Document NEkyqVRD77pzXgk4Xp0oVxvng

a) UNION CARBIDE CORPORATION MAINTENANCE PROCEDURE SEADRIPT PLANT - 510 PLAINTIFF'S EXHIBITS > I UC-P-134 MAINTENANCE DEPARTMENT NO:_____________MP-I-6 PAGE:_________01 of 05 EPPECTIVE: 06-22-78 REVISION: 03-19-86 ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL, HANDLING & DISPOSAL GENERAL This is the plant procedure for the safe removal of asbestos-containing insulation material and compliance with OSHA 29 CPR 1910.1001. The purpose of this procedure is to ensure the safety and health of employees directly involved with performing the work and others, either in the immediate area or downwind, who may be exposed to residual dust/fibers. Insulation containing asbestos is no longer installed; the concern of this practice is the identification and control of old insulation containing asbestos. STANDARDS / Permissible Exposure Limits: ... _ Asbestos dust concentrations must not exceed an 8-hour time weighted average (TWA) ef 2 fibers (longer than 5 micrometers) _per cubic centimeter of air. At no time may the "ceiling" concentra tion exceed 10 fibers Monger than 5 micrometers) per cubic .`^centimeter of air. WORKPRACTICES A. Only specially trained and qualified persons meeting medical requirements of OSEA 1910.1001, J, medical examinations, shall be employed in removal or demolition of asbestos where the possible exposure could exceed permissible exposure limits, ref. "Standards. A", above and Medical Examinations on page 4. B. When asbestos insulation is suspected, a qualified insulator will make a positive identification that an item is asbestos insulation covered and will mark it using the yellow and black stick on labels. The labels are Stores Items (63-486-160). C. Demolition, removal or handling of asbestos-containing insulation shall be performed while the material is in a sufficiently wet state to prevent emission of airborne fibers exceeding exposure limits. L- 030757 UNION CARBIDE CORPORATION MAINTENANCE PROCEDURE SEADRIPT PLANT - 510 MAINTENANCE DEPARTMENT NO:__ PAGE: EFPECTIVE: REVISION: MP-I-6 02 Of 05 06-22-78 03-19-86 ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL. HANDLING t DISPOSAL D. Caution signs and barricades shall be posted at all approaches to areas which may contain excessive concentrations of airborne asbestos fibers so that an employee may read the signs and take necessary protective steps before entering the area. The signs shall conform to 20* x 14" vertical format and state: ASBESTOS/DUST HAZARD BREATHING ASBESTOS DUST MAY BE HAZARDOUS TO YOUR HEALTH AVOID BREATHING DUST WEAR ASSIGNED PROTECTIVE EQUIPMENT DO NOT REMAIN IN AREA UNLESS YOUR WORK REQUIRES IT (These signs are available in Stores, 463486-120) E. An appropriate barricade, using yellow 6 black colored tape shall be erected around the perimeter of outdoor areas as a supplementary, protective measure to discourage unauthorized entry. F. In case of repair or transportation of an'object that is asbestos insulated, an adequate amount of insulation will be removed to allow safe repair Or transport. The exposed ends of asbestos insulation left will be coated before transporting or repair. The object will be prominently identified using labels as described in *B? (Stores item *63-486rl60).. G. Transportation will be alerted when asbestos insulated"items are -to be transported, so that special precautions can be taken. Truck Drivers so *alerted* will carry special water spray cans to wet down spots or breaks that might occur in handling or transporting. The person requesting the truck will be responsible for "special" notification and will make sure the object is prepared as in (F) above. H. Salvaged equipment with asbestos insulation will be taken to the asbestos removal site with insulation ON and be placed in the specially marked area. The equipment remover is responsible for providing a Work Request to remove and dispose of the asbestos insulation. Major demolition removal will be done on site under controlled conditions. L 030758 ONION CARBIDE CORPORATION MAINTENANCE PROCEDURE SEADRIPT PLANT - 510 MAINTENANCE DEPARTMENT NOs_____________MP-I-6 PAGE: oT of' 05 EFFECTIVE: 06-22-78 REVISION: ~03-19-86 ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL, HANDLING t DISPOSAL I. Bags & Labels: Special reinforced plastic bags are used by plant personnel for bagging and disposing of asbestos insulation. Stores item #14-103-602. Special labels for the bags are in Stores, item #64-486-160. The label states: CAUTION CONTAINS ASBESTOS FIBERS AVOID CREATING DUST BREATHING ASBESTOS DUST MAY CAUSE SERIOUS BODILY HARM J. Removal - Insulation to be removed shall be wetted and placed directly into special plastic bags (Stores #14-103-602). A good practice is to place plastic sheeting below the job site, mist spray the insulation as required while removing and then dispose of the plastic sheeting along with the insulation. Stripped insulation must not be dropped or thrown to the ground. Dust tight containers, chutes, or special metal load luggers, must be used for lowering insulation. When removing large amounts of insulation, thoroughly wetted insulation maybe placed in special open'topped metal containers (large load luggers).. This insulation must be kept wetted down and covered until disposed of. The container must.be made free of asbestos residue before reusing in the plant. A good practice is to line the container with plastic sheeting prior to loading and then dispose of the sheeting with the insulation. K. Waste Disposal - Asbestos waste, scrap, debris, bags, containers, equipment, and asbestos-contaminated disposable clothing, consigned for disposal, which may produce airborne concentrations of asbestos fibers in excess of prescribed exposure limits shall be collected and disposed of in sealed impermeable bags, or other closed impermeable containers to an approved landfill. An order for waste removal must be obtained from the E.P. Department. HOUSEKEEPING All external surfaces shall be maintained free of accumulations of asbestos fibers, if, with their dispersion, there would be an excessive concentration. Special attention should be given to cleaning scaffolds used in demolition work. 030759 ONION CARBIDE CORPORATION MAINTENANCE PROCEDURE SEADRIFT PLANT - 510 MAINTENANCE DEPARTMENT NO i__ PAGE: EFFECTIVE: REVISION: MP-I-6 04 of 05 06-22-?? 6S-19-86 ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL, HANDLING & DISPOSAL" PERSONNEL PROTECTIVE EQUIPMENT All personnel engaged in the removal of asbestos insulation are required to wear an approved respirator and approved protective clothing. In severe conditions it may be necessary to tape the wrists, ankles and neck of the protective clothing. A. The approved respirators at the Seadrift Plant are: The 3M 8710, The North Half with 7500 B cartridge (purple color), the D.S. Safety Half Mask with 158-T-12 cartridges (purple color); the Nilson Full Face Mask Respirator equipped with R-ll cartridges; the Full Face Mask Supplied Air Respirator; and the Self Contained - Breathing Unit (Scott-Air Pak) in emergency situations. B. Coveralls, white paper (53-129-010) or yellow vinyl (63-380-112), overshoes or rubber boots and vinyl or rubber gloves are minimum acceptable protective clothing. Contaminated protective clothing will be disposed of in the same manner as asbestos materials. NDUSTRIAL HYGIENE RESPONSIBILITY Employee exposure monitoring will, be conducted as required by regulations. Ref . UC.C S.H. 256* OSHA Regulation. 29 CFR 1910.1001 and Federal E.P. Regulation 40 CFR 61. MEDICAL EXAMINATIONS Medical examinations for persons doing asbestos removal and/or demolition must be conducted in accordance with OSHA Regulation 29 CFR 1910.1001, J, 1 thru 6. Additional reference material may be found in OCC Corporation Occupation and Health Medical Manual, appendix 3, pages 2*3. ASBESTOS REMOVAL NOTIFICATION/EPA Reg. 40 C.F.R. 61 When demolition or removal involves more than 160 square feet or 260 lineal feet of insulation containing more than one percent asbestos by weight, either in a single project or in a predictable series of projects over a course of one year that are additive to this amount it must be reported as follows. L 030760 UHXOli CARBIDE CORPORATION MAINTENANCE PROCEDURE SEADRIPT PLANT - 510 MAINTENANCE DEPARTMENT NO: PAGft EFFEdriVfc: REVISION: MP-I-6 SFoTTF 06-22-78 63-19-86 ASBESTOS-CONTAINING INSULATION MATERIAL/REMOVAL. HANDLING ft DISPOSAL A. The department in which the removal takes place notifies the Environmental Protection Department at least 10 days prior to planned demolition or as soon as possible after beginning an unplanned (finergency) project which exceeds the limits. B. The Enviromental Protection Department notifies the appropriate Federal and State agencies. TRAINING All employees who may be exposed to airborne asbestos concentrations in excess of the exposure limit listed with or without the use of respirators must participate in a training program that includes these information topics: A. Health affects associated with asbestos exposure. B. Relationship between exposure to asbestos and smoking in producing lung-cancer. - ~. Nature'of operations which.could result in exposure to asbestos and necessary protective steps to minimize exposure including, as applicable, engineering controls, work practices, respirators, housekeeping and protective clothing. D. Purpose, proper use, fitting instructions, and limitations'of the respirators used to' protect against asbestos fibers. E. Review of all provisions contained in 29 CFR 1910.1001, Asbestos. F. Training will be documented and recorded. RECORD KEEPING A. Applicable training and medical records for U.C.C. employees will be maintained by the location as required by applicable plant policies. B. Applicable training and medical records for contract employees will be maintained by the contractor and will be available to UCC upon request. OTHER: For further information on asbestos removal and disposal refer to OSHA egulation 29 CFR 1910.1001, Federal E.P. Regulation, 40 CFR 61, UCC >andard Practice, S.H. 256 and Occupational t Health Medical Manual, Appendix 3. 030761 UNION CARBIDE CORPORATION TECHNICAL CENTER P.O.BOX 8361 S. CHARLESTON, VY 25303 INTERNAL CORRESPONDENCE To: See Distribution List Date: July 22, 1986 Orig. Dept HS&cA Arm Industrie! Hygiene C.C. T. L Collins T. E. Hanning C. ?. Maxwell Subject Amenoa rentes Siansrc On June 20985 OSKA amended its present standard 29 CFR 1910.1001 for Asbestos which hes gone into effect cn July 21,1986. a summery of the changes in the health standard has been prepared by T. . Hanning of our Health. Safety and Environmental Technolor/ Group is attached for your review. a significant difference in tne new standard is the oermissible exposure limit now reduced from 2.0 fibers per c.c. (f/c.c) to 0.2 f/ac. with an action level of 0.1 f/ac, 8-hour time-weighted average (TWA8). A ceiling limit of 10f/aa is no longer appIicaole in the amended standard. The amended standard will result In a few changes tn now we handle asbestos containing materials. These changes are mainly relative to exposure monitoring techniques (Industrie! Hygiene responsibility), posting, training and protective equipment We will provide guidance to those groups who are involved in handling asbestos containing materials. All questions relative to compliance with this standard me/ be addressed to this writer. Attachment/ MAP Manner A. Patel Technical Center Industrial Hygienist Jo C" 030762 UNr.'. -- r-.~ : 2- ^wnrCAATlwN iNG.NE?iuG. - ' "HCi-MCuCGY ScP'/iCSS C?;,S7J.'^T "SALT*. SArST- ,-\S * ' TN'V.SN"i.L TECHNOLOGY j - : .. VVSST viPOiNU . o -- 'J " .. ,, 0. :/* s.`.` C A ."t C L M <* `i*'i W A1, i ps8A6/ TC: S. VI. Clark D. A. Scssslln v. H. Connkoskl 2. A. Leonard 2. S. Leverton^ C. P. Maxwell ' 2. E. Neff T. ?. Raby FROM: T. E. Hanning S::2utCT: final Rules for Octut:-'..'nr.l Censure to Asbestos, Trefoil re, Ar.r:.:r'-.jl Alts, and ^.ctAnollti fA-enr.r -"A 1 JULi~m * n r*i& rt- O lentTe-en: Attached As a'prelAmAnary surmry of the changes between the ame-ded subject r.aalth standard and rna original -'.;b**stos standard as stated An Zt 1913.1001. The amended standard was sus i `-aisc by OSHA An the federal Reels =r. Cur.e 20. TS86 and win take e-'ect an Z- Ay 21 . 1986. The Safety ar.d health Technology Manual health operating practice 2H-2S6 (Removal and Handling .'.toastContaining Insulation Material) will be revised to reflect the changes set forth in the amended OSHA standard. Please cull If you have further questions or comments. TH/jc Attachments T.fE. Hanning lx*. 5903 / 030763 Changes Between the Original and Amended Asbestos Occupational Health Standard General OSHA amends Its present standard (29 CFS 1910.1001) regulating occupational exposure to asbestos by developing two final standards that aoply to general industry and to construction because the differences In exposure and wort place conditions In general Industry and construction wort sites warrant separate treatment. UCC activities would generally fall under the revised standard for general Industry. OSHA has concluded that chemically modified asbestos should be regulated in the same manner as unmodified asbestos. OSHA concludes that all forms of tremollte, anthophylllte and actlnollte should be regulated under the revised standards. In the final standard the action level has been set at O'.l fibers per cubic centimeter (f/cc) which triggers the monitoring, medical, and employee Information and training requirements. This action represents no real change to the standard with regard to this provision, but merely clarifies OSHA's policy. Permissible Exposure Limit OSHA has reduced the current 2 f/cc permissible exposure limit (PEL) to an 8-hour time-weighted average (TWA) PEL of 0.2 f/cc. This lower limit should reduce the recorded mortality from lung cancer, mesothelioma, gastrointestinal cancer, and other types of cancer due to asbestos exposure. Celling Limit The amended standards do not designate a celling limit for exposure to asbestos. The original standard had a celling limit of 10 f/cc and was met througn engineering and work practice controls. Exposure Monitoring The table below lists the two exposure situations along with the monitoring frequency for each. Exposure Scenario Required Monitoring Activity 1. Below action level 2. At or above the action level 1. No monitoring required 2. Monitor exposure at least every 6 months -2- 030764 The emended standard requires the employer to collect airborne asbestos samoles using 25 mm diameter mixed cellulose filters and a 50 mra extension cowl. Samoles must be analyzed using a phase contrast microscope calibrated using a ohase shift test slide and equipped with a Walton-3eckett graticule. The filter samples must be prepared using acetone-trlacetln clearing solution and be counted In accordance with the *Aa rules contained In the NIOSH 7400 method. Regulated Areas The amended standard requires employers to Identify as regulated areas any locations In their wort places where there may be occupational exposures to airborne concentrations of asbestos above the PEL. The amended standard prohibits eating, drinking and smoking In these areas. Only authorized persons may enter regulated areas which must be clearly marked. The existing OSHA standard does not contain a provision for establishing regulated areas. Methods of Compliance The amended standard requires employers to Institute engineering and work practice controls to reduce the exposure of employees to or below the PEL. If the employer establishes that such controls are not feasible,, selected respirators may-be used to supplement the engineering'and work practice controls. Respiratory Protection Respirators may be used to limit employee exposure to asbestos In the following circumstances. 1. Ourlng the Interval necessary to Install or Implement feasible engineering and work practice controls, 2. In work operations such as maintenance and repair activities or other activities which the employer establishes that engineering and work practice control procedures are not feasible. 