets on ground in Aaines Unit.
11/05/91 42 FLASH TANK 214691
CONDITION BILL WADE
MNT
While checking out instrunents on 42 flash tank, noticed we ware right above
asbestos reaoval work. Stairs were not barricaded off.
11/04/91 GROUND 212051
CONDITION FELIX GARZA JR
MNT
Found asbastos gasket laying on the ground.
ODU SUBTOTAL: 6
08/20/91 415 OIL COOLERS 202703
08/20/91 EAST OF SLUDGE PIT 202706
08/20/91 SEPARATIONS
202704
(SOUTHEND)
08/29/91 SOUTH OF HIGH
202716
STRENGTH SEWER
09/05/91 SEPARATION AREA 194617
09/26/91 500 N. 202822
OL2 SUBTOTAL: 6
CONDITION LEE YAKLIN
MNT
Found asbestos gaskat froa oil cooler job in doaestic trash can.
CONDITION ERNEST GARCIA
MNT
Noticed 1 1/2' stub-end coning out of 475 staan header has exposed asbastos
insulation.
CONDITION LEE YAKLIN
MNT
Four asbastos gaskets in doaestic trash can near construction job site.
CONDITION ERNEST GARCIA
MNT
Just south of high strength sever of PFO, there is a 2* pipe with exposed
asbastos insulation.
CONDITION JERRY ROBINSON
SHF
Found asbastos reaoval barricade tied through valve wheal. If tha valve had
bean needed quickly tha barricade nay have bean dropped and not replaced.
CONDITION
LEE YAKLIN
MNT
Transite siding being removed froa Bldg. 500, North wind blowing, area on
north side barricaded off about 50 ft. froa N. wall. Inside of bldg,
only about 4 ft barricaded on south side of wall. Every tiae a piece of
material was reaoved, dust and/or asbestos would blow into bldg, for about
50 to 60 feet.
08/01/91 WEST SIDE OF OXIDE CONDITION
MNT
030805
177586
vent scwj.
08/08/91 B-3 HEAT EXCHANGER 209906
09/13/91 5TH EVAPORATOR 190101
10/03/91 OXIDE II--PIPE RACK 204528
10/03/91 OXIDE 204530
10/02/91 OXIDE II 204600
OKI SUBTOTAL: 6
while working at oxide ii unit i pound some friable asbestos insulation
LAYING ON THE GROUND IN THE WALKWAY. SOMEONE HAD APPARENTLY KNOCKED IT DOWN WHILE CRAWLING IN THE PIPE RAOU
CONDITION JEFFREY NEWTON
MNT
Outsid* contractors cutting asbastos insulation ara laaving sharp jaggad
adgas on natal waathar proofing. Asbastos saaling agant appaars to bo
inadaquata bacausa thara ara loos* insulation fibars in inspaction parts.
CONDITION FRANKIE DROZD JR
HOT
Found asbastos gaskat lying on ground naxt to 5th avaporator.
CONDITION BILL VINCENT
MOT
Found a 4* asbastos flax gaskat laying in a cabla tray in tha pipa rack.
CONDITION BUDDY PERKINS
HOT
Whl* claaning up, aftar raplacing pipa, found asbastos gaskat on ground
vhara soaaona had laid it aftar raaoving pipa.
CONDITION
DARRYL LYNOi
MOT
Asbastos raaoval craw was stripping insulation fron piping running undar
IGT. Thay had tha araa baracadad off, but whan thay wara finishad thay
forgot to taka part of tha barracada down.
12/03/91 FIFTH STREET a 0
148101
STREET CORNER
12/11/91 PLANT ROAD 217744
ROAD SUBTOTAL: 2
INCIDENT
CONST I was driving aast on Fifth Straat. Whan I casta up to D Straat intarsaction I had to stop bacausa Sarvic* Abataaant whit* pickup pulling a trailar loadad with asbastos failad to oak* a stop at tha intarsaction.
CONDITION MIKE WARD
MNT
Asbastos workar riding in back of pickup with baggad asbastos.
07/09/91 DOOR 19 NORTH REPAIR CONDITION JOE EWALD
WIT
184022
SHOP
Two pumps arrivad in door I9N with asbastos gaskat not ranoved.
09/10/91 DOOR 9 SOUTH 193046
. CONDITION RAYMOND HILL JR
MOT
Found asbastos gaskat on suction flang* of pump.
SHOP SUBTOTAL: 2
GRAND TOTAL: 58
030806
I
CUT BET
DATE
LOCATION
09/20/92 ODU 17(543
CNfT SUBTOTAL: 1
ON the JOB CIA SUW1AKY with tAsbestos in the description
01/01/92 to 12/31/92
TYPE
DESCRIPTION
CONDITION
FRED BERGER
MNT
Contractor called to infora that one area of the aoaonia still had a
different type of insulation than the rest of it and suspected it to be
asbestos.
* 09/10/92 BLDG. 347 1709(4
CONST SUBTOTAL: 1
INCIDENT
CONST Asbestos insulation renoved froa pipe in Bldg. protection and asbestos procedures.
347 without proper personnel
01/15/92 IN RACK N. OP 3(1 217435 BUILDING
01/17/92 3(1 SOUTH 217434 02/11/92 3(0 LUGGER 217999
0(/2(/92 BARGE DOCKS 158990
09/30/92 TANK 602 144238
DIS SUBTOTAL: 5
CONDITION
DIS
WHILE WORKING IN PIPE RACK NORTH OF BLDG.
LAYING IN THE WEBB OF AN I-BEAM.
381 I |FOUND TWO ASBESTOS GASKETS
CONDITION
DIS
NOTICED LID OF ASBESTOS GASKET TRASH CAN KISSING.
CONDITION
DIS
SIFTING THRU FULL METAL LUGGER, FOUND DISCARDED SPOOL PIECE WITH ASBESTOS
GASKET STILL ATTACHED.
CONDITION JANICE SIMON CLARK
DIS
Noticed that the asbestos warning labels on the acetic acid line at the dock
front did not contain the proper wording.
CONDITION JANICE SIMON CLARK
DIS
On the west side of tank 602 there is a 20-30 foot piece of pipe wrapped in
plastic. Pipe has asbestos labels on it which are extreaely faded.
