Document NER7Vwm8EOmNJbn0vpv0LmqpD
HEATING VENTILATING AIR CONDITIONING CUIDE 1944
will vary as given in Equation 8 where V is the velocity of the air through the grille.
db (change) = 55 logic
(8)
For a change in blade setting Equation 9 applies and in this case the total pressure is measured directly behind the face of the grille. For a typical air conditioning grille the noise level at the grille face may be approximately 48 db with a total pressure behind the grille of 0.1 in.
The resultant room noise level can be approximated by Equation 10.
Level -
"*"] ' ' "*
Grille Selection
In practice the allowable total sound arid the required air flow are usually known, and it is desired to determine the maximum allowable velocity. In comparing sound ratings of various grilles several factors must be known if the information is to be properly applied:
1. The threshold intensity on which the decibel ratings are based. 2. The distance from the grille at which data were taken. 3. If stated as loudness level versus velocity for a given grille, the core area (not nominal area) must be known. 4. The sound absorbing characteristics of the test room. 5. Whether or not corrected for test room loudness level: if not, the room level (without grille noise) must be known. 6. Methods used for recording data. (Characteristics of sound meter). 1
Since total loudness and air flow are both functions of velocity and area, the solution of the problem implies a trial and error method. It has been found possible to present these data with sufficient practical accuracy as
,632
CHAPTER 33. SOUND CONTROL
a family of uniform curves, as illustrated in Fig. 5, which are based on these assumptions:
1. Threshold intensity = 10-16 watts per square centimeter9. 2. Microphone location 5 ft from lower edge of supply opening on a line downward at 45 deg and in a plane bisecting the supply opening perpendicularly. 3. Where data are given as loudness level versus velocity, the rating is per square foot
of core area. 4. The room is assumed to have 100 sabines absorption. 5. Plotted data are loudness levels of supply openings only, correction having been
made for test room level. 6. Data taken with a direct reading sound-level meter with frequency weighing
network intended to approximate the response of the human ear.
If the published ratings are in terms of decibels per square foot, cor rection must be made for area to secure the total sound level of supply
openings of more or less than one square foot area from Equation 11.
Decibel Addition = 10 logioA
(11)
where
A - core area, square feet.
With Fig. 5 it is possible to find directly the velocity in feet per minute which will give a predetermined total loudness at a predetermined rate of flow expressed in cubic feet per minute. The values used are arbitrarily chosen for the purpose of discussion and do not necessarily represent data referring to any particular design of air supply opening. A correction chart is shown in Fig. 6 for a room having a sound absorption other than
100 sabines.
Example S. Determine the core area (see Chapter 31) of an air supply grille which will maintain a noise level of not more than 40 db in a room having 100 sabines of sound absorption, if an air volume of 2400 cfm is required to maintain the proper air con
ditioning.
Solution. Assuming a grille noise rating of at least 5 db below the noise level of the room. Fig. 5 shows that the limiting grille velocity for a total loudness of 35 db is about 725 fpm and the core area becomes fixed at 2400 725 or 3.31 sq ft.
If the room absorption had been greater, the previously selected velocity of 725 fpm would be safe, since the loudness reduces. If the room absorption had been 200 sabines a correction of plus 1.3.shouId be made by reference to Fig. 6, and the permissible velocity becomes that corresponding to a total loudness of 36.3 or approximately 800 fpm.
If the room had been highly reflective with an absorption of less than 100, the cor rection would Be much more important. For instance, for a room of 35 sabines a cor rection of minus 3 db should be made and the maximum velocity corresponding to the
32 db total loudness would be approximately 600 fpm.
Where more than one supply opening must be considered, the problem is more complicated. If a similar supply.opening is added in a far corner of a highly absorbent room, the change in noise level at the 5 ft station at the first supply opening is small; however, if the room is small, or highly reverberant or both, the intensity at the 5 ft station may be almost doubled and the noise level increased nearly 3 db thereby. -The simplest