3. In work situations where feasible engineering and work practice controls are not yet sufficient to reduce exposure to or below the PEL. 4. In emergencies. These limitations on the required use of respirators are consistent with the requirements of the past asbestos standard and with good Industrial hygiene practice. Protective Work Clothing and Equipment The final standard makes a change from the current standard to respond to the evidence developed since 1971 that asbestos Is a potent human carcinogen. Protective clothing Is to be supplied to employees exposed above the PEL of 0.2 f/cc. -3- 030765 The final standard provides that the employer ensure that all protective cloth In? Is removed at the end of each wort shift only In change rooms. The standard emphasizes the need to assure that contaminated clothing Is stored, cleaneo/laundered. or disposed of in a safe manner. The final standard clarifies that the obligation Is on the employer to provide personal clothing at no cost to the employee. The final standard also requires the employer to Inform those who handle the contaminated protective clothing of the potentially harmful effects of exposure to asbestos. Hvolene facilities and Practices The final standard like the existing standard reiterates the type of change room an employer must provide and the requirement that the employer prohibit the consumption of food and beverages In areas where there Is exposure to toxic substances. Unlike the existing standard, the final standard requires employers tor assure that employees exposed to asbestos during their work shift shower before leaving the. plant and do not leave wearing work clothing. The final standard requires employers to provide persons working In asbestos areas with filtered air lunchrooms which are readily accessible. Employers must also assure that employees wash their hands and face prior to eating or smoking and do not enter the lunch room wearing protective clothing, unless cleaned beforehand. Communication of Hazards to Employees The final rule for asbestos requires that legible caution signs be posted at each regulated area where occupational exposures could exceed the PEL. Signs must also be posted at all approaches to areas containing excessive concentrations of airborne asbestos fibers. Signs must bear the following: Oanger - Asbestos; Cancer and Lung Olsease Hazard - Authorized Personnel Only; Respirators and Protective Are Required In This Area. The final standard Is not substantially different from the present OSHA standard. The section on sign specifications simplifies the sign requirements and eliminates unnecessary detailed specifications (letter sizes and styles, spacing between lines) In favor of a more performance oriented approach. -4- 030766 . 'he -.tended standard also requires - i\' - - materials. mixtu-es. .'=*. iris, and other product: cr.n:;::.-.q niestc: fibers. or their : labeled -itn the appropriate linger - Contains Asbestos .ter:; Avoid treating Oast; '.-:sr and '.an? Cl seise hazard. ~'-.t nev standard allows tvs except'.^:-: :o v- zsr-z; sheet: (HS2S) requirement;; no lace* or ` -t..here labelling ane material : is required *.n those * Asaestos fiber; have been modified by a bonding agent provided that the manufacturing can demon:tr--.ce that during any use the employee will remain below the act.-.n level; or ' Asbestos Is present In a product l.n concentrations les: than 0.1%. The new standard updates the existing-standard by providing that airborne concentration: .oust be fcept below the action level rather than the PEL.' ~'-z final standard requires employers to prov'da a training program for >"i *".;loy*es expected to be exposed to airborne asbestos at or above the of 0.1 f/cc. .''k! the existing standard vnlch -^ct surfaces be free of accumulation of asbestos fibers if, w'th their dispersion, be en excessive concentration, the revised standard removes the i.rr.a'.yhrase of excessive concentration. Specific provisions for house- -eer ire '.-.eluded In the final rule. Some of these are prohibiting the olei:`.--t of iccestos dust with compressed air. dry-sweeping and dry clean-up, and ; 'f. .s-i-g the accumulation of asbestos -aste on surfaces. OSHA ant'd; :es tr.at compliance with this prevision will entail a regular he..;- ccnecule based on exposure conditions at a particular plant and u> ccp-ior ty for emergency cleanup of spills or other unexpected source of as:: re. fleo i ", ~_ rve 111 ance final standard requires that the medical surveillance program provide each affected employee with an opportunity for a comprehensive annual medic:1, examination. This does r.ot change the provisions of the existing st.In the final standard however, or;j.A believes it appropriate to trig-,-.-:- the ^epical surveillance requirements at the action level of 0.1 f/cc as e'.-.r.t-hcur TWA. 2LH-. has also revised the time within which the employer must conduct pre:lacr:T.=..c examinations after hiring employees. The final standard requires that :.:-.ent medical examinations be given pr'or to the assignment of an -tv. 1 ;; j job exposed to concentrations of ad-to-ne asbestos. The -- . permits the employer to conduct mec'crl examinations within ays of the hire data. 030767 " The employer Is also required to hove medical examinations performed by or under the supervision of a licensed physician, provide the physician with a copy of this standard and all work practice Information performed by tno employer, and obtain a written signed opinion from the physician containing the results of the medical examination. The final standard requires that x-rays be offered at S year intervals during the 10 years following an employee's first exposure to asbestos. After 10 years the employee's age category will determine the frequency of x-ray testing. Record Keeping The final rule provides that records be kept to Identify the employee monitored and to reflect the employee's exposure accurately. The employer Is free to keep records the most effective way. The time period required for retention of exposure records Is thirty years. Employers must notify the Olrector In writing at least 3 months prior to the disposal of any records. Appendices Eight appendices are Included In this final standard. Appendix Status A - Reference Method for Analyzing Air Samples for Asbestos Mandatory B - Asbestos Sampling and Analysis by NIOSH Method 7400 Mon-mandatory C - Qualitative and Quantitative Respirator kit testing Procedures Mandatory 0 - Medical Questionnaire Given to Employees Who May Be Exposed to asbestos Mandatory E - Interpretation and Classification of Chest Roentgenograms Mandatory F - Work Practice and Engineering Controls for Automotive Brake Repair Operations Non-mandatory 6 - General Technical Information on Asbestos Non-mandatory H - Medical Surveillance Guidelines Non-mandatory TEH:Jc 07-10-86 51220 -6- 030768 UNION CARBIDE CORPORATION Owmcsls and Plastics Dtastw Pi. Bom 186 ____ Port Lavaca. Texas 77979 INTERNAL CORRESPONDENCE ro: A W. Kenne 2229 one. August 11. 1986 From: Safety Cm to: M. L. Fox J. N. Permit 13 13 Subject: ASBESTOS RESPIRATORS The new OSHA Asbestos Standard requires that powered air respirators will be provided to employees exposed to asbestos If they request them. I do not feel that we should provide powered air respirators for UCC employee use in the plant since we do not get involved with asbestos insulation removal. However, you may want to inform B&R of this new OSHA requirement so that they can provide them If requested. Sincerely, L 6. McMullen 030769 MOBILE DECON UNIT Unit to be mounted on a 20' Tandem Axle Trailer with a Tongue Mounted Leveling Jack, 2" Ball Hitch, 6 Plyrated Tires (no spare required). The aluminum outer cover shall be primed and painted to prevent corrosion. We may want to paint it here to assure an adequate paint job. The Unit should be 3 compartmented consisting of: 1. A Dirty Area with a built in negative air flow system of adequate capacity to prevent contaminated air from entering the clean area. This area should be lighted, have storage space, benches, hangers for miscellaneous items and a waste container for contaminated throw away items. There should be a clothes washer and dryer installed with the washer discharge water piped into the shower holding tank and the dryer discharge ducted to the inlet of the negative air flow system. There should be several 110 volt electrical outlets and the walls and floor should be constructed of materials that are easily cleaned and waterproof. The access door to this area is preferred through the back of the trailer. The access way should have a retractable steps. 2. A Shower or Clean Up Area consisting of two showers, an inline electrical hot water system capable of supplying ample hot water for both showers and the wash machine. Me will not operate the washer and showers simultaneously. A waste water holding tank equipped with a pump to discharge waste water through a dual filtering system. Final filtration shall be 5 micron maximum. 030770 3. A Clean Area which is air conditioned, heated and lighted, has at least eight lockers for personal items and clothing that have hasp type locking devices. There must be adequate space for storage of protective clothing and respiratory equipment, gloves, filters, towels, etc. There should also be several 110 volt electrical outlets. Outside access to this area should have a retractable steps. This Unit should be equipped to receive 220 volt power from a transformer we will mount in the tongue area. The Unit electrical wiring shall be circuit breaker equipped and the electrical wiring should be in conduit or be of heavy duty underground rated wire. The potable water connection will be a hose bib with a shut-off valve. The access doors must be locable. 030771 (%&yemreen VSAFETY SYSTEMS. INC MOBILE DECONTAMINATION UNITS (NEGATIVE FORCE HIGH EFFICIENCY FILTERING SYSTEM) A CMfklcly tK-nmilirt MDU-SC PORTABLE HOT WATER UNIT NEGATIVE AIR UNIT 030772 030773 * CRIT REF DATE LOCAXIOR 06/06/94 PROD. ROOM 5. OF 259242 tl VEHT STACK 06/17/94 H.W. OF POLY BINS 259236 HP2 SUBTOTAL: 2 OH the JOB CIA SUM1ARY with %ASBEST054 in the description 01/01/94 to 06/30/94 TYPE DESCRIPTION CONDITION MIT WHILE ENPTYING CONTENTS OP ASBESTOS GASKET CAN I POUND SCRAP POLY IN BOTTOM or CAN. CONDITION MIT POUND PAPER AND PLASTIC TRASH IN AN ASBESTOS GASKET CAN. 04/17/94 BUILDING 353 247662 06/06/94 WILDING 354 259241 LP1 SUBTOTAL: 2 CONDITION MIT I NOTICED THAT AN EMPLOYEE WAS USING AN ASBESTOS BAG TO CARRY HIS TOOLS AND EQUIPMENT AROUND WITH HIM. CONDITION ran WHILE CHECKING ASBESTOS CANS FOR GASKETS I NOTICED THE CAPS ON THE EYE BATH WERE OFF. 01/19/94 SCREEN PACK BURNER 230582 06/17/94 SCREEN PACK BURNER 247676 LPlF SUBTOTAL: 2 CONDITION MNT "ASBESTOS GASKET ONLY" DISPOSAL CAN HAD LID OPEN. THE CAN SEEMED TO HAVE BEEN RUN INTO OR KICKED IN, THEREFORE NOT ALLOWING LID TO SEAL. THE CAN IS EMPTY WITH A NEW LINER. CONDITION MNT FOUND WIRE AND TRASH IN AN ASBESTOS GASKET CAN. 06/06/94 G--500 REACTOR 246600 LP1R SUBTOTAL: 1 CONDITION MIT I FOUND NON-ASBESTOS INSULATION IN AN ASBESTOS GASKET CAN. 06/06/94 BUTYLS TANK FARM 259229 06/17/94 BUTYLS TANK FARM 259237 ODU SUBTOTAL: 2 CONDITION MNT I POUND METAL OBJECTS AND TRAHS IN AN ASBESTOS GASKET CAN. CONDITION MNT I POUND FIBERGLASS INSULATION IN AN ASBESTOS GASKET CAN. 01/05/94 SEPARATIONS 255083 CONDITION MIT SAW SOME ASBESTOS ON THE FLOOR 01/24/94 FURNACE REPAIR SHOP 230352 CONDITION MIT THERE HAS AN ASBESTOS GASKET CAN WITH NO TOP ON IT 02/18/94 W. SIDE 246725 CONDITION M9T WHILE CHECKING SCAFFOLD I NOTICED SOME UNIDENTIFIED INSULATION ON THE DECK WE SUSPECTED IT TO BE ASBESTOS. 02/22/94 N. SIDE BOILER 22 246727 CONDITION MIT FOUND WRAPPING SUSPECTED TO BE ASBESTOS HANGING FROM OLD TUBING 02/22/94 E. WALKWAY SECOND 230746 LEVEL CONDITION MIT OUTSIDE CONTRACTOR WENT UNDER ASBESTOS BARRICADE. 030774 03/22/94 WEST Of MKP TANK 247854 04/29/94 E. Of 501 248590 OL2 SUBTOTAL: 7 CONDITION nn NOTICED SOME INSULATION ON THE GROUND, THAT COULD BE ASBESTOS. CONDITION wr I NOTICED WAT APPEARED TO BE ASBESTOS INSULATION LAYING ON THE GROUND. 01/06/94 SOOTH SIDE WALKWAY 255113 CONDITION HNT ASBESTOS INSULATION ON WALKWAY. COULD NOT SEE WHERE IT CANE FROM. 01/31/94 SOOTH SIDE *1 OXIDE 193577 CONDITION MNT WHEN I WAS DOING OUR MONDAY MORNING CLEAN UP I NOTICED SOME INSULATION ON THE GROUND. I WERT FOR A BETTER TOOK AND FOUND IT TO BE ASBESTOS. OXI SUBTOTAL: 2 06/08/94 BUILDING 11 259231 FPU SUBTOTAL: 1 CONDITION MIT WHILE CHECKING ASBESTOS CAMS FOR GASKETS I FOUND ASBESTOS CAN HAD BEEN THROWN IN METAL BIN. 06/06/94 WELD SHOP SPOT 24 246601 06/08/94 WELD SHOP 259235 SHOP SUBTOTAL: 2 CONDITION MIT I FOUND STYROFOAM IN AN ASBESTOS GASKET CAN WHEN CHANGING LINERS. CONDITION MWT THE ASBESTOS GASKET CAN USUALLY LOCATED HERE WAS MISSING. 06/07/94 DECONTAMINATION 263085 TRAILER CONDITION MNT FOUND THAT SOMEONE HAS BEEN STEALING OUR WASHING LIQUID ITS NOT A GREAT LOSS BUT ITS STARTING TO HAPPEN MORE OFTEN TJHIS TIME WE HAVE RECOGNIZED THAT THIS INDIVIDUAL IS ALSO GOING INTO OUR DIRTY ROOM WHICH IS CONCIDERED CONTAMINATED WITH ASBESTOS UNTIL COMPLETELY CLEANED. 06/06/94 306 EAST 259230 CONDITION MIT I FOUND ASSORTED TRASH IN AN ASBESTOS GASKET CAN. 06/08/94 S. SIDE HIGH BAY 259238 AREA CONDITION MNT FOUND AN ASBESTOS GASKET CAN WITH PLASTIC CUPS IN IT. 06/08/94 INSIDE CONTROL ROOM CONDITION MNT 259234 02 UNIT I FOUND PAPER TRASH INSIDE AN ASBESTOS GASKET CAN. UNSP SUBTOTAL: 4 GRAND TOTAL: 25 030775 CRIT REF DAZE U3CAZION 07/38/94 N. SIDE OP DOCK 259495 FROM PIPERACK BDK SUBTOTAL: X ON the JOB CIA SUTIARY with %Asbstost in the description 06/01/94 to 12/31/94 TYPE DESCRIPTION CONDITION WIT I POUND SODA CANS AND TRASH IN AN ASBESTOS GASKET CAN. 06/06/94 PROD. ROOM S. OF 259242 11 VEST STACK 06/17/94 B.W. OF POLE BINS 259236 HP2 SUBTOTAL: 2 CONDITION HIT WHILE EMPTYING CONTENTS OP ASBESTOS GASKET CAN I POUND SCRAP POLY IN BOTTOM OP CAN. CONDITION MNT POUND PAPER AND PLASTIC TRASH IN AN ASBESTOS GASKET CAN. 06/06/94 BUILDING 354 259241 LP1 SUBTOTAL: 1 CONDITION MNT WHILE CHECKING ASBESTOS CANS FOR GASKETS I NOTICED THE CAPS ON THE EYE BATH WERE OFF. 06/17/94 SCREEN PACK BURNER 247676 LP1F SUBTOTAL: 1 CONDITION MNT POUND WIRE AND TRASH IN AN ASBESTOS GASKET CAN. 06/06/94 G-500 REACTOR 246600 LP1R SUBTOTAL: 1 CONDITION WIT I FOUND NON-ASBESTOS INSULATION IN AN ASBESTOS GASKET CAN. 06/06/94 BUTYLS TANX FARM 259229 06/17/94 BUTYLS TANK FARM 259237 ODU SUBTOTAL: 2 CONDITION WIT I FOUND METAL OBJECTS AND TKAHS IN AN ASBESTOS GASKET CAN. CONDITION WIT I POUND FIBERGLASS INSULATION IN AN ASBESTOS GASKET CAN. 09/06/94 N.W. CORNER OF 260415 COOLING TONER 09/07/94 GAS-2 MAINTENANCE 261935 SHOP OL2 SUBTOTAL: 2 CONDITION WIT EXPOSED INSULATION WHIOI IS MARKED ASBESTOS. CONDITION WIT SOMEONE PUT TRASH IN AN ASBESTOS CAN. 06/08/94 BUILDING 11 259231 PPU SUBTOTAL: 1 CONDITION MNT WHILE CHECKING ASBESTOS CANS FOR GASKETS I FOUND ASBESTOS CAN HAD BEEN THROWN IN METAL BIN. 06/06/94 WELD SHOP SPOT 24 246601 CONDITION MNT I FOUND STYROFOAM IN AN ASBESTOS GASKET CAN WHEN CHANGING LINERS. 030776 06/08/94 MELD SHOP 259235 12/13/94 BUILDING 165 266013 SHOP SUBTOTAL: 3 CONDITION nrr THE ASBESTOS GASKET CAN USUALLY LOCATED HEBE HAS HISSING. CONDITION MIT PARTS OF ASBESTOS GASKET ON FLANGE FACE OF VOLATE. 06/07/94 DECONTAMINATION 263085 TRAILER CONDITION MIT FOUND THAT SOMEONE HAS BEEN STEALING OUR WASHING LIQUID ITS NOT A GREAT LOSS BUT ITS STARTING TO HAPPEN MORE OFTEN TJH1S TIME HE HAVE RECOGNIZED THAT THIS INDIVIDUAL IS ALSO GOINS INTO OUR DIRTY ROOM WHICH IS CONCIDERED CONTAMINATED WITH ASBESTOS UNTIL COMPLETELY CLEANED. 