02/05/92 GAS II 812 TURBINE 169477 DUCT
05/04/92 PIPING 148044
ENS SUBTOTAL: 2
CONDITION
CONST Shop order rush job to trip and reinsulate a section of duct. Checked with unit person, received walk thru, started to reaove insulation which was aineral wood as we neared coapletion at bottoa, ant. showed up stopped the job because there Bight be asbestos.
CONDITION
CONST Old 3/4' line running up the coluan has collapsed and both line and insulation are laying on top landing and second froa top landing insulation is suspected asbestos.
02/07/92 GEU UNIT 1260(2
GEU SUBTOTAL: 1
CONDITION JOEY MITSCKERLING
MNT
While picking up trash in unit for a unit cleanup, found asbestos gasket on
ground.
01/28/92 LP1 ACTIVATION 215551
CONDITION
CRAIG STRAKOS
MNT
Found two asbestos and one flex gasket in a flange on the condensate line to
g-5 activator bottoa line when 1 removed for Ttl.
02/05/92 TRUCK UNLOADING RACK CONDITION STEPH STEPHENS
SHF
030807
226263
09/15/92 OLD ERYER LEVEL 262531 10/06/92 BLOCK 25 230461 LP1 SUBTOTAL: 4
According to OP's, vendors for teal trucks ara supposed to supply graphite/asbestos gaskets for hook-ups to our unloading lines. The gaskets with this shipment were not this type. Teal unloading was delayed for approximately 11/2 hours.
CONDITION EDDIE M3YA
MNT
Found two 3' 1501 asbestos gaskets laying on floor.
CONDITION
MNT
FOUND AN ASBESTOS GASKET IN THE METAL BIN
11/10/92 BASEMENT BUILDING
150220
101
LP1F SUBTOTAL: 1
INCIDENT
WAYNE HC CUTCHEON
LP1
Reaoving insulation froa condensate line to find leak. Where insulation was
to be reaoved was an asbestos free label. Red arrows were also pointing
away froa this spot. As insulation was being reaoved it was noticed to be
asbestos.
09/10/92 BLDG. 347 LF-1 LAB 178542
CONDITION FRED BERGER
MNT
Deaolition contractor working on Bldg. 347 started to reaove an insulated
line that contained asbestos insulation.
LP1LB SUBTOTAL: 1
02/25/92 G-S REACTOR 215554
03/05/92 G-1750 223179
LP1R SUBTOTAL: 2
CONDITION JAMES KEISCHEN
WC
Found asbestos gasket hanging on valve handle.
CONDITION RANDY STERNADEL
SHF
I found resin trash bags in asbestos trash can.
01/10/92 EAST BLDG. 501 220906
CONDITION JERRY DELGADO
MNT
Found tubing wrapped with asbestos insulation in lugger bin.
01/15/92 BLDG 101 S. 187347
CONDITION RAMIRO TORRES
MNT
Found an asbestos gasket on driveway at bldg. 101 s.
01/11/92 NORTH SIDE ON 380 213115
CONDITION
MNT
ASBESTOS TRASH CAN NEEDS A LID ON IT. WHEN IT RAINS, WATER COLLECTS AND
MAKES THE BAGS HEAVIER. COULD POSSIBLE CREATE A BACK INJURY.
01/15/92 GAS II SEPARATIONS 218937
CONDITION
MNT WAS WALKING TO MY TOOL BOX AND NOTICED SOME INSULATION LYING ON THE GROUND. I WENT TO PICK UP THE MESS AND NOTICING IT WAS POSSIBLE ASBESTOS. I THEN NOTIFIED AN OPEATOR, BARRICADED THE AREA OFF AND CALLED THE ASBESTOS CREW. IT TURNED OUT BEING ASBESTOS.
01/14/92 822 BOILER 225951
CONDITION
MNT
........
NOTICED A RUSTED LINE THAT HAS BROKEN AND FALLEN INTO A CABLE TRAY WITH WIRE
IN IT. THIS LINE HAS WHAT APPEARS TO BE ASBESTOS INSULATION ON IT.
01/11/92 343 NORTH 213104
CONDITION
MNT
THE METAL LUGGER BIN THAT IS ON THE NORTH SIDE OF THE CONTROL ROOM HAD SOME
TUBING IN IT. THE TUBING WAS STILL INSULATED WITH ASBESTOS TAPE.
01/13/92 342-N 109265
CONDITION FRENQUE CORKIER
MNT
I noticed the lid to an asbestos container was on the gorund next to the
container.
01/24/92 W.SIDE OF UNIT UNDER CONDITION
MNT
213079
FANS
I FOUND AN ASBESTOS GASKET LAYING ON THE WHITE ROCK UNDER THE FIN FANS.
01/22/92 P,F,0 213075
CONDITION
MNT
THERE IS ASBESTOS ON GROUND AND A SMALL BOX CONTAINING ASBESTOS IS BROKE
OPEN AND LYING ON PIPE AND GROUND.
030808
01/24/92 MEZZANINE--GROUND
215570
LEVEL
CONDITION PAT DUNLAP
MNT
Pound two asbestos gaskets on floor.
01/23/92 HE CORNER GEU 190183
CONDITION FRANKIE DROZD JR
MIT
Found asbestos gasket lying on ground.
01/21/92 ENERGY SYSTEM 213177
CONDITION
MNT
FOUND LOOSE ASBESTOS ON GROUND CAUSED BY CONSTRUCTION ELECTRICIANS STEPPING
ON PIPE
01/22/92 RACE GOING NORTH AND CONDITION
MNT
225939 SOUTH
NOTICED WHEN INSPECTING JOB IN OXIDE-II WHEN I NOTICED SOME LOOSE ASBESTOS.
01/21/92 BEHIND NO. 4 215906 SETTLING BASIN
CONDITION
MNT
A 9" VALVE WITH ASBESTOS INSULATION NEEDS TO BE REPAIRED OR REMOVED.
01/27/92 COGEN 225073
CONDITION
MNT
I WAS GOING TO USE THE UNIT STEAM CLEANER TO WASH SOME PIMP BASES WHEN I
NOTICED THE INSULATING WRAP ON THE LANES WAS THE OLD ASBESTOS WRAPPING.
