Heating Ventilating Air Conditioning Guide 1938
Table 6. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals
(Riser No. S. Fig. 4)'
Floor of
Bldg.
1st
2nd -
Fixtures on
Floor
1 W. C.
2 W. C. 1 U. - 1 Lav.
Gfm PER Fixture
45
Maximum Gpm on Floor
45
Maximum Gpm ON Riser
45
Probable Use
per CENT)
Probable Demand Riser Gfm
100
45
Allowable Drop
Lb per 100 Ft
30
45 90 30 30
33
123
168
58
98
30
3rd
4 W. C. 2 U. 3 Lav.
45 30
3
180 60 9
249
417
31 130
30
4th
4 W. C. 2 U. 3 Lav.
45 30
3
180 60 9
249
666
24 160
30
5th
6 W. C. 4 Lav.
45 3
270 12
282
948
19 180
30
6th
6 W. C. 4 Lav.
45 3
270 12
282
1230
16 196
30
7th
6 W. C. 4 Lav.
45 3
270 12
282
1512
14 211
30
8th
6W.C. 4 Lav.
45 3
270 12
282
1794
12 215
2
Pipe Size
In.
1H
IX
2
2
2
2X 2X
4
Then the allowable drop per 100 ft will be --= 8.5 lb and the sizes shown
in Fig. 5 are based on this amount of drop. Of course the other risers will have the same maximum flows at the bottom as they -formerly had at the top, namely 215 and 122 gal,
respectively, for Risers Nos. 2 and 3.; Combining these maximum flows in the same man ner as pursued in the down-feed system it is seen that the maximum flow between Riser
No. 2 and Riser No. 3 is 255 gpm, and between Riser No. 3 and the street main, 282 gpm which at a drop of 8.5 lb gives the main sizes indicated. It will be noted that in determin ing the maximum flow in an up-feed riser it is necessary to begin at the top floor and work-down instead of beginning at the bottom floor and working up as was done in the
down-feed sizing.
-
SIZING UP-FEED AND DOWN-FEED HOT WATER SYSTEMS
Hot water supply systems, when of the circulating type, have a few differences to be considered although the same general principles of sizing apply to these lines as to the cold water lines. Owing to .the fact that there are no flush valves on the hot water piping and also because many plumbing fixtures have no hot water connections, the sizes of the hot water piping in general will be considerably less than the cold water piping in the same building. On the other hand it is almost invariably
794
Chapter 43. Water Supply Piping and Water Heating
Table 7. Typical Calculation of Pipe Sizes on Down-Feed Riser with Flush Valve Water-Closets and Urinals
(Riser No. S. Fig. 4)
Floor
op Bldg.
Fixtures on
Floor
1st 2nd
1 S. S.
3 W. C. 1 Lav.
3rd 2 Lav.
4th
3 W. C.
1 Lav.
1 S. S.
5th . 6th 7th 8th
1 S. S. 1 S. S. 1 S. S. 1 S. S.
Gpm PER Fixture
4 45
3
3 45
3 4
4. 4 4/ 4
Maximum Gpm ON
Floor
Maximum Gpm ON Riser
Probable Use
(per cent)
Probable Demand
Riser Gpm
Allowable Drop
Lb per 100 Ft
4 4 100
4
30
135 3
138 142 63 89
30
6 148 61 90
30
135 3 4
142
290
41 119
30
4 294
. 41
120
30
4 298
40 120
30
4 302
40 121
30
4 306
40 122
2-
Pipe Size In.
X.
IX ix
2 2 2 2
3
required that a gravity circulation be kept up in such hot water lines and
this often has a considerable influence on the size. There'are three methods of arranging circulation lines, as follows:
1. By using the,plain up-feed with a returncarried back from the top of.the riser and
paralleling it. '
' ." '
`
2. By carrying a supply riser up in one location thus supplying fixtures on up-feed, then-crossing over at the top and coming down past, another collection of fixtures and supplying these by a down-feed.
3. By carrying all of the water to the top of the building and dropping risers wherever
needed, feeding all hot water on a down-feed system.
..
Table 8." Size of Distribution Main for Down-Feed Systems (See Fig. 4)'
Riser No.
1 2 3
Maximum ` Gpm Riser
1038 1794
306
Maximum Gpm Main
1038 2832 3138
' Probable Use
(per cent)
18 9 9
1 Probable Gpm
187 255 282
.
Allowable Drop
Lb per 100 Ft
' Size op '
Main In.
24 24 25
In the first instance the up-feed riser may be sized for the same pressure, drop as used for the cold water riser and, from the top of the riser just below the top fixture connection, a return circulation line may be carried back to the main return line in the basement and connected through a check valve, set on a 45-deg angle, and a gate valve; these return circu lation lines should never be less than % in., and on the farther half of the risers, not less than 1 in. to favor circulation in the far end. Typical top and bottom connections for such risers are shown in Fig.; 6.
795