06/06/94 306 EAST 259230 06/08/94 S. SIDE HIGH BAY 259238 AREA 06/08/94 INSIDE CONTROL ROOM 259234 02 UNIT CONDITION mr I FOUND ASSORTED TRASH IN AN ASBESTOS GASKET CAN. CONDITION mr FOUND AN ASBESTOS GASKET CAN WITH PLASTIC CUPS IN IT. CONDITION mr I FOUND PAPER TRASH INSIDE AN ASBESTOS GASKET CAN. 07/10/94 SOUTH or 02 UNIT 260317 CONDITION mr POUND TRASH IN ASBESTOS CAN. NOT FOR TRASH. THE ASBESTOS CAN ARE FOR ASBESTOS GASKETS ONLY UNSP SUBTOTAL: 5 GRAND TOTAL: 19 030777 * CRIT REP DATE LOCATION 01/23/95 BLDG. 165 267470 NIT SUBTOTAL: 1 04/19/95 OLEFINS 267293 0L2 SUBTOTAL: 1 GRAND TOTAL: 2 Oil th* JOB CIA SUtlAKY with tAsbastos* in th* description 01/01/95 to 12/31/95 TYPE CONDITION MNT ASBESTOS GASKET OH FLANGE. DESCRIPTION CONDITION LEE YAKLIN NIT Found asbestos tubing wrap in domestic trash can. 030778 I OUT RET DATE LOCATION 05/19/89 B327 105144 CSD SUBTOTAL: 1 ON the JOB CIA SIMtARY with 4ASBESTOS8 in the description 01/01/89 to 12/31/89 TYPE DESCRIPTION CONDITION TOMAS ROSARIO CSD Builiding 327, sro using asbestos sheet to cover the awning ceiling. some building in EMS are using it for cover on outiside of building. Also, 08/11/89 OOCXFRONT MARINE 143913 TERMINAL DIS SUBTOTAL: 1 CONDITION ROBIN LCM1AN DIS Insulators reaoved asbestos insulation froa acetic acid unloading pot on 8/7 and 8/8. On 8/11 I went down to the systen and found asbestos pieces in area that had not been cleaned up and properly disposed of. 04/10/89 138260 05/08/89 COGEN 115761 08/03/89 MWT BLDG 154556 08/10/89 148687 08/16/89 148651 12/19/89 155082 ENS SUBTOTAL: 6 CONDITION LOUIE XRAMER MNT Asbestos gaskets on floor of Maint shop in ENS. CONDITION GORDON BEATTY MNT 8* asbestos gasket on the ground. CONDITION MIKE HARD MNT Asbestos gasket storage area is dirty. CONDITION LOUIE KRAMER MNT Asbestos gaskets in bucket on floor of Maint. Shop. CONDITION LOUIE KRAMER MNT Roll of asbestos gasket material under shed. CONDITION LOUIE KRAMER MNT Asbestos gasket stuck to flange on pad of Maint. work area. 04/06/89 101 B 132522 08/14/89 148693 HP1 SUBTOTAL: 2 CONDITION RICK DOLEJSI MNT Paper trash in asbestos can. CONDITION LOUIE KRAMER MNT Asbestos gaskets on the floor in work area. 04/05/89 SHOP 134219 05/10/89 B560 133089 05/15/89 SHOP 134224 HF2 SUBTOTAL: 3 CONDITION RICHARD THOMPSON MNT Noticed asbestos naterial left on work table. CONDITION ANDREW VASQUEZ MNT Could not find a container to dispose of asbestos gaskets in shop. CONDITION DIANE THOMPSON SHF Asbestos gaskets on floor of shop. 04/04/89 138264 04/06/89 353 142223 CONDITION LOUIE KRAMER MNT Asbestos gaskets hanging froa storage racks, second level of Building 341. CONDITION VAN SHRADER MNT Observed a person cutting Garlock 900 asbestos gasket with tin snippers. The gasket material wasn't moistened with water and person had no respirator 030779 04/13/89 149122 04/07/89 INST. WORK SHOP 142047 06/02/89 138218 06/02/89 138219 06/02/89 138220 06/19/89 148664 08/09/89 148685 09/12/89 FRECURSER UNIT 121639 12/18/89 MNT SHOP 155066 12/18/89 NR SHOP 155068 LPl SUBTOTAL:: 12 on. CONDITION IRA riLLMORE JR KMT Equipment uid air handling room at B353 being usad as a storaga room, including two larga rolls of asbestos gasket material. CONDITION TOMQE HOLT JR MNT I found an asbastos gaskat, by tha telephone in tha shop. CONDITION LOUIE KRAMER NR 20* asbastos gaskat in fibar drum that was full of othar typas of trash locatad undar 1750 raactor. CONDITION LOUIE KRAMER NR Asbastos gaskat hanging on storaga rack on tha aast sida of sacond laval B341. CONDITION LOUIE KRAMER HR Usad asbastos gaskat on valva dalivary/storaga rack locatad north wast comar of LF1 block. CONDITION LOUIE KRAMER HR Naw and usad asbastos gaskats laft on work banch in Maint. shop LP1. CONDITION LOUIE KRAMER MNT Asbastos gaskat on workbanch in Maint. Shop. CONDITION ANN THOMASON MNT Garlock asbastos gaskat fro* haxana siava at pracursar unti thrown down on tha ground. CONDITION LOUIE KRAMER NR Asbastos gaskats in 10 Qt. galvanizad buckat. CONDITION LOUIE KRAMER MNT Cabinat drawer opan exposing asbastos gaskat aatarial. 04/03/89 LP1R 142386 07 08/11/89 BLOCK 12 156814 10/17/89 345E, G-MDC 146568 10/31/89 2ND LEVEL CAT BINS 156677 LF1R SUBTOTAL: 4 CONDITION CRAIG STRAK0S MNT Found two 899 asbastos gaskats laying on grating. wash water lines. Construction was removing INCIDENT JESSE TIJERINA LP1 In tha process of revising utility drops to comply with plant policy, 75# steam utility drop piping broke upstream of isolation valve. The utility drop piping fell to the ground. Several pieces of insulation broke off and fell to the ground. Portions of the insulation on tha piping were asbastos. CONDITION JAMES MEISCHEN HR Has cleaning up work area and noticed two asbastos gaskats laying beside an I-beam. INCIDENT JOHN OSWALT SHT Discovered maintenance removing asbestos from pipe in area. had not notified myself or Tech, staff of this area. These workers 06/13/89 148799 11/26/89 GROUND LEVEL 14 2 149280 COMP LP2 SUBTOTAL:: 2 CONDITION MARK SCHROLLER NR Asbestos gaskets laying on table in control room. CONDITION GEORGE DANDY SHT The drua located on the ground level between the 81 a 82 compressor marked for asbestos material and gaskats only has baan usad for other material. Tha bottom of tha dura is rusted out and tha lid is missing. Material is in a reinforced plastic bag and contained. 12/12/89 B1 CAFETERIA CONDITION DAVID LUGO MNT 030780 150180 MISC SUBTOTAL: 1 Pound a 3/8* drinking water lina used to sarvica icemaker with asbestos taping. 03/30/89 STORES 139108 04/17/89 SKEETHKS RACK 138989 05/31/89 140-1 148917 06/07/89 140-1 148909 07/10/89 140-1 148901 08/22/89 510 SIOUXS 153760 08/30/89 B9 158716 10/30/89 B-140-1 158742 NS) SUBTOTAL: 8 CONDITION CARL BOSIER WD Employee noticas asbastos material was removed from it's plastic containar. CONDITION EPRAIN GUERRA fWD 1 roll of 1/6' 10'xlO' coda 428794-113 is not protactad with a shaat or labalad with tha containars asbastos tag. CONDITION CARL BOSIER MV3 Asbastos gaskat notarial not in plastic containar, had baan raaovad. CONDITION CARL BOSIER MMD Asbastos aatarial not in it's plastic protactiva covar. CONDITION CARL BOSIER H4D Found asbastos gaskat aatarial shaat laft unwrappad not in plastic containar to containar asbastos dust fibar. CONDITION WILLIAM INFANGER PPU Notica insulatad pipas ovarhaad of kaypunch oparator at tha antranca. pipas appaarad to ba asbastos. Tha CONDITION CARL BOSIER WD Noticad wood that had containad asbastos gaskat, but was raaovad, parsonnal raaoving gaskat laft scrap boards, cardboard with nails in upright position. CONDITION CARL BOSIER WD Asbastos shaating aatarial was not in plastic wrap or containar to contain asbastos dust fibars. 03/30/89 ASB WASH PAD 117126 ' CONDITION WILLETT NEILL MNT Found asbastos gaskats on wash pad. 04/03/89 140-2 SOUTH 135445 -CONDITION KEITH HAHN MNT two hosas with 1504 flangas wara found on tha south sida of tha Ttl shop without a shipping tag, no work request, and 2 asbestos gaskats on the flangas. 03/30/89 SPRAY GAS COOLER 2 135902 CONDITION BSR I assigned 2 nan to scrape asbastos gaskats, without Baking sura they had baan trained in tha hazards of AsB dripolene and without Baking sura they usad tha facilitas at B304 to prevent contamination of their clother and boots. 03/30/89 ASB DRIP PAD 127586 CONDITION BSR I noticad a couple of gaskats possibly asbastos, plant poly requires that tha reaoval of all asbastos ba dona with special precautions by trained individuals. Halliburton whoa is working on ths pad should ba informed about tha situation. 03/31/89 380 135916 CONDITION BSR Want to clean out asbastos gaskat cabinet and found used and broken up gaskets laying on tha top of tha cabinet and on tha floor under it. 04/07/89 141097 LANDFILL NON HAZ PIT CONDITION ED HEISOLD MNT Truck hauling roll off bins to landfill had bad sida on box. Tha box broka open at tha bottom along sida of Bin casuing plastic bag to tear open when unloading Bin exposing asbastos contaminated fum brick to tha air. 04/18/89 B306 138245 CONDITION LOUIE KRAMER MNT 20* asbastos gaskats on floor in storage area of Maint. Shop B306. 04/20/89 INSTRUMENT SHOP 127655 CONDITION LUPE RODRIGUEZ MNT Vee--ball valve/body was sant to tha instrument shop. (contains asbastos) had not baan removed. Valve flange gaskats 03078 J 04/24/89 B160 138238 CONDITION LOUIE KRAMER NR Asbastos gaskets stuck to pip* flangas on pip* schadulad to go to salvaga. 04/24/89 B101 135912 CONDITION BAR Can full of asbostos and ragular trash without a disposal bag insida of can. Can was claarly narkad asbastos gaskats only. 04/25/89 MELD SHOP 147438 CONDITION BOYD BLAKE MNT A coaprassor aufflar was brought to tha Wald Shop with a asbostos gaskat still on tha glanga. 04/24/89 B101 135912 CONDITION BAR Can full of asbastos and ragular trash without a disposal bag insida of can. Can was claarly narkad asbastos gaskats only. 04/24/89 HELD SHOP 147437 CONDITION LARRY HERRON NR Mufflor nanway had a gaskat laft on, gaskat was asbostos notarial. 04/24/89 TfcX 134204 CONDITION JOSEPH DAILEY NR Hhilo ranoving a safaty valva from sona aquipnant that is out of sarvica, savaral asbastos gaskats all around tha araa. 05/08/89 PIMP REPAIR SHOP 144610 CONDITION BAR Want to onpty asbostos gaskat can, found can full without asbostos disposal bag insida. 05/26/89 LP1 135509 CONDITION BOB KALICK NR Bolts, nuts, loosa objacts, torn asbastos insulation, on top of pantana coluan. 06/05/89 REPAIR SHOP 121959 CONDITION DAVID DENTLEK HR Asbastos gaskat was laft on punp flanga. 06/08/89 INST SHOP 146472 CONDITION BURL HENSLEY JR MNT A 3-way valva caaa to tha shop to ba ovorhaulad, had asbastos gaskats on tha flangas. 06/23/89 NTT 150507 CONDITION BOB TATE JR MNT Sonaona laft a pipa spool with an asbostos gaskat stuck on flanga at WTF-low truck loading spot. 08/01/89 PF RIG SHOP 154520 CONDITION MIKE WARD MNT Asbastos storaga naads claanup. 08/01/89 REPAIR SHOP 154519 CONDITION MIKE WARD MNT Asbastos storaga araa naads claanup. 148522 TU CONDITION BOB TESQt MNT Asbastos cabinat contains nisc. aatarial and dirty. 08/15/89 TAI SHOP 138508 CONDITION BOB TESCH MNT Gaskats in various cabinats ara thay asbastos? 08/17/89 PROJECTS CREW SHOP 148663 CONDITION LOUIE KRAMER NR Asbastos packing in parts storaga bin in projact craw shop. 08/09/89 MAHR. STORAGE BLDG CONDITION BAR 146576 Found chunks and piacas of asbastos on pad. 08/21/89 PROJECT (SEW SHOP 154617 CONDITION MIKE WARD MNT Asbastos storaga cabinat naads claanup. 09/01/89 LAYDOWI TARO 154771 CONDITION LOUIE KRAMER MNT Asbastos gaskat on 8" drillad flanga in HP2 storaga rack. 09/01/89 LAYDOWH YARD 154772 CONDITION LOUIE KRAMER MNT Asbastos gaskats on pallat south sida of alactrical storaga containars. 09/01/89 LAYDCMI YARD 154768 CONDITION LOUIE KRAMER NR Asbastos gaskats stuck to vacuua sats on pallat in ODU. 09/01/89 LAYDOWN YARD 154761 CONDITION LOUIE KRAMER MNT Asbastos gaskats stuck to valva flangas north sida of LP araa. 030782 09/18/89 INST SHOP 110567 09/18/89 REPAIR SHOP 152882 09/28/89 REPAIR SHOP 152883 10/19/89 LAYDOHi YARD 150569 10/10/89 PROD ROOM 150863 10/17/89 154955 11/01/89 INST SHOP 110557 11/08/89 163 S 155125 12/06/89 REPAIR SHOP 156325 12/06/89 REPAIR SHOP 156326 : 40 03/21/89 GEU 114693 04/06/89 GEU 114694 04/05/89 135365 04/14/89 135501 05/04/89 GEU 138227 05/04/89 138228 06/07/89 150690 06/13/89 150687 07/10/89 BUTYLS 146547 07/20/89 B367 156705 07/10/89 B367 156706 08/15/89 148650 08/15/89 148694 CONDITION GLENN WISE MNT Slid* gat* valva came to shop with asbastos gaskat on flanga. INCIDENT RAYMOND HILL JR MNT Pound asbastos gaskat on pump flanga that was dalivarad to rapair shop. CONDITION RAYMOND HILL JR MNT Asbestos gaskat was laft on pump flanga. CONDITION BUD DAVIS MNT Found asbastos gaskat on haat exchanger in laydown yard exposed. CONDITION FRENOIIE CORMIER MNT I found a 1 t 3 inch flaxitallic asbastos filled gaskat on top of tha pollster water box. CONDITION MIKE WARD MR Asbastos gaskat storage area needs cleanup. CONDITION GLENN WISE MIT Valve cane to shop with asbastos gaskets still on flange surfaces. CONDITION LARRY KNEBEL MNT Found asbastos gaskets on fuel valva, sent to Inst. Shop from 0L2. CONDITION DARRYL LYNCH MNT Punp was sant to rapair shop with asbastos gaskat still on flange. CONDITION RAYMOND HILL JR MNT Asbastos gaskat still on discharge flanga of punp. CONDITION DICK SCHNEIDER MNT Found asbastos gaskat on pipe construction removed, CONDITION DICK SCHNEIDER MNT Found asbestos gaskat on the pad. CONDITION BB BROWNING MNT Asbastos gaskat was laying on the ground by refining column calandria. CONDITION BOB KALICH MNT Found asbastos gaskets on th* ground and in structure. CONDITION LOUIE KRAMER MNT Asbastos gaskets on concrete pad in Maint work area. CONDITION LOUIE KRAMER MNT Asbastos gaskets tiara in regular trash can in ODU Maint. Shop. CONDITION BB BROWNING MNT Used asbastos gaskat was laying on th* ground. CONDITION BB BROWNING MR Foudn asbastos gaskat laying beside th* work bench. INCIDENT WAYNE JACOBS SHF Hhil* removing asbastos in tha ODU area an outside contractor had an epileptic saisur*. CONDITION LEE YAKLIN MNT Sheet of asbastos gaskat material in dumpster. CONDITION LEE YAKLIN MNT Maint shop cage needs sign on cage warning that asbastos gaskets are stored inside cage. CONDITION LOUIE KRAMER MNT Asbastos gaskat scraps on east sawar pump. CONDITION LOUIE KRAMER MNT Asbastos gaskets on the ground. 030783 09/18/89 GEU 150634 09/18/89 GEU 150628 10/18/89 150604 10/20/89 150551 11/29/89 150540 12/11/89 150531 12/18/89 MORE AREA 155069 12/18/89 GEU 155070 QOU SUBTOTAL: 21 CONDITION BB BROWNING WT An asbestos gasket was laying on the ground. CONDITION BB BROWNING wr L*borar found a valva that had insulation raaovad off it and appaarad to ba asbestos material laying on the ground. CONDITION BB BROWNING tffTT Found asbestos gasket laying on ground whare equipment had been scraped. CONDITION BB BROWNING MNT Asbestos gasket laying on tha ground. CONDITION BB BROWNING mr Found a asbestos laying in unit trash barrel. CONDITION BB BROWNING HIT Asbestos gasket was stuck to a pipe flange. CONDITION LOUIE KRAMER HR Asbastos gaskat on pad. CONDITION LOUIE KRAMER MNT Used asbestos gaskets on grating at switch station. 04/18/89 138244 04/18/89 138243 04/18/89 138241 05/02/89 CONTROL ROOM 142303 08/17/89 306 SHOP 155201 OL1 SUBTOTAL: 5 CONDITION LOUIE KRAMER NIT Asbestos gaskets scattered on the ground by the Methanol tank on the east side of 41 Olefins. CONDITION LOUIE KRAMER MNT Two plastic sacks of bolts and asbestos gaskets on the ground my Methanol tank located on the eastside of 41 Olefins. CONDITION LOUIE KRAMER MNT Asbestos gaskets on ground and on pallets inside fenced in area across road south side of 41 Olefins. CONDITION DARRELL BAILEY NIT While waiting for operator to issue HWP noticed what appeared to be asbestos insulation uncovered above panel board. CONDITION ERNEST DEHOYOS MNT Found metal lugger bin with instruaent tubing still wrapped with asbestos tape wrapping. 04/07/89 COMPRESSOR BUILDING 146281 CONDITION ERNEST GARCIA NIT As you walk inside the NE door of the compressor building ther is a steam drop with asbestos insulation that is exposed. 04/12/89 81 PRECOOLER - TOP 146300 LEVEL CONDITION ERNEST GARCIA NfT Found sob 1/2* pipe on the top level of 41 Precooler. this, is that the pipe had asbestos insualtion on it. What' s so bad about 04/18/89 FURNACE AREA 146336 CONDITION BILL FOX JR HIT While preparing to transport two motor valves to the instruaent shop, I suspected that they had asbestos gaskets on the flanges. 04/18/89 OLEFINS FLARE 138248 CONDITION LOUIE KRAMER MNT Asbestos wrapped around insulation on ground by flare separator pot. 04/18/89 138250 CONDITION LOUIE KRAMER HIT Asbestos packing in Maint storage rooa north end of coopressor building. 04/18/89 138249 CONDITION LOUIE KRAMER MNT Bulk asbestos gasket material in storage cage in 42 olefins Maint shop. 05/02/89 422 BOILER CONDITION LOUIE KRAMER HIT 030784 136233 05/10/89 SPRAY GAS POOLERS 146384 05/12/89 SEPARATIONS 137541 06/21/89 SEPARATIONS 117156 07/05/89 SEPARATIONS 117154 07/17/89 148679 08/18/89 SEPARATIONS 156513 09/25/89 500N 156770 11/03/89 MAINT SHOP 162416 11/06/89 B500 117130 11/15/89 WEST or BLDG. 500 162429 12/11/89 B500 162439 : 18 Used asbastos gaskats on concrata pad. CONDITION TED NELSON MNT Asbastos gaskats in donastic trash barral. CONDITION JERRY DELGADO MWT Asbastos gaskats on ground by 12 C2H2 still. CONDITION JERRY DELGADO MNT Asbostos gaskats insida trash can locatod north and saparations. CONDITION ERNEST GARCIA MNT Asbastos insulation on tha ground. Had fallan out of piparack. CONDITION LOUIE KRAMER MNT Asbastos gaskat scrap aatarial laft on work banch in #2 Olafins Maint. Shop. CONDITION LARRY KCHALIK SHT Insulation on piping around II drip still is datarioratad badly and falling. Sosa insulation is on abandonad piping and aay contain asbastos. CONDITION LEE YAXLXN MNT Racaivad a larga ordar of gaskats froa storas, many diffarant itaas with savaral asbastos gaskats includad with non-asbastos gaskats. No warning as to contants and asbastos gaskat not individually wrappad. CONDITION WILLETT NEILL MNT Asbastos gaskat (usad) on tabla in Maint. Shop. CONDITION WILLETT NEILL MNT Found savaral asbastos gaskats on tha ground naar aftar coolars araa. CONDITION WILLETT NEILL MNT Found asbastos gaskat on ground. CONDITION WILLETT NEILL MNT Found asbastos gaskats on pallat. 