01/30/92 S. SIDE OP PAD BY 213090 STINKY DITCH
CONDITION
MIT
FOUND ASBESTOS GASKETS THROWN ON GROUND BY STINKY DITCH NEXT TO 304 WASHPAD
01/28/92 NEST BAY HELD SHOP 206819
CONDITION
MNT
A CONDENSER HEAD FROM OXIDE II REQUIRED WELD REMOVAL ON INSIDE OF A FLANGE,
BUT IT STILL HAD AN ATTAOIED GASKET THAT WAS IDENTIFIED AS ASBESTOS
01/27/92 LAYDCMI 225056
CONDITION
MNT
WENT TO THE LAYDCMN YARD TO TAKE APART A BALL VALVE FROM A SPOOL PIECE WHEN
I NOTICED THAT THE FLANGE HAD AN ASBESTOS GASKET.
02/06/92 LPPE-1 215573
CONDITION
DONNIE MAREK
MNT
I found all sorts of trash in asbastos only cans. 'asbestos only."
Thesa cans ara labalad
01/30/92 OLEFINS 500--N 218019
CONDITION LEE YAKLIN
MNT
Found spiral wound asbastos gaskat in natal dunpstar.
coma apart.
It had coaplataly
02/04/92 OLD DRYER LEVEL 215572
CONDITION EDDIE MOYA
MNT
whan on unit claan up, found two asbastos gaskats on tha old dryar Laval
floor.
02/06/92 LPPE-1 215573
CONDITION
DONNIE MAREK
MNT
I found all sorts of trash in asbastos only cans.
'asbestos only."
Thasa cans ara labalad
02/05/92 SOUTH SIDE WALKWAY 218008 Or SEPARA.
CONDITION
MNT
THERE WAS SOME ASBESTOS INSULATION ON THE SOUTH SIDE WALKWAY OF SEPARATIONS
02/04/92 BLDG. 164 PAINT
191658
SHOP
CONDITION
MNT NOTICE 4* SPOOL OIECE WITH 2" NOZZLE LOCATED AT PAINT SHOP WITH ASBESTOS GASKET STILL INTACT ON 2' NOZZLES.
02/10/92 343 NORTH 224071
CONDITION
MNT
FOUND AN ASBESTOS GASKET CAN WITH REGULAR TRASH IN IT.
02/06/92 500 N. 207582
CONDITION LEE YAKLIN
MNT
Found three asbastos spiral wound gaskats in scrap natal dunpstar at 500 N.
Appeared to have cone fron cooler job on tha 82 coup.
02/12/92 AMINES 217859
CONDITION
MNT
I FOUND KNOCKED OFF PIECES OF ASBESTOS ON FLOOR IN FRONT OF CONTROL ROOM.
02/20/92 HP2 223752
CONDITION CECIL SHAFER
MNT
Found broken asbastos gaskat on tha ground south of Building 560.
02/27/92 WATER TREATING 168964
CONDITION ROBERT GOSSETT
MNT
Exposed asbastos insulation on stean piping above 81 cooling water pump is
blowing into atnosphare.
02/28/92 RACK WEST OF BLDG.
224151
327 ON GRND
CONDITION
MNT
ASBESTOS ON THE GROUND.
030809
03/04/92 MEST SIDE 224172
CONDITION
MNP
ASBESTOS CANS HAD MISC. TRASH
03/04/92 SCREEN PAR BURNER 224173
CONDITION
WFT
ASBESTOS CANS HAD MISC. TRASH
03/04/92 SHOP AREA
224175
CONDITION
MNT
ASBESTOS CANS HAD MISC. TRASH
03/11/92 BREEZENAX SOUTH END 224184 GAS II
CONDITION
MNT AS I WAS WALKING IN SEPARATION I NOTICED SOME INSULATION ON THE FLOOR. AS I TOOK A CLOSER LOOK, I NOTICED IT WAS ASBESTOS INSULATION THAT HAD FALLEN FROM THE PIPE RACK ABOVE.
03/11/92 ACROSS FROM 501-N 224185
CONDITION
MNT
I NOTICED INSULATION ON THE GROUND WAS ASBESTOS
04/01/92 140 S. BY ROADWAY 224046
03/05/92 1 SYSTQDt SUCTION
230879
BLOWER
03/31/92 82 GAS 224040
CONDITION
MNT
POUND AN ASBESTOS GASKET LAYING NEXT TO ROAD
CONDITION
ravT
I FOUND A PART OF AN ASBESTOS GASKET IN BLOWER CELL.
CONDITION
nvr
I HAD ENTERED INTO SEPARATIONS PART OF THE UNIT AND HAD NOTICED ASBESTOS INSULATION ON THE GROUND. THE PIPERACK DIRECTLY ABOVE HAS ASBESTOS HANGING OFF THE PIPES AND IS IN A VERY BAD CONDITION.
04/07/92 503 SEPARATION AREA CONDITION
MNT
230905
I FOUND AN ASBESTOS GASKET ON TOP OF A 55 GAL. DRUM
04/13/92 WEST END OF
226917
EAST-WEST WALK
CONDITION
MNT
WE WERE CALLED TO GAS 1 TO CLEAN UP A SMALL ASBESTOS SPILL ON CONCRETE
WALKWAY.
04/14/92 E. END OF E6W 224250 WALKWAY
CONDITION
MNT
FOUND ASBESTOS GASKETS ON GROUND
04/08/92 SOUTH SIDE OF
226648
SEPARATIONS
CONDITION
MNT
AS I WAS WALKING TO MY JOB SITE, I NOTICED SOME INSULATION ON THE FLOOR.
STOPPED TO GET A BETTER LOOK AT IT, AND I FOUND IT TO BE ASBESTOS.
I
04/08/92 EAST SIDE
226817
SEPARATIONS
CONDITION
MNT
FOUND ASBESTOS ON THE FLOOR AT GAS II SEPARATIONS.
04/08/92 SOUTH END 226816
CONDITION
MNT
ASBESTOS FOUND IN PIPE RACK IN GAS 2 SEPARATIONS
04/13/92 211470
86 PROPANE CONDENSER
CONDITION
MNT THE TUBE BUNDLE WAS REMOVED FROM #6 PROPANE CONDENSER. THE ASBESTOS GASKETS WERE NOT REMOVED FROM THE CHANNEL, CONDENSER SHELL OR ASSOCIATED PIPING. THERE ARE LARGE ASBESTOS GASKETS STILL STUCK TO THESE SURFACES.
04/16/92 SOUTH OF ANALYZER 231251 BLDG.
CONDITION
MIT
ASBESTOS INSULATION IN THE WALKWAY
04/13/92 211470
86 PROPANE CONDENSER
CONDITION
WIT THE TUBE BUNDLE HAS REMOVED FROM #6 PROPANE CONDENSER. THE ASBESTOS GASKETS WERE NOT REMOVED FROM THE CHANNEL, CONDENSER SHELL OR ASSOCIATED PIPING. THERE ARE LARGE ASBESTOS GASKETS STILL STUCK TO THESE SURFACES.
04/29/92 COMPRESSOR BUILDING 231265
CONDITION JW BLAND JR
MNT
Found used asbestos gasket on work tablo in compressor bldg.
05/01/92 BLDG. 11 SHOP AREA CONDITION ARMANDO GARCIA
MNT
187021
Bag in asbestos container missing.
05/04/92 OLD SCAFFOLD YARD 226005
CONDITION
WIT
BARRICADE AROUND ASBESTOS WAITING TO BE REMOVED WAS FALLING DOWN.
05/16/92 FURNACE AREA 231205
CONDITION
MNT
THE ROOF OVER KIDDLE AISLE BETWEEN FURNACES ON THE NORTH AND SOUTH SIDE HAS
LEAKS. THESE LEAKS BRING CHUNKS OF ASBESTOS DOWN WITH THE RAIN WATER.
030810
05/28/92 12 GAS SEPERATIONS 209919
05/21/92 PIPE RACK 209918
05/29/92 82 GAS SEP. 2ND
190244
LEVEL
05/26/92 BARGE DOCKS 219439
08/25/92 ODU 232985
08/31/92 EAST OF OLD HATER
230441
LAB
08/31/92 EAST OF OLD WATER
230440
LAB
09/15/92 900 SILOS 242506
09/10/92 341--N 229940
09/21/92 ODU 226016
11/04/92 BLDG. 1600 209915
11/18/92 GARAGE 185714
HIT SUBTOTAL: 63
CONDITION
VIVIAN SPRAGUE
HIT
Was looking at coluans w/Marty, Ricky, a Rothnan for inspection. Wa cane
upon insulation scattered in walkway of unit. Asked Marty if it was
asbestos. He verified it was. He called his people to rope off and clean
up. This insulation was in this area because the covering and insulation
has deteriorated and is just falling out in this unit.
CONDITION
VIVIAN SPRAGUE
MKT
Rossler inspectors noticed insulation (asbestos) torn and tattered in the
pipe rack on the south side of Oxide I and II and west side of energy
systems.
CONDITION TED SEVIER
HIT
There are several junction boxes along walkway with exposed asbestos.
CONDITION
MNT ASBESTOS CREW WAS WORKING SOUTH EAST CORNER OP THE BAYOU PUMP HOUSE WHEN 14 COMPRESSOR HAD AN OIL LINE RUPTURE, CAUSING AN OIL SPILL. APPROXIMATELY 2-1/2 GALLONS HAS SPILLED ON THE GROUND.
CONDITION
MNT
POUND ASBESTOS WRAPPING ON SS TUBING IN SCRAP METAL BIN.
CONDITION
MNT
WHILE BEHOVING ASBESTOS, NOTICED A CONSTRUCTION ELECTRICIAN WALKING OVER US
IN THE PIPE RACK.
CONDITION
MNT
CONSTRUCTION RIGGER CROSSED ASBESTOS BARRICADE.
CONDITION JOE GONZALEZ JR
MNT
While opening silos on top of bin 901-902, found two asbestos gasket.
CONDITION
MNT I WAS SENT TO 341-N TO PICK UP A VALVE. THIS VALVE HAD ASBESTOS GASKETS LAYING ON CART AND SMALL AMOUNT ON VALVE.
CONDITION
MNT I NOTICED A PIPE IN THE PIPE RACK THAT WAS INSULATED WITH ASBESTOS. SOMEONE HAD STRIPPED THIS SAME ASBESTOS OUT Or THE WAY TO RUN ANOTHER PIPE NEXT TO THIS LINE. IT APPEARS THAT THIS INSULATION NEEDS TO BE ENCAPSULATED.
CONDITION
VIVIAN SPRAGUE
MNT
Buske with BAR showed aw some of the asbestos bags and how they cone apart
in damp weather. These bags are app. $5 ea. Maybe we should look for
another vendor or supplier with better-nade bags. At $5 ea. thera is no
telling how many are thrown away not useful every year.
CONDITION
PHIL SCHMIDT
MNT
While cleaning out the box where we keep old starters, and altenators, I
found two sets of broke shoes that had been placed in the box for disposal.
The shoes contained asbestos.
05/11/92 MACHINE SHOP 190607
MSHOF SUBTOTAL: 1
CONDITION EDDIE BALFANZ
MIT
While cleaning up around balancing aachine, found a piece of asbestos.
02/14/92 UNIT TANKS 224453
02/25/92 ODU SURFACTANTS 224149
03/26/92 ODU 224495 10/20/92 NEST OF ODU PIPE
CONDITION JOEY MITSOVERLING
MNT
While naking our Friday aoming cleanup in unit, found an asbestos gasket on
ground by unit tanks.
CONDITION
MNT FOUND A LINE OF ASBESTOS WITH SOME PLASTIC SECURING THE ENDS AS TO ENCAPSULATE.
CONDITION BB BROWNING
MNT
An asbestos gasket was laying on the pad.
CONDITION
MNT
030811
230492 OOU SUBTOTAL: 4
KMX
WEN WORKING AT THE PIPE RACK I FOUND A GASKET THAT HAS ASBESTOS.
02/14/92 E. SIDE 11 OLEFINS 204477
CONDITION LOUIE KRAMER
KWT
Fount 1 1/2* used asbestos gasket on pad a. sida II Olefins.
OU SUBTOTAL: 1
07/07/92 OLEFINS 11 205153
11/10/92 GAS 2 SEPARATIONS 232995
11/23/92 GAS 2 SEPARATIONS 172457 OL2 SUBTOTAL: 3
CONDITION RANIER BRIGHAM
MNT
Found asbestos insulation on 1 1/2 or 2' conduit lina on aast sida of
compressor bldg, basida cross ovar; insulation has savaral cracks in it.
CONDITION
MNT
WILE WORKING AT GAS 2, I NOTICED SOME ASBESTOS INSULATION LAYING ON TOP Or
BLDG. 504.
CONDITION
MT
SAW SOME ASBESTOS LAYING ON THE CEMENT FROM A FLANGE ABOVE.