04/12/89 81 BIOCE 138254 04/14/89 B120 133873 04/13/89 130363 04/25/89 UNIT 150791 05/10/89 140945 07/10/89 12 148670 07/11/89 *2 148673 07/11/89 *2 148674 07/12/89 12 148675 81 07/08/89 144852 CONDITION LOUIE KRAMER MNT Asbastos gaskat on pallat with IGT parts storad in naw building at II Glycol. CONDITION BUDDY PERKINS MNT Found asbastos shaat in stora room. CONDITION CHARLIE ZIRKELBACK MNT Saw 2 Flaxitalic gaskat on north nail rack of OXI that appaarad to ba asbastos fillad. CONDITION RICK CURTIS OXI Cabla trays hava what looks lika asbastos insulation shaats undar than. insulation is not ancapsulatad andis braaking off in savaral placas. ~ Tha CONDITION ALEX MARTINEZ JR MIT Construction knockad off sona asbastos insulation fron cabla trays. CONDITION LOUIE KRAMER MNT Asbastos gaskat laft on top of pre-haatar locatad north and of air building. CONDITION LOUIE KRAMER MNT Asbastos gaskats on top convartor laval grating. CONDITION LOUIE KRAMER MNT Asbastos gaskats on pad undar FI & F2 convartors. CONDITION LOUIE KRAMER MNT Torn up asbastos gaskats on ground by BAC pracoolar. INCIDENT B4R Construction insulation craw was stripping insulation froa 8" staaa lina 0307*5 that was still in sarvica. Upon seeing tha insulation Gan. Foraaan inquired whether insulation night contain asbestos. After performing an eapirical test, a good possibility was that insulation contained asbestos fibers. 07/30/89 82 148683 CONDITION LOUIE KRAMER MNT Asbestos gasket stuck to blind flange located on pallet of blind flanges north side of 82 Oxide. 07/17/89 140937 CONDITION MARTY MARTINEZ MNT Asbestos insulation ws knock off. Cable tray between B2 and B3 scrubbers. 08/06/89 82 PURIFYING COLUMN 153624 AREA CONDITION RJ TRIPP SHF Found some asbestos on the pad. A lot of damage has been done to the unit cable tray shields during hte recent shutdown. Small chunks of this material has fallen to the ground level. 08/04/89 140599 CONDITION PAUL MOYA JR SHF Several small pieces and some dust of asbestos insulation were found on pad west of B1 converter. 08/08/89 82 148684 CONDITION LOUIE KRAMER MNT DMU from 82 oxide shutdown left on the ground north end of Air Compressor Building, has an asbestos gasket stuck to the flange. 09/27/89 140910 10/26/89 LAYDCMIYARD 140893 CONDITION MARTY MARTINEZ MNT Found asbestos gasket laying on ground under south pipe rack Oxide I. CONDITION MARTY MARTINEZ MNT Equipment was sent to laydown yard with asbestos insulation. 10/25/89 STORAGEBUILDING 154781 CONDITION LOUIE KRAMER MNT Trash can with asbestos gasket scraps located in south end Oxide storage buidling. OXI SUBTOTAL: 18 10/30/89 136706 FLE SUBTOTAL: 1 CONDITION ANDREW ENGELS PLE Instructor for safety training - Asbestos Awareness. 04/04/89 POLYPROPYLENE 132306 CONDITION TOM TOLER MNT Found three asbestos gaskets stuck on the flanges that were removed from service and temporarily stored. 05/18/89 132562 CONDITION TOM TOLER MNT Asbestos gasket still on flange that had been removed from service. 06/15/89 5 PRESS BLOWER 134339 CONDITION JAMES MORGAN SHF Line insulated with waht was labeled asbestos, casing was missing in several places and the insualtion was deteriorating. 07/25/89 132703 CONDITION ARMANDO GARCIA KIT Found several asbestos gaskets hanging on ladder rack. ( used) 08/02/89 JOINT BLDG 154538 CONDITION MIKE WARD MNT Asbestos storage cabinet not labeled, and dirty. 08/23/89 MAINTENANCE BUILDING CONDITION MIKE HARD MNT 154631 Asbestos gasket storage cabinet - no label - not clean. 10/12/89 SOUTHSXDE MIT BLDG 154931 CONDITION MIKE WARD MNT Asbestos gasket storage cabinet needs cleanup. 12/19/89 155085 CONDITION LOUIE KRAMER MNT Several 4" asbestos gaskets under workbench FPU unit. FPU SUBTOTAL: 8 GRAND TOTAL: 151 030786 8 OUT REF DATE LOCATION 05/03/90 H3C WASH FACILITY 163682 04/30/90 INSIDE BLDG. 3S0 139363 DIS SUBTOTAL: 2 ON the JOB CIA SUM1ARY with kAsbestos* in the dascription 01/01/90 to 12/31/90 TYPE DESCRIPTION CONDITION LOUIE KRAMER MNT 8' asbestos gasket on the ground just outside KX wesh facility. CONDITION WES ZEPLIN DIS Found asbestos gasket material in regular trash can. Also suspect other gasket in can night be asbestos. Also suspect asbestos gaskets are being stored with asbestos - free gaskets. 01/19/90 CHF STORAGE CAB 116031 CONDITION WILLIE BROMf JR MR Asbestos gasket stored in cabinet, also oily rags. 03/28/90 21 & 22 BOILERS 168761 CONDITION JOHN SIMONS MR Busted lines of asbestos all around boilers. 04/25/90 COGEN 164028 CONDITION EDDIE STEVENS MNT Asbestos gasket laying on ground by NR valve. 04/23/90 SW CORNER 11 STEAM 155406 PLANT INCIDENT BAR Pipefitter working on steam tracing laak removed insulation wrap from tubing. Wrap was asbestos tape. Fitter was unaware of the wrap being asbestos. 05/02/90 12 FIRE WATER PUMP 168594 TURB CONDITION RANDY LAMPREOJT MNT Noticed staaa piping going to 82 fire water pump turbine had asbestos insulation on it. 07/25/90 SOUTH OF BLDG. 327 168731 CONDITION ROBERT GOSSETT MNT Found 4 pieces of 3/8" copper tubing wrapped with insulation (some asbestos) in natal lugger bin. ENS SUBTOTAL: 6 04/16/90 KP1 132708 09/23/90 SOUTHEAST DOOR AND 174171 WALKWAY HP1 SUBTOTAL: 2 CONDITION TOM TOLER MNT Found asbestos gasket on second level of additive bldg that had been left after a job. CONDITION ROBERT MORGENROTH SHF Two 'out of service' steaa lines leaking asbestos insulation into area. Lines were started taking out of unit about 1 year ago, but never finished removing. 09/25/90 BUILDING 11 186902 HF1PF SUBTOTAL: 1 CONDITION ARMANDO GARCIA MIT Two blind flanges in back of pickup truck with asbestos gaskets still stuck on then. 11/08/90 KR2 195127 76 11/08/90 HF2 196059 CONDITION BLR While removing asbestos gaskets in cell block no. 1, operator entered barricaded area and clinbed up to where I was working to check on flanges I was scraping. ACCIDENT BAR I had my asbestos tools in ny bucket, I took out ay pouch and ny knife fellout; at that point I reached in ny bucket to retrieve the knife not 030787 11/16/90 KPII 195101 BP2 SUBTOTAL: 3 noticing y hook knife. It cut ay thuab ont ho first joint. CONDITION But Outsido contractor aaployso walkad through an asbestos barricade. 02/05/90 G3 BLENDER 142403 CONDITION JAMES MEISOffiN MNT Two used asbestos gaskets laying by G3 blender. 02/20/90 G17 142402 CONDITION EDDIE MOYA MNT Pipe with exposed asbestos insulation at oil pit. 05/10/90 BLOCK 12 157251 CONDITION JERRY FYKA SOT There is what appears to be asbestos wrap on tubing leads going to a couple of instruments just south of the main C2H4 header emergency valve. 06/12/90 NOT OGMFOUNT HC-2 166484 AREA CONDITION FAT DUNLAP MNT A flange on the 6001b. steaa header has a bad leak, and it blew off the insulation material which is asbestos. Insulation. 08/04/90 G-17 COOLER ROOF 173482 AREA CONDITION JOHN BRADLEY NIT While removing old walkways I found an asbestos gasket. 08/08/90 BULK 25 173478 CONDITION VAN SHRADER MNT While clean up unit grounds I found three asbestos gaskets on ground. 08/13/90 345 EAST 173477 CONDITION JAMES MEISCHEN NIT Found 1 1/2* pipe that had been removed from pipe rack with 2 asbestos gaskets still on the flanges. 09/12/90 G-1750 173463 CONDITION JAMES MEISCHEN MNT I was taking measurements for a sketch when I found an asbestos gasket on a beam. 10/01/90 PENTANE COLUMN 173363 CONDITION DONNIE MAREK MNT While working on pentane column I noticed some exposed asbestos insulation. 10/17/90 LP1 186261 CONDITION BLR The insulators had put up a barricade tape saying "danger, asbestos'. hte area that they had barricaded off was very small and the wind was blowing slightly. But 12/02/90 ODU OLD POLY REACTOR CONDITION JOHN BRADLEY MNT 104607 Found exposed asbestos in pipe rack at old Poly-0Is reactor. LP1 SUBTOTAL: 11 02/28/90 B344 148994 04/16/90 LPI CAT AREA 168468 04/20/90 BLOCK 25 BLDG 444 149001 04/26/90 G5 REACTOR 168439 05/07/90 TOP OF G 1750 168493 REACTOR 06/20/90 E/W PIPE RATE WEST 171855 SIDE BLD 1 10/03/90 LFl REACTION 191798 CONDITION LARRY CA5DORPH MNT Asbestos gaskets laying on the ground. CONDITION CRAIG STRAKOS MNT Found flex asbestos gasket left over from other job. CONDITION LARKY CASDORFH NIT Found large number of asbestos gaskets stored in storage bldg 444. CONDITION PAT DUNLAP MNT A 75 sb steam line that is insulated with asbestos insulation has the outer covering missing and pieces of asbestos are falling off. CONDITION DONNIE MAREK NIT Found three asbestos gaskets on top level. They were deteriorating. CONDITION CHERYL ENGELS LP1 1/2* steam supply lines for steam tracing are very rusty, leaking, insulated with what may be asbestos and in one case (within reach) uninsulated. CONDITION BUI The analyzer tubing servicing G-1750 has several spots of asbestos wrap which are frayed and open to the atmosphere. 030788 LP1R SUBTOTAL: 7 08/16/90 CONTROL ROOM 170683 LF2 SUBTOTAL: 1 CONDITION CORN!LIU FANELLX MNT Whle cleaning out filing cabinet in control room, cum across an asbestos gasket and a steel choker. Neither belongs in the control room. 03/19/90 SAT FENCE 155344 MX5C SUBTOTAL: 1 CONDITION BfcR Abandoned 6" acetylene line no. 29 has exposed asbestos insulation. This line goes through the north fence and open ended. Exposed area is on south side of fence. 02/15/90 B140-1 159897 10/18/90 MEZ-1 185931 (M3 SUBTOTAL: 2 CONDITION CARL BOSXER HID Pound roll of asbestos sheeting materiel unwrapped. CONDITION JOE DELGADO JR HID round a pile of asbestos bags on floor partially in walkway. 01/17/90 REPAIR SHOP 156389 CONDITION DARRYL LYNCH MNT Asbestos gasket was left on multi-port valve. 01/22/90 B148 162783 CONDITION B&R Pound valve from surlus with an asbestos gasket stuck to the outlet flange. 01/22/90 BAR HASH PAD 155183 CONDITION LOUIE KRAMER MNT Two sections of 4" pipe have asbestos gaskets stuck to flanges. 01/24/90 REPAIR SHOP 156423 CONDITION DARRYL LYNCH MNT Pump was sent to shop with asbestos gasket on the flange. 01/30/90 DOCK 162614 CONDITION SENE WILLIAMS MNT Asbestos gasket on the ground of loading area of dock. 02/09/90 504 S HAILRACK 162504 CONDITION LEE YAXUN MNT New and used asbestos gaskets on the ground and on the rail rack. 02/08/90 REPAIR SHOP 153004 CONDITION DARRYL LYNCH MNT #2 gs sent compressor cylinder in to have liner bored, asbestos gasket was left on one of the flanges. 02/16/90 82 GAS 150876 CONDITION ROYAL MAREK MNT Pound 12 flanges where coolers have been permanently removed with asbestos gaskets still on them. 03/02/90 122 BOILER 168501 CONDITION GEORGE HEINS JR MNT Pound asbestos gasket hanging on south end of boiler and mise. ground; trash on 03/02/90 S OP MAIHT. BLDG. 161245 CONDITION MIKE WARD MNT Asbestos waste storage area dirty. 03/02/90 H SICE AIR BLDG. 161240 CONDITION MIKE WARD MNT Asbestos gasket in asbestos trailer not in bag. 03/05/90 PROJECT CREW STORAGE CONDITION LOUIE KRAMER MNT 155169 YARD Several asbestos gaskets on the ground. 03/05/90 PROJECT CREW STORAGE CONDITION LOUIE KRAMER MNT 155168 YARD Asbestos gaskets in shutdown trailer. 03/15/90 REPAIR SHOP 153088 CONDITION RAYMOND KILL JR MNT Gasket was left on suction flange of pump. (Asbestos> 03/18/90 TANK 2963 155453 CONDITION BfcR Fab cloth on asbestos insualtion, ground level has deteriorated on 3 lines 030789 and valves exposing asbestos. 03/08/90 SALVAGE YARD 155460 INCIDENT FRED BERGER MOT Contractor was raaoving traps from a surplus coluan, and tha strip gasket atarial on tha traps looked lika it may ba asbastos. 03/29/90 B148 162185 CONDITION IRA FTLLMORE JR MOT Fickad up bar of asbastos gaskat natarial that had blown off a truck. 03/28/90 REPAIR SHOP 153178 CONDITION DAVID DEOTLER MOT Asbastos packing was put in trash can naar hand wash araa. ba put in can aarkad for asbastos disposal. Asbastos is to 04/11/90 T 4 I KRAY TRAILER 148493 CONDITION BOB TESCH MOT Top of asbastos gaskat box has othar natarial storad. 04/20/90 BLD 140*2 SOOTH 162668 CONDITION ANN THOMASON MOT Spara cooprasson on trailar was brought froai laydown yard for anargancy usa. Gang box on trailar was opanad aftar arrival by T & I aachanic, loosa and brokan asbastos gaskats wara insida. 04/26/90 STANDARDS ROOM 160301 CONDITION OIARLIE JAHN JR MOT Transaction temp calibrator was sant to tha standards rooa for RM. A length of theraocouple load wira was insida tha instruaent casa. Tha insulation appeared to ba asbastos, a saaple was analysed and it tasted positive as asbastos. 04/26/90 MEZZ AREA OF INST 160300 SHOP CONDITION CHARLIE JAHN JR MOT Found roll of thermocouple lead wira containing asbastos insulation. 05/07/90 LP1 159768 CONDITION KEN DORRIES MOT Noticed asbastos insulation on tubing in pit by G 1750 reactor. 05/14/90 REPAIR SHOP 169262 CONDITION MIKE WARD MOT Asbastos storage cabinet is dirty. 06/01/90 INSTRUMENT SHOP 179221 CONDITION ROLAND VILLAFRANCA MOT While taking apart 2" jamesbury valve noticed that valve had asbastos gaskats material still on valve. 06/14/90 REPAIR SHOP 180504 CONDITION MIKE WARD MOT Asbastos storage araa not cleaned. 07/03/90 12 OLEFINS COMP. 163694 BUILDING CONDITION LOUIE XRAMER MOT 20* asbastos gaskat hanging on Pag board in Mint, bldg, no asbastos hasard sign. araa 82 olefins coop, 07/03/90 LPPE I MAIOT. SHOP 163689 CONDITION LOUIE KRAMER MOT Asbestos waste disposal drum in naint. shop at Lppe I was uncovered. 07/05/90 NEST FIELD 173700 CONDITION DON HARKED MOT Found asbastos gaskat laying on road to barge docks. 07/03/90 GEU 163691 CONDITION LOUIE KRAMER MOT Turn up asbastos gaskat on grating at switching station in GEU. 07/03/90 82 OLEFINS COMP. 163694 BUILDING CONDITION LOUIE KRAMER MOT 20* asbastos gaskat hanging on Peg board in naint. bldg, no asbastos haxard sign. araa 82 olefins conp. 07/02/90 BUILDING 148 175847 CONDITION JOSEPH DAILEY MOT Found asbastos gaskat in Northwest corner of building. feat froa an asbastos can. This was 20 to 25 07/02/90 85 HOT WATER PUMP 170438 CONDITION ERNEST GARCIA MOT This pump has exposed asbastos on piping. 07/02/90 85 COOLING WATER 170439 PUMP CONDITION ERNEST GARCIA MOT This pump has piping with exposed asbastos. 07/11/90 VACUUM DEGASSING 170492 CONDITION ERNEST GARCIA MOT South vacuum degassing pump discharge pipe has insulation exposed. asbestos. Could ba 030790 08/02/90 MAXNT. 177317 LAYDCMf YARD CONDITION LOUIE KRAMER MNT Two 8" asbestos gaskets stuck to pip* flanges in ODU equipment storage area in ant. laydown yard. 08/02/90 mt. LAYDCMf YARD 177309 CONDITION LOUIE KRAMER MNT Asbestos gaskets inside column skirt located in Oxide equipment storage area in amt. laydown yard. 08/10/90 175703 BLDG. 163 HYEKOTEST STATION CONDITION ANN THOMASON MNT Needs clean up - beans used as catch all. Countertops piled up. face shield on top of asbestos disposal can. Trash cans full. Red rags scattered. 08/05/90 WELD SHOP 147809 CONDITION TOMflf TUCKER JR MNT Head sent to weld shop froa field with asbestos gaskets. 08/27/90 GEU 176429 CONDITION BB BROWNING MNT found 2 snail asbestos gaskets laying on the ground. 08/27/90 ODU 176434 CONDITION BB BROWNING MNT An asbestos was stuck to a flange on soae old pipe that had been removed froa the unit. 09/05/90 OLEfIKS ftl 177329 CONDITION LOUIE KRAMER MNT Used asbestos gasket on pad in No. 1 Olefins. 09/14/90 BLDG. 148 STORAGE 177347 AREA CONDITION LOUIE KRAMER MNT Used asbestos gasket on exposed flange on out of service s. S. piping in storage area of building. 09/25/90 POLYPROPYLENE 177326 CONDITION LOUIE KRAMER $N blind fig. pickup. MNT with asbestos gasket stick to it in back of maintenance 09/25/90 SCAFTOLD YARD 184420 INCIDENT BLR Asbestos insulation truck. employees could fall out. The benches in back of this truck are too high, 09/26/90 164 AREA 196270 CONDITION BLR Deficiencies of asbestos deron trailer ----- 1) Soae oily substance bleeding through walls, ceilings, etc. 2) Walls and ceiling bulgeing out 3) Neg. air machine pulls dust through receptacles door 4) Door leaks whne it rains S) floors sweat under nat 6) Water runs out froa bottoa of walls 10/24/90 BUILDING 160 WEST 183251 47 CONDITION BLR Chain link fence on the west side of bldg. 160 has been repeatedly bumped and pushed by pallets causing hte fence to separate froa the poles. This in turn pushes asbestos equipment away froa fence into the path of personal trying to enter van box. 02/08/90 GEU 157916 04/20/90 AMINES 164510 05/17/90 164554 05/30/90 164491 05/29/90 164474 06/04/90 N. SURT UNIT 164468 07/20/90 ODU ACETATE UNIT 164451 CONDITION JOEY MXTSCHERLING MNT Numerous asbestos gaskets on ground where old piping was removed. CONDITION WALLY WILLIAMS MNT found asbestos gaskets on ground in amines. CONDITION BB BROWNING MNT A half of an asbestos gasket was laying on the ground. CONDITION BB BROWNING MNT Old asbestos gasket was on pipe flange laying in aetal lugger bin. CONDITION BB BRCWNING MNT Lid that goes to the asbestos gasket container was left off the barrel. CONDITION BUD DAVIS MNT Exposed asbestos gaskets on vessel stored North of surf unit. CONDITION BB BROWNING MNT Picked up a 1 1/2" asbestos gasket laying on the ground. 030791 07/20/90 ODU 360 WEST 164450 CONDITION BB BROWNING MNT Picked up a 4" asbestos gasket by crude column. 