05/22/92 OXI 222524
CONDITION
TIMOTHY JANCA
MIT
While anptying trash cans in Oxide unit, I again discovered significant
amounts of natal scrap, including t9 vira, insulation jacketing,
asbestos-wrapped tubing, etc.
06/04/92 OXIDE 145453
CONDITION CRAIG STRAKOS
MNT
Found asbestos gasket in regular trash can.
06/10/92 OXIDE 222543
CONDITION BUDDY PERKINS
MNT
Found part of asbestos gasket on roadway.
06/29/92 169493
SOUTH WEST CORNER OF OXIDE I
CONDITION
CONST At the south west corner of Oxide I some insulation which probably fell from rack was gathered up and left lying on the grond next to beam with no barricade or signs around it. Exposed insulation was not bagged or labeled. Insulation looks like possible asbestos.
04/24/92 BLDG. 221 214054
CONDITION BILL VINCENT
MNT
Found a asbestos flax gasket that was not completely covered, exposing some
asbestos.
09/15/92 SOUTHSIDE BLOCK 4 143776
CONDITION JULIA SMITH
PLE
Saw insulation that I suspected was asbestos. The material was flaking off.
10/24/92 OXIDE II 227079
CONDITION
MNT
WILE WORXING IN OXIDE, CAME ACROSS ASBESTOS GASKET ON GROUND.
OKI SUBTOTAL: 7
05/01/92 P-1 PELLETING AREA 147016
PPU SUBTOTAL: 1
CONDITION ARMANDO GARCIA
MNT
Found asbestos gasket laying on ground.
09/23/92 ODU 190203
PRJ SUBTOTAL: 1
CONDITION KEN DORRIES
MET
While working on steam leaks on BJCB steam line, noticed tubing wrapped with
asbestos tape.
03/05/92 P/S SHOP 135779
PSHOP SUBTOTAL: 1
CONDITION YOLANDA PADRON
MNT
Two safaty valves from N. field came in with asbestos gaskets.
i>
030812
06/08/92 STREET HI LAY OOMI 207424 YARD
ROAD SUBTOTAL: 1
CONDITION JOHN BRADLEY
MIT
I found several asbestos gaskets on the road.
04/27/92 NORTH SIDE REPAIR 20S698 SHOP
SSHOP SUBTOTAL: 1
CONDITION TOM TOLER
MIT
Found an asbestos gasket lying on the concrete right outside doorway.
10/15/92 SEMICON CONTROL BOOM CONDITION TIM MANNING
SHT
245077
When opening a desk drawer in the control rooa, discovered two full rolls of
asbestos wrap insulation.
SCO SUBTOTAL: 1
02/01/92 41H LEVEL OR 220282 PELLETING BLDG.
SHF SUBTOTAL: 1
CONDITION
SHT
FOUND ASBESTOS GASKET LYING ON THE GRATING
11/10/92 FURNACE SHOP 231307
CONDITION
MIT
AFTER ALL THE RAIN WE HAD TUESDAY WE HAD A LAKE ON THE SOUTH SIDE OF THE
FURKACER. WHEN THE WATER WENT DOWN I FOUND AN ASBESTOS GASKET ON THE
SHOP SUBTOTAL: 1
10/29/92 PIPE RACK SOUTH OF 244924 OOU
UHSP SUBTOTAL: 1
CONDITION
MIT
INSULATION ON PIPE IN RACK BROKEN DOWN AND FALLING APART.
ASBESTOS.
POSSIBLY
01/28/92 WELD SHOP 216644
NSHOP SUBTOTAL: 1
CONDITION TOMff TUCKER JR
MIT
Head was delivered to weld shop with gaskets still in place.
attached. Gasket naterial was asbestos.
Clean tag was
GRAND TOTAL: 107
030813
I
CUT DBF
DATE
LOCATION
07/29/94 N. SIB OF COCK
25949*
F80N PIPERACK
BDK SUBTOTAL: 1
ON th. JOB CIA SUhMARY with tAxbestost in the description
01/01/91 to 12/31/9*
TYPE
DESCRIPTION
CONDITION
MNP
I POUND SODA CANS AND TRASH IN AN ASBESTOS GASKET CAN.
07/26/91 OL1 VD AREA A
192619
CONST. COMPOUND
12/14/95 CCHPOUND AREA 272930
04/01/96 NORTH EAST CORNER
219304
P-1
CONST SUBTOTAL: 3
CONDITION
KATHLEEN HUNT
EVP
Many bags of what appears to bo non-haz, non-asbestos insulation waste are
being stored in unregistered areas, such as Olefins I Laydown area and the
Construction Dept, compound. EPD, and hence TWC, have not been notified of
this activity.
CONDITION
CONST
A 5 GALLON CONTAINING CP. 10 AND A 1 GALLON JUG Or HAND SOAP WERE DISPOSED OF IN THE INSULATION BIN LOCATED ON THE EAST SIDE or BLDG 2254. THE CP.10 IS A LOCK DOWN ADHESIVE USED TO SEAL OF ASBESTOS INSULATION BY OUTSIDE CONTRACTORS. B&ft ASBESTOS ABATEMENT DOES NOT USE THIS TYPE OF LOCK DOWN. I DON' T KNOW WEHRE THESE ITEMS CAME FROM.
CONDITION
CONST
DURING A JOB PUNNING WALK THRU I NOTICED THAT A SCAFFOLD POLE AND BASE WERE BEING SECURED TO AN EXISTING ASBESTOS INSULATED LINE WITH 9 WIRE. AS THE *9 WIRE WAS TIGHTENED TO SECURE THE BASE XT CUT (PENETRATED) INTO THE MULEHIDE EXPOSING SOME ASBESTOS INSULATION.
02/11/93 NORTH OF 2603 TANK
217495
IN N.FIELD
CONDITION
DIS
I FOUND AN OLD ASBESTOS GASKET IN THE DITCH JUST NORTH OF 2803 TANK.
04/02/93 380 246483
CONDITION
MNT
ASBESTOS CAN DOES NOT HAVE A LID.
04/05/93 230312
BESIB THE MAIL RACK AT 380
CONDITION
MNT
THE ASBESTOS CAN AT 380 HAD COCA COLA CANS AND OTHER TRASH IN IT.
CANS ARE NOT FOR ANYTHING BUT ASBESTOS GASKETS.
THESE
04/16/93 380 MAIL RACK 248589
CONDITION
DIS
NOTICED ASBESTOS TRASH CAN WITH NO LID.
04/16/93 NORTH FIELD TANK
248583
FARM
CONDITION
DIS
NOTICED ASBESTOS STICKERS FADED
04/16/93 NORTH FIELD TANK 2485*2 FARM
CONDITION
DIS
NOTICED SEVERAL "ASBESTOS FREE" STICKERS ARE FADED, HARD TO DISTINGUISH.
DIS SUBTOTAL: 6
01/06/93 BESIB THE MAINT. 226975 BLDG. SOUTH
CONDITION
WfT
POUND TRASH AND OTHER DEBRIS IN ASBESTOS GASKET CAN.
05/10/93 SOUTH OF VENT STACK CONDITION
MNT
250580
FOUND ASBESTOS GASKET IN TRASH CAN AT HP-II.
06/06/94 PROD. ROOM S. OF
259242
11 VENT STACK
CONDITION
NfT
WHILE EMPTYING CONTENTS OF ASBESTOS GASKET CAN I FOUND SCRAP POLY IN BOTTOM
OF CAN.
06/17/94 N.W. OF POLE BINS 259236
CONDITION
MNT
FOUND PAPER AND PLASTIC TRASH IN AN ASBESTOS GASKET CAN.
030814
10/11/9* HP2 FINISHING 29377*
HP2 SUBTOTAL: 5
CONDITION RICHARD VALENZUELA JR
SHF
Asbastos material being storad right outside of tha control rooa froa tha
job that took place in raaoving tha aatarial froa tha control rooa.
04/20/93 BUILDIBS 2 LAB 246495
LAB SUBTOTAL: 1
CONDITION
MNT
WENT TO CHECK INSULATION JOB IN LAB AND POUND 8-10 FEET OF ASBESTOS WRAP IN
A SMALL TRASH CAN.
01/05/93 NORTH WEST CORNER OF CONDITION
MNT
1*4722
TOUT F
WHILE I WAS EMPTYING OUT ASBESTOS GASKET CANS I POUND TRASH IN THE ASBESTOS
CAN.
01/13/93 LF-1 239*40
CONDITION
JERRY PYKA
SHF
Asbastos on tubing aountad on KC-S dryer, handrail. Asbestos on tubing on
raaction analyzer valva rack. Asbastos ovarhaad in tha pipa racks.
Asbastos in tha finishing structura and in purification.
03/12/93 BUILDING 344-EAST 24*665
CONDITION
KIT
ASBESTOS CAN LAYING ON ITS SIDE.
OVER BY THE WIND.
CAM WASN'T OPEN, IT WAS PROBALBY BLOW
04/01/93 G5000 DELUKPER 222223
CONDITION TOMUE HOLT JR
MNT
Found trash in "asbastos only" containar by GSOOO Daluapar.
05/03/93 BLOCK 12 242541
CONDITION CRAIG STRAKOS
MNT
Soaaona put asbastos gaskat in luggar bin.
04/17/94 BUILDING 353 247862
CONDITION
MNT
I NOTICED THAT AN EMPLOYEE WAS USING AN ASBESTOS BAG TO CARRY HIS TOOLS AND
EQUIPMENT AROUND WITH HIM.
06/06/94 BUILDING 354 259241
CONDITION
MNT
WHILE CHECKING ASBESTOS CANS FOR GASKETS I NOTICED THE CAPS ON THE EYE BATH
WERE OFF.
02/06/96 LP1 RX 283219
CONDITION DONNIE MAREK
MNT
Found asbastos gaskats on N2 prhaatar piping.
LP1 SUBTOTAL: 8
01/19/94 SCREEN PACK BURNER 230582
06/17/94 SCREEN PACK BURNER 247876 LP1F SUBTOTAL: 2
CONDITION
MNT "ASBESTOS GASKET ONLY' DISPOSAL CAN HAD LID OPEN. THE CAN SEEMED TO HAVE BEEN RUN INTO OR KICKED IN, THEREFORE NOT ALLOWING LID TO SEAL. THE CAN IS EMPTY WITH A NEW LINER.
CONDITION
MNT
FOUND WIRE AND TRASH IN AN ASBESTOS GASKET CAN.
06/06/94 0-500 REACTOR 246600
LP1R SUBTOTAL: 1
CONDITION
MNT
I FOUND NOW-ASBESTOS INSULATION IN AN ASBESTOS GASKET CAN.
05/14/93 SOUTH SIDE BLD. 11 246653
02/08/93 SWITCH RACK S. SIDE 237670 TANK FARM
01/23/95 BLDG. 165 267470
CONDITION
MNT
THE ASBESTOS CAN AT BLDG. 11 HAD DOMESTIC TRASH IN IT.
CONDITION
MIT
SEVERAL SPOOL PIECES LAYING ON WHITE ROCK AND GASKETS LAYING ON GROUND
(POSSIBLE ASBESTOS GASKETS)
CONDITION
MNT
ASBESTOS GASKET ON FLANGE.
030815
02/30/96 CAS II EKL TANK 271910
02/16/96 OEU 275974
04/26/96 ENERGY SYSTEMS
266210
10/01/96 HF2 RXK 271926
09/09/96 ODU 271925
MT SUBTOTAL: 1
CONDITION
nrr
REMOVE ASBESTOS INSULATION ON SOUTHWEST SIDE Or THE EKL TANK. (VAL. ) THERE
WAS BROKEN INSULATION THAT CAME FROM VAL. AND WAS LAYING ON GROUND.
CONDITION
nrr
FOUND VALVE IN METAL LUGGER AT GEU WITH POSSIBLE ASBESTOS GASKET ON THEM.
INCIDENT
MNT
WHEN SETTING 17 COOLING WATER MOTOR, HAD TWO CRANES HOOKED ON TO THE MOTOR, UPON SETTING THE MOTOR INTO PLACE THE LOAD SWUNG OVER, AFTER LETTING DOMI ON ONE OF THE CRANES, AND THE CHOKER HIT A LINE WITH ASBESTOS INSULATION AND BROKE A PIECE OFF. AFTER SETTING THE MOTOR IN PLACE RIGGER NOTIFIED THAT ASBESTOS WAS BROKE AND HE TOLD THE OM'S TO GET OUT OF THE AREA AND STOP WORK.