07/30/90 HAUfTEKANCE/ODU 164446 CONDITION BB BROWNING MNT An asbestos gasket was laying on tho ground whoro piping had boon removed. 08/01/90 ROADWAY SOUTH OP 367 CONDITION BUD DAVIS MNT 176447 2" 150# usod asbestos faskel lying in way. 08/01/90 ODU 176440 CONDITION DICK SCHNEIDER KIT Small asbostos gaskot was laying on tho ground. 09/05/90 GEU 176408 CONDITION DICK SCHNEIDER KIT Pound a 1 1/2" asbostos gaskot laying on tho pad. 10/02/90 ODU 177343 CONDITION LOUIE KRAMER MNT Asbostos gaskot stuck to flang of pump storod by oast road into ODU. 10/02/90 ODU 177344 CONDITION LOUIE KRAMER KIT Asbostos gaskots stuck to flangos on piping locatod by sido of oast road into ODU. 09/27/90 WEST SIDE OP ODU 181516 INCIDENT BAR Thoro was some piping and tubing connoctod to column No. MK3- 701 that will bo removed fron tho unit whilo scaffold crow was working on column for asbostos crow, thoy noticod a pioco of pipo that had asbostos on it was noxt to tho coluan and had exposed insulation on it so thoy callod no. 10/03/90 360 NORTH 176475 CONDITION BUD DAVIS MNT Found 10" asbostos gaskot lying on ground. 10/02/90 PIPERACK 176483 11/07/90 UNIT 176396 CONDITION B&R Found asbostos gaskot in tho wobb of a boaa. CONDITION BUD DAVIS MNT Pound half of asbostos gaskot lying undor hoat exchanger. 11/09/90 ODU 176395 CONDITION FELIX GARZA JR MNT An asbostos gaskot was stuck to a pipo flango. 12/09/90 ODU 194164 CONDITION CECIL SHAFER MNT Noticod MEA strippor hoad was insulatod with uncovorod asbostos. Approxiaatoly 1/2 tho aroa of tho hoad was uncovorod. 20 01/23/90 EAST SIDE 155182 12/29/89 PIPE RACKS 148294 01/30/90 SETTLING BASINS 162430 01/31/90 #21 BOILER 117145 02/06/90 159741 02/09/90 306 162553 02/09/90 COOLING TOWERS 162525 CONDITION LOUIE KRAMER MNT Section of 2" SS pipo by tho road, has asbostos gaskots stuck to flango. INCIDENT CONST Tho BAR instrument department was hanging cable tray when a piece of fire protection was broken off tho existing cable tray, tho unit informed mo tho broken fire protector was made of asbostos. There wore no signs warning employee about asbostos in tho pipo rack. CONDITION WILLETT NEILL MNT Asbestos gaskets in area. CONDITION WILLETT NEILL MNT Asbestos gaskot on ground near vacuum tower. CONDITION DAVID LUGO KIT Scrap copper tubing, asbestos, cardboard boxes on the ground. CONDITION LEE YAKLXN MNT Scrap metal dumpster conains half used can o NOver-Sees, 1 quart plastic bottle of unknown liquid, bottles of Sherlock leak detoctor, asbostos gaskets, paper and plastic trash, new bolts and U-bolts. CONDITION LEE YAKLXN MNT Asbestos gaskot hanging on piping at #3 cold water pump. fire extinguisher cabinet at open top tank. Also, on top of 030792 02/09/90 11 GAS UNIT 102560 CONDITION LEE YAKLIN MNT Asbestos gaskets throughout unit, new and used on ground. 02/09/90 VD PIT PFO 162545 CONDITION LEE YAKLIN MNT Asbestos gaskets laying everywhere. 02/09/90 SEPERATIOKS MIT 162495 CABINET CONDITION LEE YAKLIN MNT Asbestos gasket and asbestos packing in cabient has no warning label on outside of cabient. 02/09/90 PFO DIKED AREA 162537 CONDITION LEE YAKLIN MNT New and used asbestos gasket inside diked area. 03/01/90 501N 162579 CONDITION LEE YAKLIN MNT Ordered 2 gaskets froe stores, then received one contained asbestos. Sasket was not wrapped, nor had warning label. 03/14/90 SETTLING BASINS 162433 CONDITION WILLETT NEILL MNT Found asbestos gaskets in area. 03/19/90 162597 CONDITION JOHN SHANNON JR MNT Scrap asbestos gasket material left on table in SOI N. shop. 04/17/90 SETTLING BASINS 162436 CONDITION WILLETT NEILL MIT Found asbestos gasket laying on ground at IS basins. 04/17/90 TREATED WATER TANK 171927 CONDITION JOHN SHANNON JR MNT Asbestos gaskets on ground. 04/17/90 E BUTADIENE PUMP PIT CONDITION JOHN SHANNON JR MNT 171943 11 GAS Asbestos gaskt hanging on handrail. 04/17/90 S OF ANALYZER BLDG 171922 CONDITION JOHN SHANNON JR MNT Slip blind with asbestos gasket under pump. 04/18/90 84 COMP 171912 CONDITION RUDY RAMIREZ MNT Asbestos insulated line suction 114 compressor blowing asbestos to air. 04/24/90 SEPARATIONS 170399 CONDITION ERNEST GARCIA MNT Found asbestos gasket in domestic trash barrell. 05/11/90 ELECTRIC SHOP, 170383 B-501N CONDITION HOSS NEILL MNT Found pieces of asbestos gasket in trash can. 07/02/90 PFO 170437 CONDITION ERNEST GARCIA MNT Found asbestos gaskets lying around PPO unit. 07/23/90 COOLING TOWERS 170465 CONDITION WILLETT NEILL MNT Found asbestos gaskets on ground at treated water storage tank. 07/19/90 SEPARATIONS - NORTH 170470 SIDE CONDITION JERRY DELGADO MNT Found large amount of asbestos insulation on ground in front of bldg. Asbestos fell through pipe rack to ground due to hard rain. 503. 08/17/90 WEST SIDE, B-400 183538 ANALYZER CONDITION ERNEST GARCIA MNT West side of Bldg. 400 has exposed asbestos on 3/S* SS tubing lilies/ Tubing appears to be out of service, but the asbestos insulation is exposed and is on the verge of falling out of the pipe rack. 09/11/90 BUILDING 501 SHOP 183513 CONDITION BUTCH HODGES JR MNT Found asbestos gasket on work table. 09/12/90 500 N 183509 CONDITION LEE YAKLIN MNT Gasket purchased on a field requisition. Gasket received was asbestos, not wrapped and no warning. Gasket is supposed to be purchased from Cooper-Bessemer only. No substitute. Could have been left over from an old Corpus Christ! gasket contract. 09/14/90 *1 GAS 183502 CONDITION WILLETT NEILL MNT Found asbestos gaskets on ground. 10/02/90 FURNACE ANALYZER 183276 BUILDING CONDITION ERNEST GARCIA MNT Noticed steam leak above lock boxes on west side of analyzer bldg, roof. Leak appears to be piping insulated with asbestos. on the 030793 10/31/80 PPO HIGH STRENGTH 192970 SEWER PUMP 12/10/90 12 OLEFINS 177350 0L2 SUBTOTAL: 31 CONDITION ERNEST GARCIA MNT 2* piping located south of high strength savor pump has axposad asbastos insulation. Tha insulation is falling off tha pip*. CONDITION LOUIE KRAMER WIT Two 1 1/2* nav asbastos gaskats on storaga rack in bldg. 504 02/14/90 140065 CONDITION BUDDY PERKINS MNT Found usad flax asbastos gaskat in araa. 02/21/90 140061 CONDITION BUDDY PERKINS WIT Saall piacas of asbastos broka off cabla trays. 04/16/90 1ST 140044 CONDITION ERNEST GARCIA WIT Exposad insulation, lookad lika asbastos. 05/04/90 OXIDE LOADING HACK 163605 CONDITION LOUIE KRAMER WIT Usad asbastos gaskat on tha ground at oxida loading rack. 04/26/90 B1 HX 140471 CONDITION DEAN STRAIN OXI Loosa asbastos froa cabla tray on pad at aast sida of B1 haat exchanger. 05/17/90 140014 CONDITION JIM FLEEMAN MNT While housekeeping inspection found wire, debris, asbestos, etc. in area. discarded 05/17/90 170132 CONDITION JAMES PORTER OXI During inspection, two large pieces of asbestos insulation was laying on the ground. 07/11/90 OXIDE I 173697 CONDITION BUDDY PERKINS MNT Pound 2 asbestos gaskets laying on ground had been there for jl long time. 07/21/90 B--3 HEAT EXCHANGER 173077 CONDITION BRUCE WOODS SHF Noticed asbestos insulation open to atmosphere between sample stream boxes *5 and <12 on the southwest end of B-3 heat exchanger. 10/09/90 OXIDE 173663 CONDITION BUDDY PERKINS MNT Found asbestos gasket that came down from pipe rack during the wind and rain. 10/25/90 OXIDE i 170070 CONDITION BILL VINCENT MNT Asbestos gasket stuck to a pipe flange. 11/07/90 OXIDE ii 194096 CONDITION MARTY MARTINEZ MNT Fond asbestos insulation that fell off froa under cable tray. 11/15/90 OXIDE ii 194093 CONDITION MARTY MARTINEZ MNT Construction parsonnal knocked ovar SOM asbastos insulation whila working in pip* rack. 11/15/90 OXIDE ii 170053 CONDITION BILLY WALKER WIT I found savaral larga piacas of asbastos notarial in tha pips rack. Thasa piacas wara brokan off tha bottoa of cabla trays. Also thara is fina particlas blowing in tha wind. 11/15/90 OXIDE ii 100169 CONDITION BSR Noticad asbastos barricada that-wasn't complata. situation, I noticad it had baan aaltad into. Aftar chacking out tha 12/02/90 SOUTH SIDE SCRUBBER 147953 HATER PUMP CONDITION CONST Contractor was sant in to ramova asbastos froa cabla trays at night. Wa showad up tha naxt aoming whan job was said to ba coaplata. Asbastos was still laying in araa. 12/12/90 OXIDE UNIT 194000 CONDITION BUDDY PERKINS MNT Found asbastos gaskat on ground by mono column. OXI SUBTOTAL: 17 030794 05/14/90 PFO DIKED AREA 170380 pro SUBTOTAL: 1 09/27/90 OL2 183834 PLE SUBTOTAL: 1 01/30/90 MAINT SHOP 161166 04/16/90 BUILDING 19 132736 06/01/90 MAiirr. shop 163726 POLYPROPYLENE 08/07/90 EAST OF ANALYZER 186950 BLDG. 12/02/90 ODU 194166 FPU SUBTOTAL: 5 01/16/90 NEAR PAINT SHOP 150808 06/05/90 CORNER 5TH fi F 163688 STREETS ROAD SUBTOTAL: 2 04/25/90 SEMICON 132803 05/15/90 SEMICONS 132947 06/10/90 CARBON BLACK 132828 BUILDING SEKICON SCO SUBTOTAL: 3 07/31/90 RACK 3 135930 11/29/90 INST. SHOP 163861 11/29/90 OXIDE 193982 11/29/90 W/S 193976 CONDITION LEE YAKLXN MNT Trash can on south aast comar with asbastos gask.ts. CONDITION FAT PETRISKY JR PLE Insulation marked "danger asbastos* has tha cover tom away exposing insulation. CONDITION HIKE MAUD MOT Asbastos storage cabinet is dirty. CONDITION ARMANDO GARCIA MIT Found six asbastos filled flax tuba gaskats in Betel lugger bin. CONDITION LOUIE KRAMER HOT Asbestos gaskets stuck to spargers that are leaning against south outside wall of poleprpylena aaint. shop. CONDITION ANDREW VASQUEZ MNT Found abandoned line with asbastos insulation deteriorating, east of analyser building. CONDITION CURTIS MARTIN MNT Found asbastos gasket laying on ground. CONDITION ANN THOMASON MOT Found asbastos gasket laying in roadway. CONDITION LOUIE KRAMER MNT 2' used asbestos gasket on the street comer of Sth and F streets. CONDITION CECIL SHAFER MNT Renoved manway flange on carbon black transporter and found the gasket to be asbastos impregnated material. CONDITION CECIL SHAFER MNT Opened tranporter at 5* blind flange, found gasket to be made from material containing asbestos. Checked transporter on line 2 and 3 and found same type of material. CONDITION CECIL SHAFER MNT REMOVED 12 AND 13 CARBON BLACK TRANSPORTER MANWAYS AND FOUND THE GASKET TO BE MADE OF ASBESTOS MATERIAL. CONDITION BAR Found 3/4* pip south of rack 3 in ditch with asbestos insulation exposed and loose asbestos in white rocks. CONDITION CHARLES SAMEY MNT Valve came into shop for repair (TV 1853 D) with asbestos gasket on flange surface. CONDITION ROGER HOCHGRABER MNT Was ask to cut bolts on B.O.U. reactor, insulation dust was flying everywhere. Found out next day tha insulation was asbestos. CONDITION GLENN BEGO MNT Head brought to shop still had asbestos gaskets attached. 030795 SHOP SUBTOTAL: 4 01/12/90 BSfil 152265 SQA SUBTOTAL: 1 GRAND TOTAL: 16S CONDITION JEROME JANAS SQA Asbestos board in us* in th* HP2 lab in us* as an apparent h*at insulation pad for th* tap* extruder axtrudate. 030796 * ON the JOB CIA SUtMARY with kasbestost in the description 01/01/91 to 06/30/91 CHIT RET DATE LOCATION TIPE DESCRIPTION 03/23/91 N/S PIPE RACK S. OF CONDITION CONST 169511 THE BLACK While talking with By supervisor I observed a sub contract employee Moving about in the pepe rack. He was wearing a half face respirator with purple cartridges. He was not wearing any protective clothing or fall protective equipment. There were approximately 12 to IS other employees stripping asbestos with full protective gear and full body harnesses. 03/19/91 COGEN 198609 CONDITION DIS JOINED JOB IN PIPE RACK ALREADY IN PROGRESS. FOUND PIPE INSULATION CONTAINING ASBESTOS, REMOVED BUT NOT ENCAPSULATED. 04/02/91 B-W PIPE RACK 173346 341-343 LP1 CONDITION JOHN BRADLEY MPT Noticed large steam line probably had Asbestos Insulation and it was worn and exposed. 04/30/91 EAST/WEST PRECURSOR 195345 SOUTH 360 CONDITION FRED BERGER MNT Construction sandblaster was blasting pipe in piperack. Blast stream accidently hit insulated lake knocking asbestos insulation off. DIS SUBTOTAL: 4 02/07/91 321 NORTH 173186 CONDITION JOHN SIM*)NS MNT Someone unloaded asbestos pipe in unit. *1177015-6. Tag on pipe reads ( Tie in (A8 DRW. 02/12/91 HATER TREATING 173165 CONDITION ROBERT GOSSETT MNT Found asbestos insulation exposed on soda ash tank piping nad also some insulation laying on ground. 03/17/91 EAST OF OXIDE 1 179979 CONDITION MIKE WARD MNT Person not wearing respirator in asbestos area. 04/17/91 *21 S 122 BOILER 179913 CONDITION MIKE WARD MNT Asbestos not picks up yet. 04/17/91 NORTHEAST OF BLDG. 173285 327 CONDITION GEORGE HEINS JR MNT Found two asbestos gaskets in lugger bin. 04/19/91 SOUTH OF BLDG. 500 194553 CONDITION AL HARTMAN MNT Found asbestos gasket on the ground. 04/25/91 199474 BLOCK 9, *3 GEN AREA AND B.324 CONDITION RANDY MADDUX MNT After doing a visual inspection of the *2 gen., I exited by the North stairwell near Bldg. 324, when-1 wes almost to grade level, I noticed that I was inside an area barricaded with asbestos tape. 04/30/91 02 UNIT 168517 CONDITION GEORGE HEINS JR MT Found 21 asbestos gaskets in tool box in 02 unit. ENS SUBTOTAL: 8 - 02/14/91 OOU WASTE WATER 194058 PUMPS EVP SUBTOTAL: 1 CONDITION DON HARNED MNT Found two asbestos gaskets on ground at OOU waste water pump station. 04/16/91 NORTH OF G.E.U. 195046 CONDITION MNT WENT TO PUT ASBESTOS IN RED TRAILER. IT HAD NOT BEEN LINED WITH POLY. WHEN OPENING LID ON TRAILER FOUND THAT 030797 GEU SUBTOTAL: 1 04/16/91 EAST OF SHOP 179922 04/16/91 EAST OF SUB D 179921 HF2 SUBTOTAL: 2 CONDITION KIKE WARD MIT Gasket storage cabinat (containing som asbestos) not claan. CONDITION KIKE WARD HOT Gaskat storaga cabinat - asbastos labal about to COM off. 01/02/91 BLDG. 341 HEZZAZINE CONDITION HIKE ADKINS MIT 173339 AREA Locatad piping thrown in scrap luggar with asbastos wrapping on it. 01/23/91 LP-1 173956 CONDITION MASK SCHROLLER MOT Found asbastos gaskat laying on railroad tracks in front of Bldg. 353. 02/12/91 0-1750 17(002 CONDITION VAN SHRADER MOT While correcting jobs on housekeeping inspection list I found two asbastos gaskets hanging on a valve wheal on catalyst feeder level. 02/06/91 LF1 REACTOR G-5 200000 CONDITION CRAIG STRAKOS MOT Foudn asbastos gaskets laying on structure on reactor. 03/04/91 BLDG. 341 177364 CONDITION LOUIE KRAMER HOT Two 10" asbastos gaskets on floor in front of storaga cabinets by cage locatad in bldg. 341. 03/04/91 BLDG. 341 177366 CONDITION LOUIE KRAMER MOT No asbastos labal on Mtal cabinat used to store asbastos gaskets on the third level of bldg. (341. 03/04/91 BLDG. 341 177365 CONDITION LOUIE KRAMER MOT Approx. 24" asbastos gaskat hanging on a halve on nitrogen header 3rd level of bldg. 341 by 1750 reactor. 04/09/91 2ND LEVEL WEST SIDE 17(075 CONDITION JOHN BRADLEY MOT Exposed asbestos looking West in pipe rack between RX- control room and 344 structure. 2 lines. 04/18/91 LF1 190756 CONDITION JOE ESTRADA MIT Noticed an asbestos gasket in trash can. only. Trash can was for regular trash 05/01/91 G-5000 178015 CONDITION JOE GONZALEZ JR MOT While cleaning around G-5000, found about 12, 30* asbestos gaskets. 05/14/91 GS REACTOR 205223 CONDITION MIKE ADKINS MIT Found asbestos gaskets that were not disposed of properly. LF1 SUBTOTAL: 11 02/06/91 HOT COMPOUND - 4 199987 04/03/91 EAST OF HC-5 MIXER 173347 LP1F SUBTOTAL: 2 CONDITION JOE GONZALEZ JR MIT Found asbestos gasket on pad by HC-4. CONDITION JOHN BRADLEY MOT Noticed condensate line had asbestos insulation. (I Think) 04/23/91 BLDG. 347 OLD LAB 199946 BLDG. LP1LB SUBTOTAL: 1 CONDITION JOHN BRADLEY MOT Noticed pieces of asbestos in old furnace. 01/09/91 173331 WEST OF G-5000 PURGE GIN CONDITION VAN SHRADER MOT Found three large asbestos gaskets on floor East of the G-5000 purge bin. Both rupture disk on this vessel were blown several weeks ago. It appears personal on this job did not clean up after job was collate. 030798 01/33/91 REACTION CONTROL 173304 ROOM 02/05/91 BLOCK 12 REAR 1739S2 NITROGEN SIEVE LF1R SUBTOTAL: 3 CONDITION DONNIE MARIK MNT I found six asbestos gaskets in operations/ shift fittors spar* parts cabinet. CONDITION JEFT DIETZEL MNT Reaoved a pressure regulator from a nitrogen line in order to work on the regulator. I noticed that the flange gaskets used were asbestos. 05/29/91 STORES 208122 06/07/91 140-1 208127 MtD SUBTOTAL: 2 CONDITION CARL BOSIER MID round a sheet of asbestos gasket material left unwrapped. CONDITION CARL BOSIER MMD Discovered a sheet of asbestos gasket material that was not wrapped. 01/16/91 GAS 2 SEPERATIONS 191808 02/05/91 320 WEST 147016 02/21/91 G.E.U 191815 02/22/91 #2 STEAM PLANT 191816 04/24/91 3 TURBO GENERATOR 168676 04/17/91 353 S SECOND FLOOR 195059 POLY F 05/10/91 GARAGE WORK BAY 195394 05/17/91 NORTH FIELD BARGE 191566 DOCKS 06/13/91 SALVAGE YARD 196399 06/17/91 PLANTWIDE 196390 MIT SUBTOTAL: 10 CONDITION MNT STEAM PIPING TO THE BASE OF THE NUMBER ONE AND TWO C2H2 ABSORBER COLUMNS IS ENSULATED WITH, WHAT I SUSPECT IS ASBESTOS INSULATION. THE FABRIC COVER COVERING THIS INSULATION IS DAMAGED IN SEVERAL PLACES AT BOTH COLUMNS, LEAVING THIS INSULATION OPEN TO THE ATMOSPHERE. CONDITION MNT PIPE LAYING BESIDE DUMPSTER HAS ASBESTOS ON IT. ASBESTOS IS LAYING ON THE GROUND. SOMEONE HAS MOVED IT AND CONDITION MNT I FOUND A LARGE DIAMETER ASBESTOS GASKET IN THE UNIT TRASH BARREL. CONDITION MNT I WAS riELD MEASURING PIPING ON THE *21 IBO TANK FOR AN UP COMING SHUTDOWN. I ENCOUNTERED QUITE A BIT OF TUBING WITH ASBESTOS WRAP FOR INSULATION. THE COVERING OVER THE ASBESTOS WRAP IS NON EXISTANT IN MANY PLACES LEAVING THE ASBESTOS OPEN TO THE ATMOSPHERE. CONDITION CHARLIE ZIRKELBACK MNT Asbestos barrier tape exists on #3 Turbo Generator platform stairs on south side but not on north side. Either tape should be removed on south side or south should be taped off also. CONDITION MNT WHILE REMOVING ASBESTOS TRANSITE FROM THE BUILDING I NOTICED TWO EMPLOYEES ENTERING OUR BARRICADED AREA WITHOUT THE PROPER PROTECTIVE EQUIPMENT. CONDITION DARWIN BROWNING MNT Lid missing from asbestos waste drum. ACCIDENT MNT WHILE WORKING INSIDE THE BASKET I LEANED OVER TO STRIP ASBESTOS INSULATION, THE STORAGE TANK HAD ACETIC ACID DUST BUILD UP, CAME IN CONTACT WITH DUST AND HAD A BURNING SENSATION. CONDITION ton DUMP HOPPER FROM BARGE DOCK MAINTENANCE HAS SMALL SPOOL PIECE STILL BOLTED UP AND BOTH OPEN END FLANGES HAS ASBESTOS GASKET ON THEM. ALSO ONE (1) ALUMINUM FLANGE HAS ASBESTOS GASKET ON IT. CONDITION MNT NEED TO PUT SOME KIND OF HANDRAIL ON BACK OF PAINT TRUCK WW969 AND ASBESTOS CREW TRUCK, STEPPING OFT TRUCK UNTO BUMPER WITH WET BOOTS OR MUD ON BUMPER COULD CAUSE YOU TO SLIP AND FALL CAUSING INJURY TO YOUR BODY. 01/09/91 BLDG. 367 194180 04/19/91 AMINES 184758 CONDITION BUD DAVIS MNT Two used asbestos gaskets lying on table in shop. CONDITION WALLY WILLIAMS MNT A piece of 1/2" steam tracing pipe with asbestos insulation fell out of 030799 05/01/91 AMINES 174735 05/16/91 BTC COLI** 174731 06/17/91 OIDflCALS 360 NEST 174701 ODU SUBTOTAL: 5 structure to second level in amines. CONDITION HALLY WILLIAMS MNT Asbestos insulation on floor in anions unit foil out of pipe rack. CONDITION BARNEY CARROLL MNT Personnel working inside plastic enclosure with "Danger - Do Not Enter, Asbestos Hazard* signs on entrance door. CONDITION BB BROWNING NET Pound a part of a asbestos gasket laying on the ground. 10 03/28/91 OLEFINS I 188511 OL1 SUBTOTAL: 1 INCIDENT NATHAN BEDEE OL2 Without notifying unit personnel or obtaining required HWP, naintenance crew of Oxide assessment team entered HWP area of Olefins I to renove pieces of ORS column. This area had already been deemed unstable and off-limits to all except asbestos crew. They entered area with potential ignition source and began using jacks in piperack jeopardising safety of personnel. (HWP High injury potential - violators maintenance) 02/10/91 REACTION WALKWAY 196203 SOUTH END CONDITION MNT CONSTRUCTION WAS WORKING IN THE PIPE RACK AND KNOCKED SOME ASBESTOS OUT OF THE RACK. 02/07/91 GAS II (NOl 193055 C2HZSTILL) CONDITION MNT EXPOSED ASBESTOS ON 3/4" LINE RUNNING VERTICA ON THE NORTH SIDE OF NO. C2H2 STILL. 1 02/07/91 AREA NORTH OF 13 168162 C.T.G. CONDITION RED SUMS ENS Some person had put a piece of piping with a swant out and insulation on piping is asbestos. 03/10/91 EAST OF 201 173014 CONDITION DAVID HOLDER SHF Asbestos trailer needs to be removed from unit and stored elsewhere. bean in unit for several months. Has 04/19/91 SEPARATIONS 194570 CONDITION JERRY DELGADO MNT Found "asbestos" gaskets on ground. sight and not put in proper place. These gaskets were just left on job 04/19/91 501 NORTH 194572 CONDITION LEE YAKLIN MNT Found asbestos spiral wound gasket overlayed with grafoil tape in scrap metal dumpster. 04/23/91 207535 815 COMPRESSOR BLDG. 500 CONDITION JOHN SHANNON JR MNT Suction pipe has asbestos insulation. This has been identified and marked previously. The problem lies in the cover, it is deteriorated and the asbestos is exposed to the atmosphere. 04/23/91 COMPRESSOR BUILDING CONDITION BUTCH HODGES JR MNT 207509 Found asbestos gasket on ground near compressor building. 03/27/91 INSTRUMENT AIR 207518 FILTERS S. 501 CONDITION WILLETT NEILL MNT Asbestos tubing wrap on tubin gat instrument air filters is unwrapped with fibers exposed to air. 04/23/91 115 COMPRESSOR BLDG. 207535 500 CONDITION JOHN SHANNON JR MNT Suction pipe has asbestos insulation. This has been identified and marked previously. The problem lies in the cover, it is deteriorated and the asbestos is exposed to the atmosphere. 03/18/91 SEPARATION AREA 207520 CONDITION WILLETT NEILL MNT Found asbestos gasket in lugger bin. 04/24/91 COMPRESSOR BUILDING CONDITION JW BLAND JR MNT 207523 Found used asbestos gasket on work table in compressor building. 04/24/91 SETTLING BASIN CONDITION JAVIER VILLARREAL MNT 030800. 207538 05/16/91 SEPARATIONS 202854 06/20/91 SEPARATIONS UNIT 202770 01*2 SUBTOTAL: 15 found asbestos gasket on ground. CONDITION LEE YAKLIN WT round asbestos gasket in domestic trash can. CONDITION JERRY DELGADO MNT Found loose asbastos insulation on ground. Probably fall through piparack. 12/08/90 OXIDE II 184494 CONDITION B&R Observed three outside asbestos abatement workmen working in piperack without being tied off. Violation of elevated work policy PSH-IV-6. 01/17/91 196073 12 PIPELINE PUMP STM PIPE CONDITION MNT TWO INSULATORS STRIPPED TWO 90 DEGREE ELBOWS WHEN THEY NOTICED ONE OP THE 90'S HAD ASBESTOS ON IT. 01/24/91 OXIDE I 194074 CONDITION BUDDY PERKINS MNT found asbestos gaskets on ladder rack that were left after shutdown. 02/08/91 SPOT 4 LUGGER BIN 132655 CONDITION MIT FOUND TUBING WITH ASBESTOS WRAPPING IN METAL LUGGER BIN. 02/11/91 12 GLYCOL 200621 CONDITION LILA FOSTER SHF Found loose asbastos hanging in piperack above FC aake pumps. 03/28/91 OXIDE BLOCK 199832 CONDITION JANICE SIMON CLARK SAP Saw person inside asbestos barricade without a respirator on. 04/27/91 REACTION 196741 CONDITION SYLVESTE MOSLEY JR SHF While touring unit, found some scaffold crew working around asbestos removal operation. 04/25/91 PIPERACK SOUTH OF 195347 OXIDE I CONDITION FRED BERGER MNT Asbestos insulation was knocked out of overhead piperack and was on the ground. One insulated line appearred to be severly damaged from being stepped on. 04/25/91 SUBSTATION El AND E2 ACCIDENT 169643 CONST While performing electrical demolition activities at substation E-l and E-2 at Oxide II, six BtR Braun Const, electricians were possibly exposed to an unknown amount of asbestos fibers. The insulation was allowed to free fall to the ground and as it hit obstacles on the way down it formed a visible cloud of dust that drifted well outside of the barricade that was erected in an approximate twenty foot area at the base of the column. 04/30/91 MAIN NORTH/SOUTH 172115 UNIT PIPERACK CONDITION DEAN STRAIN OXI While checking on asbestos removal progress in unit discovered two workers standing in middle of span of cable tray passing equipment from outside of the cablet tray to the other. HWP states to avoid walking or climbing on the cable tray. Standing on the tray will damage it or cuase it to break resulting in the worker falling through the tray. 05/08/91 OXIDE II 196890 CONDITION MIT BAILS OF ASBESTOS WERE NOT PROPERLY BARRICADED. 05/24/91 OXIDE II STRIPPING 148118 STILL COL. CONDITION CONST Removed metal weather barrier from stripper still. Insulators put on job to remove metal misunderstood Gen. Foreman' s work detail about job and removed metal jacket leaving asbestos insulation exposed. We immediately called B&R Safety inspector and insulation superintendent, also a UCC operator involved. 06/18/91 STRIPPING STILL 206936 CONDITION RUDY SOTO SHF While asbestos removal people were enclosing area around stripping still with plastic, discovered vent valve with nitrogen venting inside enclosed area. 0X1 SUBTOTAL: 13 01/03/91 3RD STREET CONDITION BILL SPELLACY PPU 030801 160367 01/21/91 BEHIND THE P-1 174544 ANALYZES BLDG. 04/11/91 KAINT. BLDG. 179942 04/18/91 P-1 187312 04/22/91 BLDG. 11 187250 05/16/91 BLDG. 101 161954 05/22/91 P-1 CONTROL ROOM 161926 06/07/91 P-1 CONTROL EAST 201023 DOOR 8 04/18/91 INSTRUMENT SHOP 195812 04/05/91 82 GAS 179524 04/20/91 INSTRUMENT SHOP 19S824 05/16/91 REPAIR SHOP 162961 SHOP SUBTOTAL: 4 GRAND TOTAL: 91 A 4' long section of pipo covorod with asbestos insulation laying in tha roadway. CONDITION JAKES MORGAN SHF While looking at linos in tha aast-vost pipa rack, I noticad a lino bahind tha analyzer that appaars to ba out of service. The insulation was Barked asbestos and the jacket on the end was off and the insulator appeared to ba enabling. Along tha entire length tha insulation appears in siailar condition. CONDITION MIRE WARD MNT Open asbestos storage. CONDITION CURTIS MARTIN MNT Found asbestos gasket on first landing of structure. CONDITION ANDREW VASQUES HIT Disposnig asbestos gaskets in proper container found designated container full of trash nixed with asbestos gaskats. CONDITION BILL 5PELLACT PPU Approachined within a faw feet of asbestos reaoval work because tha job site was not properly barricaded off. CONDITION BILL SPELLACY PPU A large piece of asbestos siding aaterial was found laying loose inside a wall during wall repairs. No one recognized this naterial and it was pulled out and laying on the control rooa floor. CONDITION MNT Coming up the stairway noticad that the subcontractors asbestos barricade was down on tha floor. CONDITION LARRY KNEBEL MNT A valve cane in from the 02 unit with a gasket attached. some asbestos fibers. These gaskets have CONDITION DARRYL LYNCH MNT While taking piping off of 113 Gas Turbine noticed that it had asbestos gasket. CONDITION JOE GARZA MNT Noticed gaskets on M/V flanges to be asbestos. CONDITION RICHARD REYES MNT Gasket storage cabinet in repair shop has some durable gasket material. Some repair shop personnel were told that his is asbestos free. 308o2 CUT REF DUE LOCATION 11/15/91 HYDRO METHANE 166903 COMPRESSOR 11/15/91 HYDRO-METHANE 16(103 COMPRESSOR EHS SUBTOTAL: 2 ON the JOB CIA SIM4ARY with tAsbestost in the dascription 07/01/91 to 12/31/91 TYPE DESCRIPTION CONDITION AUGIE RIVERA JR MNT Noticad asbastos gaskets on top landing of compressor. CONDITION AUGIE RIVERA JR MNT Noticad asbastos gaskats on top landing of conprassor. 10/08/91 TANK PARM 212094 GEU SUBTOTAL: 1 CONDITION JOEY MITSCHERLING NR Pound two asbastos gaskats on tha ground in tank fan. 08/05/91 HP2 211456 11/18/91 TANK VENT 135751 HP2 SUBTOTAL: 2 CONDITION MNT I HAS LOOKING OVER A JOB LOCATED AT THE CHEMICAL RAIL CAR LOADING RACK IN HP-2 AND FOUND POUR ASBESTOS GASKETS LYING ON THE PAD. CONDITION RICHARD REYES MNT Tank vant was sant in for routina naintananca and still had asbastos gaskat attachad to it. 07/01/91 G-5000 REACTOR 208993 07/26/91 1750 REACTOR 206750 08/15/91 G-5 REACTOR 209017 LP1 SUBTOTAL: 3 CONDITION VAN SHRADER MNT I found four usad asbastos gaskats of assortad sisas on tha raactor catalyst faadar laval. CONDITION COLLIN WENDEL MNT Found asbastos gaskat laying on top of two drums. CONDITION JAMES MEISCHEN MNT I put a safaty valva back on tha raactor. Whan I was picking up tha araa, I found an asbastos gaskat laying on tha grating. 09/16/91 HOT COMPOUND 208971 LP1P SUBTOTAL: 1 CONDITION EDDIE MOYA MNT Found asbastos gaskats laying on tha ground and not in propar placa. 08/22/91 ISNTRUMENT SHOP 209664 LP1R SUBTOTAL: 1 CONDITION JEFF DIETZEL MNT I found a 2* asbastos gaskat in storaga cabinet inside of shop araa. 10/30/91 140-1 208166 MID SUBTOTAL: 1 CONDITION CARL ROSIER MID On my routina check of work araa I noticad that a roll of asbastos gaskat material had bean removed from tha plastic bag. 07/19/91 2ND FLOOR UNDER ROOF CONDITION MNT 192253 E. OF G--1 A PIECE OF ASBESTOS TRANSITS HANGING FROM ROOF TOP 07/24/91 BOILER 21-22 CONDITION MIT 030803 196796 07/29/91 SIS 12 LDXDCMI IMS 171536 WHILE I WAS DEINSULATING SOKE ASBESTOS WRAPPING OFT A TUBING LINE AT BOILER 21-22, I FOUND A LEAK. CONDITION WT THERE IS A GANG BOX IN THE IAYD0MN YARD THAT IS FULL OF ASBESTOS GASKETS. THEY NEED TO BE DISPOSED Or PROPERLY. 01/09/91 BLDG. 345 SILICA 171506 SHED CONDITION MNT ASBESTOS CREW HAS CALLED TO BLDG. 345 SILICA SHED TO CLEAN UP TRANSITS THAT WAS BROKEN OUT BY AN OUTSIDE CONTRACTOR. 01/19/91 14AUMAS WEST OP SRV 171513 MAZER PUMP CONDITION MNT ASBESTOS INSULATION WAS KNOCKED OR FELL FROM THE PIPE RACK. INSULATION FITTING NEEDS TO BE REMOVED. THE REMAINING 01/27/91 PAINT SHOP SANS 209450 BLAST BOOTH CONDITION MNT Send blast booth recieved a flange that had asbastos gaskat rasidua left on it. 09/05/91 BLDG. 164 209436 CONDITION MIT UCC PERSONNEL BROUGHT HEAD TO GET SANDBLASTED. GASKET IN IT. IT CONTAINED SOKE ASBESTOS 09/12/91 360 M. GASKET CKA 177510 CONDITION MNT WHILE DISPOSING OF ASBESTOS GASKETS OUT OF CAN AT O.D.U. I NOTICED THAT THE CAN ALSO CONTAINED *9 WIRE AND PIECES OF WOOD. THIS CAN IS CLEARLY MARKED "ASBESTOS GASKETS ONLY". 09/10/91 DECON TRAILER EAST 177654 OP PAINT SH CONDITION MNT WHILE WORKING AT THE ASBESTOS DECONTAMINATION TRAILER I NOTICED THAT THE PLYVTOOD BOARDS CURRENTLY BEING USED TO LEVEL THE TRAILER WERE ROTTED OUT CAUSING THE TRAILER TO SHIFT AND TILT. 09/19/91 GAS X 171537 CONDITION FRED BERGER MNT Crows foot connactor on water hose to asbastos dacon trailer did not have safety pin. 09/24/91 OXIDE II 204574 CONDITION MNT ASBESTOS LAYING ON GROUND EAST SIDE OF IGT UNDER PIPE RACK. 09/30/91 HP-2 172495 CONDITION MNT NOTICED ASBESTOS WORKER NOT WEARING CUT PROOF GLOVES WORKING ON COOLER HEADS REMOVING GASKETS. 09/26/91 MELD SHOP 177619 CONDITION MNT ASBESTOS CANS HAVE TRASH IN THEM. 10/07/91 HP-1 117349 10/01/91 2ND FLOOR POUT F 172534 EAST SIDE CONDITION CURTIS MARTIN MNT Found asbestos gasket in unit. CONDITION ran ASBESTOS GASKET CAN HAD PAPER TRASH INSIDE. 10/01/91 NORTH PIPE RACK ODU 209319 CONDITION MNT NOTICED ASBESTOS OlEW MEMBER OF OUTSIDE CONTRACTOR INSIDE BARRICADE TAPING BAGS OF ASBESTOS WITH NO PROTECTIVE GLOVES 10/09/91 CORNER OF "G* AND 172530 2ND STREET CONDITION MNT WHILE WALKING BACK TO BLDG. 521 Z NOTICED SOME INSULATION ON THE GROUND. STOPPED TO LOOK AT IT AND FOUND IT TO BE ASBESTOS. I 10/06/91 NORTH PIPE RACK ODU 209319 CONDITION ran NOTICED ASBESTOS CREW MEMBER OF OUTSIDE CONTRACTOR INSIDE BARRICADE TAPING BAGS OF ASBESTOS WITH NO PROTECTIVE GLOVES 10/21/91 NORTH FIELD TANX 217665 FARM CONDITION ran HAS WORKING IN HIGH PIPE RACK, WHEN WE CAME DOWN I NOTICED A LARGE PIECE OF ASBESTOS LAYING ON THE GROUND. 10/29/91 12 COOPER-BE5SD1ER 200511 CONDITION RICHARD MARXS JR M7T While analyzing 12 cooper, notiec the exhaust manifold leaking through the insulation batween 2L and 3L power cyliinders. Thera is small piaces of insulation scattarad on the piping, catwalk, and on top of the heads. Considering the age of this conprassor, the insulation could be asbastos. 030804 11/01/91 165 SANDBLAST 147330 CONDITION MNT WENT TO 165 TO PICK UP 6' PIPE. ON ONE Or THE FLANGES THESE WAS AN ASBESTOS 11/06/91 360 W. AMINES 212073 CONDITION BB BROWNING MNT Found a 4' asbestos gasket laying on tha ground. 11/05/91 INSIDE BLDG. 164 209552 CONDITION MNT REPAIR SHOP BROUGHT OVER DIRTY PUMP WITH ASBESTOS GASKET STILL ON. BEEN PARTIALLY SCRAPED BUT NOT ALL THE WAY OFT.Z IT HAD 11/14/91 BLD. 209501 164 PAINT SHOP CONDITION MNT INDIVIDUAL BROUGHT VALVES 6 PIPING TO SANDBLAST SHOP TO GET SANDBLASTED t PAINTED. UPON INSPECTION OF MATERIAL FOUND ASBESTOS GASKETS STILL OH PIPING 6 FLANGE. 