CONDITION
nvr
I WAS NOTIFIED BY AN EMPLOYEE THAT THERE WAS UNIDENTIFIED GASKET MATERIAL LAYING IN THE SOUTH DRIVEWAY NEAR THE 1 VENT STACK AREA. THIS MATERIAL LOOKED LIKE IT COULD POSSIBLY CONTAIN ASBESTOS.
INCIDENT
NfT WORKING AT ODU ON A LINE TO STRIP ASBESTOS PUT UP GLOVE BAG AND STRIPPED LINE. THE ASBESTOS WAS SOAKED WITH CHZXXCALS. THE OttMICAL WAS CRUD TRIETHANOLAMINE.
01/06/93 NORTH NEST CORNER
226974
ODU
CONDITION
MNT
FOUND SHEET METAL AND OTHER TRASH IN ASBESTOS CAN.
03/01/93 237639
H.4 S. PIPERACK 4TH
ST. ON TOP
CONDITION
MNT
EXPOSED ASBESTOS ON ENTIRE PIPE (ESTIMATION OF A 6-0" PIPE ON THE VERY TOP LEVEL)
06/06/94 BUTYLS TANK FARM 259229
CONDITION
MNT
I FOUND METAL OBJECTS AND TRAHS IN AN ASBESTOS GASKET CAN.
06/17/94 BUTYLS TANK FARM 259237
CONDITION
MNT
I FOUND FIBERGLASS INSULATION IN AN ASBESTOS GASKET CAN.
ODU SUBTOTAL: 4
03/21/93 304 NASH RACK 241670
0L1 SUBTOTAL: 1
CONDITION
MNT
THERE IS AN ASBESTOS DRUM IN THE WASH RACK THAT IS FADED OUT AND NOT CLEARLY
MARKED.
01/21/93 501--NORTH 207612
CONDITION
ran
TUBING IN SCRAP LUGGER METAL 501 NORTH WITH ASBESTOS WRAPPING ON IT.
01/21/93 500 BUILDING 207613 COMPRESSOR
CONDITION
Mfr
TRASH INSIDE "ASBESTOS CAN"
02/10/93 UNDER 12 CO2 KETTLE 230745
CONDITION
MNT
IT WAS BROUGHT TO MY ATTENTION THAT AN ASBESTOS PIPE HAD BEEN DAMAGED AND
NEEDED PATCHING.
02/22/93 504 SPOT 11 247033
CONDITION
MNT
INDIVIDUAL PICXED UP VALVE AND TOOK IT TO THE INST.
GASKET ON IT.
SHOP WITH ASBESTOS
03/11/93 C2H4 6 LIGHTER VS. 237651 ACETONE
CONDITION
MIT
EXPOSED ASBESTOS INSULATION
03/01/93 C2H4 4 LIGHTER VS
237652
PROPANE
CONDITION
MIT
EXPOSED ASBESTOS INSULATION
03/01/93 TOP MANWAY ON 237653 NORTH/SOUTH P.R.
CONDITION
MIT
ALL JUNCTION BOXES ON TOP MANWAY HAVE EXPOSED ASBESTOS INSULATION ON THEM.
JUNCTION BOXES RUN FROM P.R. MARKER 4-A 6 B SOUTH. (FROM SOUTH TO NORTH
030816
END OF CATWALX)
Q 2/24/93 PIPERACK. lOA(ll)
237656
75-15 GEN.
CONDITION
i*rr
EXPOSED ASBESTOS INSULATION OR STEAM GENERATOR
03/01/93 PIPERACK 1A TO 3A 237630
CONDITION
NIT
EXPOSED ASBESTOS INSULATION ON PIPE IS-34 FROM 90 DEGREE ( ELBOW) SOUTH IN PIPERACK. INSULATION IS CRACKED OPEN AND EXPOSED. FROM NORTH END OF SEPARATIONS AT BEGINNING OF RACK TO JUST BEFORE 2ND ST. RACE CROSSING.
03/11/93 PIPERACK R. 344 237650
CONDITION
MOT
EXPOSED ASBESTOS INSULATION ON LINES 146, 147, AND 148 MIDWAY IN LOWER
WALKWAY AT 12-1 SUPPORT
03/24/93 REST OF BOILER 22 246637
ACCIDENT
MIT WE WERE LOADING THE ASBESTOS TRAILER. ONE EMPLOYEE THREW A BAG ON THE TRAILER. ANOTHER EMPLOYEE GRABBED THE BAG AND THREW IT OFF THE TRAILER HITTING ME IN THE FACE CAUSING MY HEAD TO SNAP BACK.
05/25/93 GAS 2 246500
CONDITION
MIT
POUND 2 EMPTY DRINKING WATER CAMS AT VAN BOX ON SOUTH SIDE OF SEPARATIONS
BELONGING TO ASBESTOS CREW.
04/30/93 503 SOUTH 246651
CONDITION
MIT
I FOUND SOME ASBESTOS INSULATION LAYING IN THE WALKWAY ON THE SOUTH SIDE OF
SEPARATIONS. IT HAD FALLEN OFF OF A PIPE IN THE RACK.
10/10/93 GAS--II 254124
CONDITION
MIT
INSULATION LOOKED LIKE ASBESTOS LAYING BY THE DIRTY OIL TANK THAT SOMEONE
REMOVED
01/05/94 SEPARATIONS 255003
CONDITION
MIT
SAW SOME ASBESTOS ON THE FLOOR
01/24/94 FURNACE REPAIR SHOP CONDITION
MOT
230352
THERE WAS AN ASBESTOS GASKET CAN WITH NO TOP ON IT
02/10/94 W. SIDE 246725
CONDITION
MOT
WHILE CHECKING SCATFOLD I NOTICED SOME UNIDENTIFIED INSULATION ON THE DECK
WE SUSPECTED IT TO BE ASBESTOS.
02/22/94 S. SIDE BOILER 22 246727
CONDITION
MIT
FOUND WRAPPING SUSPECTED TO BE ASBESTOS HANGING FROM OLD TUBING
02/22/94 E. WALKWAY SECOND
230746
LEVEL
CONDITION
MOT
OUTSIDE CONTRACTOR WENT UNDER ASBESTOS BARRICADE.
03/22/94 REST OF MKP TANK 247054
CONDITION
MOT
I NOTICED SOME INSULATION ON THE GROUND, THAT COULD BE ASBESTOS.
04/29/94 E. OF 501 246590
CONDITION
MOT
I NOTICED WHAT APPEARED TO BE ASBESTOS INSULATION LAYING ON THE GROUND.