11/26/91 CORNER OF SECOND 6 G CONDITION MNT 213201 STREET ASBESTOS INSULATION FOUND ON THE GROUND UNDER PIPE RACK. MR SUBTOTAL: 25 09/03/91 ODU MAINTENANCE SHOP CONDITION LOUIE KRAMER MNT 207862 Asbastos gasket scraps on work tabla ODU maintenance shop. 09/03/91 GEU MAINTENANCE WORK CONDITION LOUIE KRAMER MNT 207864 AREA Usad asbastos gaskat on pad in aaintananca work araa in GEU. 09/03/91 MR. WORK AREA AT 207865 GEU CONDITION LOUIE KRAMER MNT Asbastos scraps on top of storaga cabinet GEu aaintananca work araa. 09/30/91 AMINES 212096 CONDITION WALLY WILLIAMS MNT Found 3 used asbestos gaskets on ground in Aaines Unit. 11/05/91 42 FLASH TANK 214691 CONDITION BILL WADE MNT While checking out instrunents on 42 flash tank, noticed we ware right above asbestos reaoval work. Stairs were not barricaded off. 11/04/91 GROUND 212051 CONDITION FELIX GARZA JR MNT Found asbastos gasket laying on the ground. ODU SUBTOTAL: 6 08/20/91 415 OIL COOLERS 202703 08/20/91 EAST OF SLUDGE PIT 202706 08/20/91 SEPARATIONS 202704 (SOUTHEND) 08/29/91 SOUTH OF HIGH 202716 STRENGTH SEWER 09/05/91 SEPARATION AREA 194617 09/26/91 500 N. 202822 OL2 SUBTOTAL: 6 CONDITION LEE YAKLIN MNT Found asbestos gaskat froa oil cooler job in doaestic trash can. CONDITION ERNEST GARCIA MNT Noticed 1 1/2' stub-end coning out of 475 staan header has exposed asbastos insulation. CONDITION LEE YAKLIN MNT Four asbastos gaskets in doaestic trash can near construction job site. CONDITION ERNEST GARCIA MNT Just south of high strength sever of PFO, there is a 2* pipe with exposed asbastos insulation. CONDITION JERRY ROBINSON SHF Found asbastos reaoval barricade tied through valve wheal. If tha valve had bean needed quickly tha barricade nay have bean dropped and not replaced. CONDITION LEE YAKLIN MNT Transite siding being removed froa Bldg. 500, North wind blowing, area on north side barricaded off about 50 ft. froa N. wall. Inside of bldg, only about 4 ft barricaded on south side of wall. Every tiae a piece of material was reaoved, dust and/or asbestos would blow into bldg, for about 50 to 60 feet. 08/01/91 WEST SIDE OF OXIDE CONDITION MNT 030805 177586 vent scwj. 08/08/91 B-3 HEAT EXCHANGER 209906 09/13/91 5TH EVAPORATOR 190101 10/03/91 OXIDE II--PIPE RACK 204528 10/03/91 OXIDE 204530 10/02/91 OXIDE II 204600 OKI SUBTOTAL: 6 while working at oxide ii unit i pound some friable asbestos insulation LAYING ON THE GROUND IN THE WALKWAY. SOMEONE HAD APPARENTLY KNOCKED IT DOWN WHILE CRAWLING IN THE PIPE RAOU CONDITION JEFFREY NEWTON MNT Outsid* contractors cutting asbastos insulation ara laaving sharp jaggad adgas on natal waathar proofing. Asbastos saaling agant appaars to bo inadaquata bacausa thara ara loos* insulation fibars in inspaction parts. CONDITION FRANKIE DROZD JR HOT Found asbastos gaskat lying on ground naxt to 5th avaporator. CONDITION BILL VINCENT MOT Found a 4* asbastos flax gaskat laying in a cabla tray in tha pipa rack. CONDITION BUDDY PERKINS HOT Whl* claaning up, aftar raplacing pipa, found asbastos gaskat on ground vhara soaaona had laid it aftar raaoving pipa. CONDITION DARRYL LYNOi MOT Asbastos raaoval craw was stripping insulation fron piping running undar IGT. Thay had tha araa baracadad off, but whan thay wara finishad thay forgot to taka part of tha barracada down. 12/03/91 FIFTH STREET a 0 148101 STREET CORNER 12/11/91 PLANT ROAD 217744 ROAD SUBTOTAL: 2 INCIDENT CONST I was driving aast on Fifth Straat. Whan I casta up to D Straat intarsaction I had to stop bacausa Sarvic* Abataaant whit* pickup pulling a trailar loadad with asbastos failad to oak* a stop at tha intarsaction. CONDITION MIKE WARD MNT Asbastos workar riding in back of pickup with baggad asbastos. 07/09/91 DOOR 19 NORTH REPAIR CONDITION JOE EWALD WIT 184022 SHOP Two pumps arrivad in door I9N with asbastos gaskat not ranoved. 09/10/91 DOOR 9 SOUTH 193046 . CONDITION RAYMOND HILL JR MOT Found asbastos gaskat on suction flang* of pump. SHOP SUBTOTAL: 2 GRAND TOTAL: 58 030806 I CUT BET DATE LOCATION 09/20/92 ODU 17(543 CNfT SUBTOTAL: 1 ON the JOB CIA SUW1AKY with tAsbestos in the description 01/01/92 to 12/31/92 TYPE DESCRIPTION CONDITION FRED BERGER MNT Contractor called to infora that one area of the aoaonia still had a different type of insulation than the rest of it and suspected it to be asbestos. * 09/10/92 BLDG. 347 1709(4 CONST SUBTOTAL: 1 INCIDENT CONST Asbestos insulation renoved froa pipe in Bldg. protection and asbestos procedures. 347 without proper personnel 01/15/92 IN RACK N. OP 3(1 217435 BUILDING 01/17/92 3(1 SOUTH 217434 02/11/92 3(0 LUGGER 217999 0(/2(/92 BARGE DOCKS 158990 09/30/92 TANK 602 144238 DIS SUBTOTAL: 5 CONDITION DIS WHILE WORKING IN PIPE RACK NORTH OF BLDG. LAYING IN THE WEBB OF AN I-BEAM. 381 I |FOUND TWO ASBESTOS GASKETS CONDITION DIS NOTICED LID OF ASBESTOS GASKET TRASH CAN KISSING. CONDITION DIS SIFTING THRU FULL METAL LUGGER, FOUND DISCARDED SPOOL PIECE WITH ASBESTOS GASKET STILL ATTACHED. CONDITION JANICE SIMON CLARK DIS Noticed that the asbestos warning labels on the acetic acid line at the dock front did not contain the proper wording. CONDITION JANICE SIMON CLARK DIS On the west side of tank 602 there is a 20-30 foot piece of pipe wrapped in plastic. Pipe has asbestos labels on it which are extreaely faded. 02/05/92 GAS II 812 TURBINE 169477 DUCT 05/04/92 PIPING 148044 ENS SUBTOTAL: 2 CONDITION CONST Shop order rush job to trip and reinsulate a section of duct. Checked with unit person, received walk thru, started to reaove insulation which was aineral wood as we neared coapletion at bottoa, ant. showed up stopped the job because there Bight be asbestos. CONDITION CONST Old 3/4' line running up the coluan has collapsed and both line and insulation are laying on top landing and second froa top landing insulation is suspected asbestos. 02/07/92 GEU UNIT 1260(2 GEU SUBTOTAL: 1 CONDITION JOEY MITSCKERLING MNT While picking up trash in unit for a unit cleanup, found asbestos gasket on ground. 01/28/92 LP1 ACTIVATION 215551 CONDITION CRAIG STRAKOS MNT Found two asbestos and one flex gasket in a flange on the condensate line to g-5 activator bottoa line when 1 removed for Ttl. 02/05/92 TRUCK UNLOADING RACK CONDITION STEPH STEPHENS SHF 030807 226263 09/15/92 OLD ERYER LEVEL 262531 10/06/92 BLOCK 25 230461 LP1 SUBTOTAL: 4 According to OP's, vendors for teal trucks ara supposed to supply graphite/asbestos gaskets for hook-ups to our unloading lines. The gaskets with this shipment were not this type. Teal unloading was delayed for approximately 11/2 hours. CONDITION EDDIE M3YA MNT Found two 3' 1501 asbestos gaskets laying on floor. CONDITION MNT FOUND AN ASBESTOS GASKET IN THE METAL BIN 11/10/92 BASEMENT BUILDING 150220 101 LP1F SUBTOTAL: 1 INCIDENT WAYNE HC CUTCHEON LP1 Reaoving insulation froa condensate line to find leak. Where insulation was to be reaoved was an asbestos free label. Red arrows were also pointing away froa this spot. As insulation was being reaoved it was noticed to be asbestos. 09/10/92 BLDG. 347 LF-1 LAB 178542 CONDITION FRED BERGER MNT Deaolition contractor working on Bldg. 347 started to reaove an insulated line that contained asbestos insulation. LP1LB SUBTOTAL: 1 02/25/92 G-S REACTOR 215554 03/05/92 G-1750 223179 LP1R SUBTOTAL: 2 CONDITION JAMES KEISCHEN WC Found asbestos gasket hanging on valve handle. CONDITION RANDY STERNADEL SHF I found resin trash bags in asbestos trash can. 01/10/92 EAST BLDG. 501 220906 CONDITION JERRY DELGADO MNT Found tubing wrapped with asbestos insulation in lugger bin. 01/15/92 BLDG 101 S. 187347 CONDITION RAMIRO TORRES MNT Found an asbestos gasket on driveway at bldg. 101 s. 01/11/92 NORTH SIDE ON 380 213115 CONDITION MNT ASBESTOS TRASH CAN NEEDS A LID ON IT. WHEN IT RAINS, WATER COLLECTS AND MAKES THE BAGS HEAVIER. COULD POSSIBLE CREATE A BACK INJURY. 01/15/92 GAS II SEPARATIONS 218937 CONDITION MNT WAS WALKING TO MY TOOL BOX AND NOTICED SOME INSULATION LYING ON THE GROUND. I WENT TO PICK UP THE MESS AND NOTICING IT WAS POSSIBLE ASBESTOS. I THEN NOTIFIED AN OPEATOR, BARRICADED THE AREA OFF AND CALLED THE ASBESTOS CREW. IT TURNED OUT BEING ASBESTOS. 01/14/92 822 BOILER 225951 CONDITION MNT ........ NOTICED A RUSTED LINE THAT HAS BROKEN AND FALLEN INTO A CABLE TRAY WITH WIRE IN IT. THIS LINE HAS WHAT APPEARS TO BE ASBESTOS INSULATION ON IT. 01/11/92 343 NORTH 213104 CONDITION MNT THE METAL LUGGER BIN THAT IS ON THE NORTH SIDE OF THE CONTROL ROOM HAD SOME TUBING IN IT. THE TUBING WAS STILL INSULATED WITH ASBESTOS TAPE. 01/13/92 342-N 109265 CONDITION FRENQUE CORKIER MNT I noticed the lid to an asbestos container was on the gorund next to the container. 01/24/92 W.SIDE OF UNIT UNDER CONDITION MNT 213079 FANS I FOUND AN ASBESTOS GASKET LAYING ON THE WHITE ROCK UNDER THE FIN FANS. 01/22/92 P,F,0 213075 CONDITION MNT THERE IS ASBESTOS ON GROUND AND A SMALL BOX CONTAINING ASBESTOS IS BROKE OPEN AND LYING ON PIPE AND GROUND. 030808 01/24/92 MEZZANINE--GROUND 215570 LEVEL CONDITION PAT DUNLAP MNT Pound two asbestos gaskets on floor. 01/23/92 HE CORNER GEU 190183 CONDITION FRANKIE DROZD JR MIT Found asbestos gasket lying on ground. 01/21/92 ENERGY SYSTEM 213177 CONDITION MNT FOUND LOOSE ASBESTOS ON GROUND CAUSED BY CONSTRUCTION ELECTRICIANS STEPPING ON PIPE 01/22/92 RACE GOING NORTH AND CONDITION MNT 225939 SOUTH NOTICED WHEN INSPECTING JOB IN OXIDE-II WHEN I NOTICED SOME LOOSE ASBESTOS. 01/21/92 BEHIND NO. 4 215906 SETTLING BASIN CONDITION MNT A 9" VALVE WITH ASBESTOS INSULATION NEEDS TO BE REPAIRED OR REMOVED. 01/27/92 COGEN 225073 CONDITION MNT I WAS GOING TO USE THE UNIT STEAM CLEANER TO WASH SOME PIMP BASES WHEN I NOTICED THE INSULATING WRAP ON THE LANES WAS THE OLD ASBESTOS WRAPPING. 01/30/92 S. SIDE OP PAD BY 213090 STINKY DITCH CONDITION MIT FOUND ASBESTOS GASKETS THROWN ON GROUND BY STINKY DITCH NEXT TO 304 WASHPAD 01/28/92 NEST BAY HELD SHOP 206819 CONDITION MNT A CONDENSER HEAD FROM OXIDE II REQUIRED WELD REMOVAL ON INSIDE OF A FLANGE, BUT IT STILL HAD AN ATTAOIED GASKET THAT WAS IDENTIFIED AS ASBESTOS 01/27/92 LAYDCMI 225056 CONDITION MNT WENT TO THE LAYDCMN YARD TO TAKE APART A BALL VALVE FROM A SPOOL PIECE WHEN I NOTICED THAT THE FLANGE HAD AN ASBESTOS GASKET. 02/06/92 LPPE-1 215573 CONDITION DONNIE MAREK MNT I found all sorts of trash in asbastos only cans. 'asbestos only." Thesa cans ara labalad 01/30/92 OLEFINS 500--N 218019 CONDITION LEE YAKLIN MNT Found spiral wound asbastos gaskat in natal dunpstar. coma apart. It had coaplataly 02/04/92 OLD DRYER LEVEL 215572 CONDITION EDDIE MOYA MNT whan on unit claan up, found two asbastos gaskats on tha old dryar Laval floor. 02/06/92 LPPE-1 215573 CONDITION DONNIE MAREK MNT I found all sorts of trash in asbastos only cans. 'asbestos only." Thasa cans ara labalad 02/05/92 SOUTH SIDE WALKWAY 218008 Or SEPARA. CONDITION MNT THERE WAS SOME ASBESTOS INSULATION ON THE SOUTH SIDE WALKWAY OF SEPARATIONS 02/04/92 BLDG. 164 PAINT 191658 SHOP CONDITION MNT NOTICE 4* SPOOL OIECE WITH 2" NOZZLE LOCATED AT PAINT SHOP WITH ASBESTOS GASKET STILL INTACT ON 2' NOZZLES. 02/10/92 343 NORTH 224071 CONDITION MNT FOUND AN ASBESTOS GASKET CAN WITH REGULAR TRASH IN IT. 02/06/92 500 N. 207582 CONDITION LEE YAKLIN MNT Found three asbastos spiral wound gaskats in scrap natal dunpstar at 500 N. Appeared to have cone fron cooler job on tha 82 coup. 02/12/92 AMINES 217859 CONDITION MNT I FOUND KNOCKED OFF PIECES OF ASBESTOS ON FLOOR IN FRONT OF CONTROL ROOM. 02/20/92 HP2 223752 CONDITION CECIL SHAFER MNT Found broken asbastos gaskat on tha ground south of Building 560. 02/27/92 WATER TREATING 168964 CONDITION ROBERT GOSSETT MNT Exposed asbastos insulation on stean piping above 81 cooling water pump is blowing into atnosphare. 02/28/92 RACK WEST OF BLDG. 224151 327 ON GRND CONDITION MNT ASBESTOS ON THE GROUND. 030809 03/04/92 MEST SIDE 224172 CONDITION MNP ASBESTOS CANS HAD MISC. TRASH 03/04/92 SCREEN PAR BURNER 224173 CONDITION WFT ASBESTOS CANS HAD MISC. TRASH 03/04/92 SHOP AREA 224175 CONDITION MNT ASBESTOS CANS HAD MISC. TRASH 03/11/92 BREEZENAX SOUTH END 224184 GAS II CONDITION MNT AS I WAS WALKING IN SEPARATION I NOTICED SOME INSULATION ON THE FLOOR. AS I TOOK A CLOSER LOOK, I NOTICED IT WAS ASBESTOS INSULATION THAT HAD FALLEN FROM THE PIPE RACK ABOVE. 03/11/92 ACROSS FROM 501-N 224185 CONDITION MNT I NOTICED INSULATION ON THE GROUND WAS ASBESTOS 04/01/92 140 S. BY ROADWAY 224046 03/05/92 1 SYSTQDt SUCTION 230879 BLOWER 03/31/92 82 GAS 224040 CONDITION MNT POUND AN ASBESTOS GASKET LAYING NEXT TO ROAD CONDITION ravT I FOUND A PART OF AN ASBESTOS GASKET IN BLOWER CELL. CONDITION nvr I HAD ENTERED INTO SEPARATIONS PART OF THE UNIT AND HAD NOTICED ASBESTOS INSULATION ON THE GROUND. THE PIPERACK DIRECTLY ABOVE HAS ASBESTOS HANGING OFF THE PIPES AND IS IN A VERY BAD CONDITION. 04/07/92 503 SEPARATION AREA CONDITION MNT 230905 I FOUND AN ASBESTOS GASKET ON TOP OF A 55 GAL. DRUM 04/13/92 WEST END OF 226917 EAST-WEST WALK CONDITION MNT WE WERE CALLED TO GAS 1 TO CLEAN UP A SMALL ASBESTOS SPILL ON CONCRETE WALKWAY. 04/14/92 E. END OF E6W 224250 WALKWAY CONDITION MNT FOUND ASBESTOS GASKETS ON GROUND 04/08/92 SOUTH SIDE OF 226648 SEPARATIONS CONDITION MNT AS I WAS WALKING TO MY JOB SITE, I NOTICED SOME INSULATION ON THE FLOOR. STOPPED TO GET A BETTER LOOK AT IT, AND I FOUND IT TO BE ASBESTOS. I 04/08/92 EAST SIDE 226817 SEPARATIONS CONDITION MNT FOUND ASBESTOS ON THE FLOOR AT GAS II SEPARATIONS. 04/08/92 SOUTH END 226816 CONDITION MNT ASBESTOS FOUND IN PIPE RACK IN GAS 2 SEPARATIONS 04/13/92 211470 86 PROPANE CONDENSER CONDITION MNT THE TUBE BUNDLE WAS REMOVED FROM #6 PROPANE CONDENSER. THE ASBESTOS GASKETS WERE NOT REMOVED FROM THE CHANNEL, CONDENSER SHELL OR ASSOCIATED PIPING. THERE ARE LARGE ASBESTOS GASKETS STILL STUCK TO THESE SURFACES. 04/16/92 SOUTH OF ANALYZER 231251 BLDG. CONDITION MIT ASBESTOS INSULATION IN THE WALKWAY 04/13/92 211470 86 PROPANE CONDENSER CONDITION WIT THE TUBE BUNDLE HAS REMOVED FROM #6 PROPANE CONDENSER. THE ASBESTOS GASKETS WERE NOT REMOVED FROM THE CHANNEL, CONDENSER SHELL OR ASSOCIATED PIPING. THERE ARE LARGE ASBESTOS GASKETS STILL STUCK TO THESE SURFACES. 04/29/92 COMPRESSOR BUILDING 231265 CONDITION JW BLAND JR MNT Found used asbestos gasket on work tablo in compressor bldg. 05/01/92 BLDG. 11 SHOP AREA CONDITION ARMANDO GARCIA MNT 187021 Bag in asbestos container missing. 05/04/92 OLD SCAFFOLD YARD 226005 CONDITION WIT BARRICADE AROUND ASBESTOS WAITING TO BE REMOVED WAS FALLING DOWN. 05/16/92 FURNACE AREA 231205 CONDITION MNT THE ROOF OVER KIDDLE AISLE BETWEEN FURNACES ON THE NORTH AND SOUTH SIDE HAS LEAKS. THESE LEAKS BRING CHUNKS OF ASBESTOS DOWN WITH THE RAIN WATER. 030810 05/28/92 12 GAS SEPERATIONS 209919 05/21/92 PIPE RACK 209918 05/29/92 82 GAS SEP. 2ND 190244 LEVEL 05/26/92 BARGE DOCKS 219439 08/25/92 ODU 232985 08/31/92 EAST OF OLD HATER 230441 LAB 08/31/92 EAST OF OLD WATER 230440 LAB 09/15/92 900 SILOS 242506 09/10/92 341--N 229940 09/21/92 ODU 226016 11/04/92 BLDG. 1600 209915 11/18/92 GARAGE 185714 HIT SUBTOTAL: 63 CONDITION VIVIAN SPRAGUE HIT Was looking at coluans w/Marty, Ricky, a Rothnan for inspection. Wa cane upon insulation scattered in walkway of unit. Asked Marty if it was asbestos. He verified it was. He called his people to rope off and clean up. This insulation was in this area because the covering and insulation has deteriorated and is just falling out in this unit. CONDITION VIVIAN SPRAGUE MKT Rossler inspectors noticed insulation (asbestos) torn and tattered in the pipe rack on the south side of Oxide I and II and west side of energy systems. CONDITION TED SEVIER HIT There are several junction boxes along walkway with exposed asbestos. CONDITION MNT ASBESTOS CREW WAS WORKING SOUTH EAST CORNER OP THE BAYOU PUMP HOUSE WHEN 14 COMPRESSOR HAD AN OIL LINE RUPTURE, CAUSING AN OIL SPILL. APPROXIMATELY 2-1/2 GALLONS HAS SPILLED ON THE GROUND. CONDITION MNT POUND ASBESTOS WRAPPING ON SS TUBING IN SCRAP METAL BIN. CONDITION MNT WHILE BEHOVING ASBESTOS, NOTICED A CONSTRUCTION ELECTRICIAN WALKING OVER US IN THE PIPE RACK. CONDITION MNT CONSTRUCTION RIGGER CROSSED ASBESTOS BARRICADE. CONDITION JOE GONZALEZ JR MNT While opening silos on top of bin 901-902, found two asbestos gasket. CONDITION MNT I WAS SENT TO 341-N TO PICK UP A VALVE. THIS VALVE HAD ASBESTOS GASKETS LAYING ON CART AND SMALL AMOUNT ON VALVE. CONDITION MNT I NOTICED A PIPE IN THE PIPE RACK THAT WAS INSULATED WITH ASBESTOS. SOMEONE HAD STRIPPED THIS SAME ASBESTOS OUT Or THE WAY TO RUN ANOTHER PIPE NEXT TO THIS LINE. IT APPEARS THAT THIS INSULATION NEEDS TO BE ENCAPSULATED. CONDITION VIVIAN SPRAGUE MNT Buske with BAR showed aw some of the asbestos bags and how they cone apart in damp weather. These bags are app. $5 ea. Maybe we should look for another vendor or supplier with better-nade bags. At $5 ea. thera is no telling how many are thrown away not useful every year. CONDITION PHIL SCHMIDT MNT While cleaning out the box where we keep old starters, and altenators, I found two sets of broke shoes that had been placed in the box for disposal. The shoes contained asbestos. 05/11/92 MACHINE SHOP 190607 MSHOF SUBTOTAL: 1 CONDITION EDDIE BALFANZ MIT While cleaning up around balancing aachine, found a piece of asbestos. 02/14/92 UNIT TANKS 224453 02/25/92 ODU SURFACTANTS 224149 03/26/92 ODU 224495 10/20/92 NEST OF ODU PIPE CONDITION JOEY MITSOVERLING MNT While naking our Friday aoming cleanup in unit, found an asbestos gasket on ground by unit tanks. CONDITION MNT FOUND A LINE OF ASBESTOS WITH SOME PLASTIC SECURING THE ENDS AS TO ENCAPSULATE. CONDITION BB BROWNING MNT An asbestos gasket was laying on the pad. CONDITION MNT 030811 230492 OOU SUBTOTAL: 4 KMX WEN WORKING AT THE PIPE RACK I FOUND A GASKET THAT HAS ASBESTOS. 