09/06/94 H.W. CORNER OF
260415
COOLING TONER
CONDITION
MIT
EXPOSED INSULATION WXCX IS MARKED ASBESTOS.
09/07/94 GAS-2 MAINTENANCE 261935 SHOP
CONDITION
MOT
SOMEONE PUT TRASH IN AN ASBESTOS CAN.
04/19/95 OLZFIHS 267293
CONDITION LEE YAXLXN
MOT
Found asbastos tubing wrap in doaastic trash can.
11/04/96 OL2 205226
CONDITION KEN DORRIES
SHF
Found Asbastos insulation on staaa tracing on rafrigaration oil lina going
to cosprassor bldg.
11/04/96 OL2 205225
CONDITION KEN DORRIES
SHF
Found Asbastos insulation on staaa tracing on angina oil lina going to
coaprassor bldg.
11/04/96 OL2 205220
CONDITION KEN DORRIES
SHF
Found asbastos insulation on tubing on top of biowcaso for FG scrubbars.
(Abandonad tubing)
030817
11/04/96 OL2 285227 11/07/96 OL2 285220
11/07/96 OL2 285221
OL2 SUBTOTAL: 30
CONDITION KEN DORRIES
SHF
Pound asbastos insulation on coaprassor blowcasa tubing.
CONDITION REM DORRIES
SHT
Noticad axposad asbastos insulation on 151 staaa haadar going froa co^.
bldg, to boilors south sida of walkway.
CONDITION KEN DORRIES
SHF
Koticad axposad asbastos insulation on abandonad staaa lina by walkway going
froa coaprassor bldg, to boilars.
06/18/96 SETTLIHG BASIN 12 297964 GAS
OL2 SB SUBTOTAL: 1
CONDITION PAT DUNLAP
MNT
Found asbastos gaskat on ground by cooling towar north sida.
01/06/94 SOUTH SIDE HALKNAX 255113
01/31/94 SOUTH SIDE 11 OXIDE 193577
axx SUBTOTAL: 2
CONDITION
MIT
ASBESTOS INSULATION ON WALKWAY. COULD NOT SEE WHERE IT CAME FROM.
CONDITION
WT
WHEN I WAS DOING OUR MONDAY MORNING CLEAN UP I NOTICED SOKE INSULATION ON
THE GROUND. I WENT FOR A BETTER LOOK AND FOUND IT TO 8E ASBESTOS.
04/15/93 PP-1 BLD. 11 248204
06/08/94 BUILDING 11 259231
06/18/96 PI REACTOR 297963 PPU SUBTOTAL: 3
CONDITION
MNT
NOTICED A TRASH CAN BESIDE BLD.
BAG FOR A TRASH CAN LINER.
11 THAT HAD TRASH IN IT AND HAD AN ASBESTOS
CONDITION
MNT
WHILE CHECKING ASBESTOS CANS FOR GASKETS I FOUND ASBESTOS CAN HAD BEEN
THROWN IN METAL BIN.
CONDITION PAT DUNLAP
MNT
Found four asbastos gaskats on third laval.
04/16/93 E & 5TH ST. 211036
BOAS SUBTOTAL: 1
CONDITION
DIS
PICKED UP 2" 150# ASBESTOS GASKET FROM DITCH.
12/09/92 HELD SHOP 222659
04/23/93 CARBIDE HELD SHOP 248039
06/06/94 HELD SHOP SPOT 24 246601 06/08/94 HELD SHOP 259235 12/13/94 BUILDING 165 266013 SHOP SUBTOTAL: 5
CONDITION
DIS 1" PIPE FROM HP-2 IJ50751, JOB RET. 1253, BLDG. 566 SPOT 9. LARRY HERRON GAVE ME RED CARD JOB FROM SANDBLAST WHICH REQUIRED CUTTING PIPE 1/2" AND PUTTING BACK TOGETHER WITH 1" WELDED UNION. WHILE LEVELING PIPE UP TO MAKE FIT, NOTICED ASBESTOS REMAINING ON TWO OF THE FLANGE FACES.
CONDITION
DIS ON 12/9/92 I WROTE A CIA (AN INCIDENT) CONCERNING THE RECEIPT OF A PIPE TO BE REVISED IN THE WELD SHOP. THE FLANGES ON THIS PARTICLUAR PIPE HAD ASBESTOS ON THE FLANGE FACES. JOB REF. 1253
CONDITION
MNT
Z FOUND STYROFOAM IN AN ASBESTOS GASKET CAN WHEN CHANGING LINERS.
CONDITION
MNT
THE ASBESTOS GASKET CAN USUALLY LOCATED HERE WAS MISSING.
CONDITION
MNT
PARTS OF ASBESTOS GASKET ON FLANGE FACE OF VOLATE.
04/13/93 BLDG. 11
CONDITION
MNT
030818
211030
NOTICES EMPLOYEE PUTTING TRASH IN A CAN MARKED ASBESTOS ONLY.
06/07/94 DECONTAMINATION 263065 TRAILER
CONDITION
MNT FOUND THAT SOMEONE HAS BEEN STEALING OUR WASHING LIQUID ITS NOT A GREAT LOSS BUT ITS STARTING TO HAPPEN MORE OFTEN TJHIS TIME HE HAVE RECOGNIZED THAT THIS INDIVIDUAL IS ALSO GOING INTO OUR DIRTY ROOM WHICH IS C0NCIDERED CONTAMINATED WITH ASBESTOS UNTIL COMPLETELY CLEANED.
06/06/94 306 EAST 259230
CONDITION
MNT
I FOUND ASSORTED TRASH IN AN ASBESTOS GASXET CAN.
06/06/94 S. SIDE HIGH BAX 259236 AREA
CONDITION
MNT
POUND AN ASBESTOS GASKET CAN WITH PLASTIC CUPS IN IT.
06/06/94 INSIDE CONTROL ROOM CONDITION
MNT
259234
02 UNIT
I POUND PAPER TRASH INSIDE AN ASBESTOS GASKET CAN.
07/10/94 SOUTH Or 02 UNIT 260317
CONDITION
KIT
FOUND TRASH IN ASBESTOS CAM.
NOT FOR TRASH.
THE ASBESTOS CAN ARE FOR ASBESTOS GASKETS ORLY
UXSP SUBTOTAL: <
GRAND TOTAL: St
030819