02/14/92 E. SIDE 11 OLEFINS 204477 CONDITION LOUIE KRAMER KWT Fount 1 1/2* used asbestos gasket on pad a. sida II Olefins. OU SUBTOTAL: 1 07/07/92 OLEFINS 11 205153 11/10/92 GAS 2 SEPARATIONS 232995 11/23/92 GAS 2 SEPARATIONS 172457 OL2 SUBTOTAL: 3 CONDITION RANIER BRIGHAM MNT Found asbestos insulation on 1 1/2 or 2' conduit lina on aast sida of compressor bldg, basida cross ovar; insulation has savaral cracks in it. CONDITION MNT WILE WORKING AT GAS 2, I NOTICED SOME ASBESTOS INSULATION LAYING ON TOP Or BLDG. 504. CONDITION MT SAW SOME ASBESTOS LAYING ON THE CEMENT FROM A FLANGE ABOVE. 05/22/92 OXI 222524 CONDITION TIMOTHY JANCA MIT While anptying trash cans in Oxide unit, I again discovered significant amounts of natal scrap, including t9 vira, insulation jacketing, asbestos-wrapped tubing, etc. 06/04/92 OXIDE 145453 CONDITION CRAIG STRAKOS MNT Found asbestos gasket in regular trash can. 06/10/92 OXIDE 222543 CONDITION BUDDY PERKINS MNT Found part of asbestos gasket on roadway. 06/29/92 169493 SOUTH WEST CORNER OF OXIDE I CONDITION CONST At the south west corner of Oxide I some insulation which probably fell from rack was gathered up and left lying on the grond next to beam with no barricade or signs around it. Exposed insulation was not bagged or labeled. Insulation looks like possible asbestos. 04/24/92 BLDG. 221 214054 CONDITION BILL VINCENT MNT Found a asbestos flax gasket that was not completely covered, exposing some asbestos. 09/15/92 SOUTHSIDE BLOCK 4 143776 CONDITION JULIA SMITH PLE Saw insulation that I suspected was asbestos. The material was flaking off. 10/24/92 OXIDE II 227079 CONDITION MNT WILE WORXING IN OXIDE, CAME ACROSS ASBESTOS GASKET ON GROUND. OKI SUBTOTAL: 7 05/01/92 P-1 PELLETING AREA 147016 PPU SUBTOTAL: 1 CONDITION ARMANDO GARCIA MNT Found asbestos gasket laying on ground. 09/23/92 ODU 190203 PRJ SUBTOTAL: 1 CONDITION KEN DORRIES MET While working on steam leaks on BJCB steam line, noticed tubing wrapped with asbestos tape. 03/05/92 P/S SHOP 135779 PSHOP SUBTOTAL: 1 CONDITION YOLANDA PADRON MNT Two safaty valves from N. field came in with asbestos gaskets. i> 030812 06/08/92 STREET HI LAY OOMI 207424 YARD ROAD SUBTOTAL: 1 CONDITION JOHN BRADLEY MIT I found several asbestos gaskets on the road. 04/27/92 NORTH SIDE REPAIR 20S698 SHOP SSHOP SUBTOTAL: 1 CONDITION TOM TOLER MIT Found an asbestos gasket lying on the concrete right outside doorway. 10/15/92 SEMICON CONTROL BOOM CONDITION TIM MANNING SHT 245077 When opening a desk drawer in the control rooa, discovered two full rolls of asbestos wrap insulation. SCO SUBTOTAL: 1 02/01/92 41H LEVEL OR 220282 PELLETING BLDG. SHF SUBTOTAL: 1 CONDITION SHT FOUND ASBESTOS GASKET LYING ON THE GRATING 11/10/92 FURNACE SHOP 231307 CONDITION MIT AFTER ALL THE RAIN WE HAD TUESDAY WE HAD A LAKE ON THE SOUTH SIDE OF THE FURKACER. WHEN THE WATER WENT DOWN I FOUND AN ASBESTOS GASKET ON THE SHOP SUBTOTAL: 1 10/29/92 PIPE RACK SOUTH OF 244924 OOU UHSP SUBTOTAL: 1 CONDITION MIT INSULATION ON PIPE IN RACK BROKEN DOWN AND FALLING APART. ASBESTOS. POSSIBLY 01/28/92 WELD SHOP 216644 NSHOP SUBTOTAL: 1 CONDITION TOMff TUCKER JR MIT Head was delivered to weld shop with gaskets still in place. attached. Gasket naterial was asbestos. Clean tag was GRAND TOTAL: 107 030813 I CUT DBF DATE LOCATION 07/29/94 N. SIB OF COCK 25949* F80N PIPERACK BDK SUBTOTAL: 1 ON th. JOB CIA SUhMARY with tAxbestost in the description 01/01/91 to 12/31/9* TYPE DESCRIPTION CONDITION MNP I POUND SODA CANS AND TRASH IN AN ASBESTOS GASKET CAN. 07/26/91 OL1 VD AREA A 192619 CONST. COMPOUND 12/14/95 CCHPOUND AREA 272930 04/01/96 NORTH EAST CORNER 219304 P-1 CONST SUBTOTAL: 3 CONDITION KATHLEEN HUNT EVP Many bags of what appears to bo non-haz, non-asbestos insulation waste are being stored in unregistered areas, such as Olefins I Laydown area and the Construction Dept, compound. EPD, and hence TWC, have not been notified of this activity. CONDITION CONST A 5 GALLON CONTAINING CP. 10 AND A 1 GALLON JUG Or HAND SOAP WERE DISPOSED OF IN THE INSULATION BIN LOCATED ON THE EAST SIDE or BLDG 2254. THE CP.10 IS A LOCK DOWN ADHESIVE USED TO SEAL OF ASBESTOS INSULATION BY OUTSIDE CONTRACTORS. B&ft ASBESTOS ABATEMENT DOES NOT USE THIS TYPE OF LOCK DOWN. I DON' T KNOW WEHRE THESE ITEMS CAME FROM. CONDITION CONST DURING A JOB PUNNING WALK THRU I NOTICED THAT A SCAFFOLD POLE AND BASE WERE BEING SECURED TO AN EXISTING ASBESTOS INSULATED LINE WITH 9 WIRE. AS THE *9 WIRE WAS TIGHTENED TO SECURE THE BASE XT CUT (PENETRATED) INTO THE MULEHIDE EXPOSING SOME ASBESTOS INSULATION. 02/11/93 NORTH OF 2603 TANK 217495 IN N.FIELD CONDITION DIS I FOUND AN OLD ASBESTOS GASKET IN THE DITCH JUST NORTH OF 2803 TANK. 04/02/93 380 246483 CONDITION MNT ASBESTOS CAN DOES NOT HAVE A LID. 04/05/93 230312 BESIB THE MAIL RACK AT 380 CONDITION MNT THE ASBESTOS CAN AT 380 HAD COCA COLA CANS AND OTHER TRASH IN IT. CANS ARE NOT FOR ANYTHING BUT ASBESTOS GASKETS. THESE 04/16/93 380 MAIL RACK 248589 CONDITION DIS NOTICED ASBESTOS TRASH CAN WITH NO LID. 04/16/93 NORTH FIELD TANK 248583 FARM CONDITION DIS NOTICED ASBESTOS STICKERS FADED 04/16/93 NORTH FIELD TANK 2485*2 FARM CONDITION DIS NOTICED SEVERAL "ASBESTOS FREE" STICKERS ARE FADED, HARD TO DISTINGUISH. DIS SUBTOTAL: 6 01/06/93 BESIB THE MAINT. 226975 BLDG. SOUTH CONDITION WfT POUND TRASH AND OTHER DEBRIS IN ASBESTOS GASKET CAN. 05/10/93 SOUTH OF VENT STACK CONDITION MNT 250580 FOUND ASBESTOS GASKET IN TRASH CAN AT HP-II. 06/06/94 PROD. ROOM S. OF 259242 11 VENT STACK CONDITION NfT WHILE EMPTYING CONTENTS OF ASBESTOS GASKET CAN I FOUND SCRAP POLY IN BOTTOM OF CAN. 06/17/94 N.W. OF POLE BINS 259236 CONDITION MNT FOUND PAPER AND PLASTIC TRASH IN AN ASBESTOS GASKET CAN. 030814 10/11/9* HP2 FINISHING 29377* HP2 SUBTOTAL: 5 CONDITION RICHARD VALENZUELA JR SHF Asbastos material being storad right outside of tha control rooa froa tha job that took place in raaoving tha aatarial froa tha control rooa. 04/20/93 BUILDIBS 2 LAB 246495 LAB SUBTOTAL: 1 CONDITION MNT WENT TO CHECK INSULATION JOB IN LAB AND POUND 8-10 FEET OF ASBESTOS WRAP IN A SMALL TRASH CAN. 01/05/93 NORTH WEST CORNER OF CONDITION MNT 1*4722 TOUT F WHILE I WAS EMPTYING OUT ASBESTOS GASKET CANS I POUND TRASH IN THE ASBESTOS CAN. 01/13/93 LF-1 239*40 CONDITION JERRY PYKA SHF Asbastos on tubing aountad on KC-S dryer, handrail. Asbestos on tubing on raaction analyzer valva rack. Asbastos ovarhaad in tha pipa racks. Asbastos in tha finishing structura and in purification. 03/12/93 BUILDING 344-EAST 24*665 CONDITION KIT ASBESTOS CAN LAYING ON ITS SIDE. OVER BY THE WIND. CAM WASN'T OPEN, IT WAS PROBALBY BLOW 04/01/93 G5000 DELUKPER 222223 CONDITION TOMUE HOLT JR MNT Found trash in "asbastos only" containar by GSOOO Daluapar. 05/03/93 BLOCK 12 242541 CONDITION CRAIG STRAKOS MNT Soaaona put asbastos gaskat in luggar bin. 04/17/94 BUILDING 353 247862 CONDITION MNT I NOTICED THAT AN EMPLOYEE WAS USING AN ASBESTOS BAG TO CARRY HIS TOOLS AND EQUIPMENT AROUND WITH HIM. 06/06/94 BUILDING 354 259241 CONDITION MNT WHILE CHECKING ASBESTOS CANS FOR GASKETS I NOTICED THE CAPS ON THE EYE BATH WERE OFF. 02/06/96 LP1 RX 283219 CONDITION DONNIE MAREK MNT Found asbastos gaskats on N2 prhaatar piping. LP1 SUBTOTAL: 8 01/19/94 SCREEN PACK BURNER 230582 06/17/94 SCREEN PACK BURNER 247876 LP1F SUBTOTAL: 2 CONDITION MNT "ASBESTOS GASKET ONLY' DISPOSAL CAN HAD LID OPEN. THE CAN SEEMED TO HAVE BEEN RUN INTO OR KICKED IN, THEREFORE NOT ALLOWING LID TO SEAL. THE CAN IS EMPTY WITH A NEW LINER. CONDITION MNT FOUND WIRE AND TRASH IN AN ASBESTOS GASKET CAN. 06/06/94 0-500 REACTOR 246600 LP1R SUBTOTAL: 1 CONDITION MNT I FOUND NOW-ASBESTOS INSULATION IN AN ASBESTOS GASKET CAN. 05/14/93 SOUTH SIDE BLD. 11 246653 02/08/93 SWITCH RACK S. SIDE 237670 TANK FARM 01/23/95 BLDG. 165 267470 CONDITION MNT THE ASBESTOS CAN AT BLDG. 11 HAD DOMESTIC TRASH IN IT. CONDITION MIT SEVERAL SPOOL PIECES LAYING ON WHITE ROCK AND GASKETS LAYING ON GROUND (POSSIBLE ASBESTOS GASKETS) CONDITION MNT ASBESTOS GASKET ON FLANGE. 030815 02/30/96 CAS II EKL TANK 271910 02/16/96 OEU 275974 04/26/96 ENERGY SYSTEMS 266210 10/01/96 HF2 RXK 271926 09/09/96 ODU 271925 MT SUBTOTAL: 1 CONDITION nrr REMOVE ASBESTOS INSULATION ON SOUTHWEST SIDE Or THE EKL TANK. (VAL. ) THERE WAS BROKEN INSULATION THAT CAME FROM VAL. AND WAS LAYING ON GROUND. CONDITION nrr FOUND VALVE IN METAL LUGGER AT GEU WITH POSSIBLE ASBESTOS GASKET ON THEM. INCIDENT MNT WHEN SETTING 17 COOLING WATER MOTOR, HAD TWO CRANES HOOKED ON TO THE MOTOR, UPON SETTING THE MOTOR INTO PLACE THE LOAD SWUNG OVER, AFTER LETTING DOMI ON ONE OF THE CRANES, AND THE CHOKER HIT A LINE WITH ASBESTOS INSULATION AND BROKE A PIECE OFF. AFTER SETTING THE MOTOR IN PLACE RIGGER NOTIFIED THAT ASBESTOS WAS BROKE AND HE TOLD THE OM'S TO GET OUT OF THE AREA AND STOP WORK. CONDITION nvr I WAS NOTIFIED BY AN EMPLOYEE THAT THERE WAS UNIDENTIFIED GASKET MATERIAL LAYING IN THE SOUTH DRIVEWAY NEAR THE 1 VENT STACK AREA. THIS MATERIAL LOOKED LIKE IT COULD POSSIBLY CONTAIN ASBESTOS. INCIDENT NfT WORKING AT ODU ON A LINE TO STRIP ASBESTOS PUT UP GLOVE BAG AND STRIPPED LINE. THE ASBESTOS WAS SOAKED WITH CHZXXCALS. THE OttMICAL WAS CRUD TRIETHANOLAMINE. 01/06/93 NORTH NEST CORNER 226974 ODU CONDITION MNT FOUND SHEET METAL AND OTHER TRASH IN ASBESTOS CAN. 03/01/93 237639 H.4 S. PIPERACK 4TH ST. ON TOP CONDITION MNT EXPOSED ASBESTOS ON ENTIRE PIPE (ESTIMATION OF A 6-0" PIPE ON THE VERY TOP LEVEL) 06/06/94 BUTYLS TANK FARM 259229 CONDITION MNT I FOUND METAL OBJECTS AND TRAHS IN AN ASBESTOS GASKET CAN. 06/17/94 BUTYLS TANK FARM 259237 CONDITION MNT I FOUND FIBERGLASS INSULATION IN AN ASBESTOS GASKET CAN. ODU SUBTOTAL: 4 03/21/93 304 NASH RACK 241670 0L1 SUBTOTAL: 1 CONDITION MNT THERE IS AN ASBESTOS DRUM IN THE WASH RACK THAT IS FADED OUT AND NOT CLEARLY MARKED. 01/21/93 501--NORTH 207612 CONDITION ran TUBING IN SCRAP LUGGER METAL 501 NORTH WITH ASBESTOS WRAPPING ON IT. 01/21/93 500 BUILDING 207613 COMPRESSOR CONDITION Mfr TRASH INSIDE "ASBESTOS CAN" 02/10/93 UNDER 12 CO2 KETTLE 230745 CONDITION MNT IT WAS BROUGHT TO MY ATTENTION THAT AN ASBESTOS PIPE HAD BEEN DAMAGED AND NEEDED PATCHING. 02/22/93 504 SPOT 11 247033 CONDITION MNT INDIVIDUAL PICXED UP VALVE AND TOOK IT TO THE INST. GASKET ON IT. SHOP WITH ASBESTOS 03/11/93 C2H4 6 LIGHTER VS. 237651 ACETONE CONDITION MIT EXPOSED ASBESTOS INSULATION 03/01/93 C2H4 4 LIGHTER VS 237652 PROPANE CONDITION MIT EXPOSED ASBESTOS INSULATION 03/01/93 TOP MANWAY ON 237653 NORTH/SOUTH P.R. CONDITION MIT ALL JUNCTION BOXES ON TOP MANWAY HAVE EXPOSED ASBESTOS INSULATION ON THEM. JUNCTION BOXES RUN FROM P.R. MARKER 4-A 6 B SOUTH. (FROM SOUTH TO NORTH 030816 END OF CATWALX) Q 2/24/93 PIPERACK. lOA(ll) 237656 75-15 GEN. CONDITION i*rr EXPOSED ASBESTOS INSULATION OR STEAM GENERATOR 03/01/93 PIPERACK 1A TO 3A 237630 CONDITION NIT EXPOSED ASBESTOS INSULATION ON PIPE IS-34 FROM 90 DEGREE ( ELBOW) SOUTH IN PIPERACK. INSULATION IS CRACKED OPEN AND EXPOSED. FROM NORTH END OF SEPARATIONS AT BEGINNING OF RACK TO JUST BEFORE 2ND ST. RACE CROSSING. 03/11/93 PIPERACK R. 344 237650 CONDITION MOT EXPOSED ASBESTOS INSULATION ON LINES 146, 147, AND 148 MIDWAY IN LOWER WALKWAY AT 12-1 SUPPORT 03/24/93 REST OF BOILER 22 246637 ACCIDENT MIT WE WERE LOADING THE ASBESTOS TRAILER. ONE EMPLOYEE THREW A BAG ON THE TRAILER. ANOTHER EMPLOYEE GRABBED THE BAG AND THREW IT OFF THE TRAILER HITTING ME IN THE FACE CAUSING MY HEAD TO SNAP BACK. 05/25/93 GAS 2 246500 CONDITION MIT POUND 2 EMPTY DRINKING WATER CAMS AT VAN BOX ON SOUTH SIDE OF SEPARATIONS BELONGING TO ASBESTOS CREW. 04/30/93 503 SOUTH 246651 CONDITION MIT I FOUND SOME ASBESTOS INSULATION LAYING IN THE WALKWAY ON THE SOUTH SIDE OF SEPARATIONS. IT HAD FALLEN OFF OF A PIPE IN THE RACK. 10/10/93 GAS--II 254124 CONDITION MIT INSULATION LOOKED LIKE ASBESTOS LAYING BY THE DIRTY OIL TANK THAT SOMEONE REMOVED 01/05/94 SEPARATIONS 255003 CONDITION MIT SAW SOME ASBESTOS ON THE FLOOR 01/24/94 FURNACE REPAIR SHOP CONDITION MOT 230352 THERE WAS AN ASBESTOS GASKET CAN WITH NO TOP ON IT 02/10/94 W. SIDE 246725 CONDITION MOT WHILE CHECKING SCATFOLD I NOTICED SOME UNIDENTIFIED INSULATION ON THE DECK WE SUSPECTED IT TO BE ASBESTOS. 02/22/94 S. SIDE BOILER 22 246727 CONDITION MIT FOUND WRAPPING SUSPECTED TO BE ASBESTOS HANGING FROM OLD TUBING 02/22/94 E. WALKWAY SECOND 230746 LEVEL CONDITION MOT OUTSIDE CONTRACTOR WENT UNDER ASBESTOS BARRICADE. 03/22/94 REST OF MKP TANK 247054 CONDITION MOT I NOTICED SOME INSULATION ON THE GROUND, THAT COULD BE ASBESTOS. 04/29/94 E. OF 501 246590 CONDITION MOT I NOTICED WHAT APPEARED TO BE ASBESTOS INSULATION LAYING ON THE GROUND. 09/06/94 H.W. CORNER OF 260415 COOLING TONER CONDITION MIT EXPOSED INSULATION WXCX IS MARKED ASBESTOS. 09/07/94 GAS-2 MAINTENANCE 261935 SHOP CONDITION MOT SOMEONE PUT TRASH IN AN ASBESTOS CAN. 04/19/95 OLZFIHS 267293 CONDITION LEE YAXLXN MOT Found asbastos tubing wrap in doaastic trash can. 11/04/96 OL2 205226 CONDITION KEN DORRIES SHF Found Asbastos insulation on staaa tracing on rafrigaration oil lina going to cosprassor bldg. 11/04/96 OL2 205225 CONDITION KEN DORRIES SHF Found Asbastos insulation on staaa tracing on angina oil lina going to coaprassor bldg. 11/04/96 OL2 205220 CONDITION KEN DORRIES SHF Found asbastos insulation on tubing on top of biowcaso for FG scrubbars. (Abandonad tubing) 030817 11/04/96 OL2 285227 11/07/96 OL2 285220 11/07/96 OL2 285221 OL2 SUBTOTAL: 30 CONDITION KEN DORRIES SHF Pound asbastos insulation on coaprassor blowcasa tubing. CONDITION REM DORRIES SHT Noticad axposad asbastos insulation on 151 staaa haadar going froa co^. bldg, to boilors south sida of walkway. CONDITION KEN DORRIES SHF Koticad axposad asbastos insulation on abandonad staaa lina by walkway going froa coaprassor bldg, to boilars. 06/18/96 SETTLIHG BASIN 12 297964 GAS OL2 SB SUBTOTAL: 1 CONDITION PAT DUNLAP MNT Found asbastos gaskat on ground by cooling towar north sida. 01/06/94 SOUTH SIDE HALKNAX 255113 01/31/94 SOUTH SIDE 11 OXIDE 193577 axx SUBTOTAL: 2 CONDITION MIT ASBESTOS INSULATION ON WALKWAY. COULD NOT SEE WHERE IT CAME FROM. CONDITION WT WHEN I WAS DOING OUR MONDAY MORNING CLEAN UP I NOTICED SOKE INSULATION ON THE GROUND. I WENT FOR A BETTER LOOK AND FOUND IT TO 8E ASBESTOS. 04/15/93 PP-1 BLD. 11 248204 06/08/94 BUILDING 11 259231 06/18/96 PI REACTOR 297963 PPU SUBTOTAL: 3 CONDITION MNT NOTICED A TRASH CAN BESIDE BLD. BAG FOR A TRASH CAN LINER. 11 THAT HAD TRASH IN IT AND HAD AN ASBESTOS CONDITION MNT WHILE CHECKING ASBESTOS CANS FOR GASKETS I FOUND ASBESTOS CAN HAD BEEN THROWN IN METAL BIN. CONDITION PAT DUNLAP MNT Found four asbastos gaskats on third laval. 04/16/93 E & 5TH ST. 211036 BOAS SUBTOTAL: 1 CONDITION DIS PICKED UP 2" 150# ASBESTOS GASKET FROM DITCH. 12/09/92 HELD SHOP 222659 04/23/93 CARBIDE HELD SHOP 248039 06/06/94 HELD SHOP SPOT 24 246601 06/08/94 HELD SHOP 259235 12/13/94 BUILDING 165 266013 SHOP SUBTOTAL: 5 CONDITION DIS 1" PIPE FROM HP-2 IJ50751, JOB RET. 1253, BLDG. 566 SPOT 9. LARRY HERRON GAVE ME RED CARD JOB FROM SANDBLAST WHICH REQUIRED CUTTING PIPE 1/2" AND PUTTING BACK TOGETHER WITH 1" WELDED UNION. WHILE LEVELING PIPE UP TO MAKE FIT, NOTICED ASBESTOS REMAINING ON TWO OF THE FLANGE FACES. CONDITION DIS ON 12/9/92 I WROTE A CIA (AN INCIDENT) CONCERNING THE RECEIPT OF A PIPE TO BE REVISED IN THE WELD SHOP. THE FLANGES ON THIS PARTICLUAR PIPE HAD ASBESTOS ON THE FLANGE FACES. JOB REF. 1253 CONDITION MNT Z FOUND STYROFOAM IN AN ASBESTOS GASKET CAN WHEN CHANGING LINERS. CONDITION MNT THE ASBESTOS GASKET CAN USUALLY LOCATED HERE WAS MISSING. CONDITION MNT PARTS OF ASBESTOS GASKET ON FLANGE FACE OF VOLATE. 04/13/93 BLDG. 11 CONDITION MNT 030818 211030 NOTICES EMPLOYEE PUTTING TRASH IN A CAN MARKED ASBESTOS ONLY. 06/07/94 DECONTAMINATION 263065 TRAILER CONDITION MNT FOUND THAT SOMEONE HAS BEEN STEALING OUR WASHING LIQUID ITS NOT A GREAT LOSS BUT ITS STARTING TO HAPPEN MORE OFTEN TJHIS TIME HE HAVE RECOGNIZED THAT THIS INDIVIDUAL IS ALSO GOING INTO OUR DIRTY ROOM WHICH IS C0NCIDERED CONTAMINATED WITH ASBESTOS UNTIL COMPLETELY CLEANED. 06/06/94 306 EAST 259230 CONDITION MNT I FOUND ASSORTED TRASH IN AN ASBESTOS GASXET CAN. 06/06/94 S. SIDE HIGH BAX 259236 AREA CONDITION MNT POUND AN ASBESTOS GASKET CAN WITH PLASTIC CUPS IN IT. 06/06/94 INSIDE CONTROL ROOM CONDITION MNT 259234 02 UNIT I POUND PAPER TRASH INSIDE AN ASBESTOS GASKET CAN. 07/10/94 SOUTH Or 02 UNIT 260317 CONDITION KIT FOUND TRASH IN ASBESTOS CAM. NOT FOR TRASH. THE ASBESTOS CAN ARE FOR ASBESTOS GASKETS ORLY UXSP SUBTOTAL: < GRAND TOTAL: St 030819