RETURN TO: kjk DATE er.i'oor ul, 1^72 STANDARDS section - DESIGN DIVISION engineering department WILMINGTON, DELAWARE SERIAL LETTER uul. RETURN TO STANDARDS SECTION BY subject. Sl+T - ASBESTOS DUST EXPOSURE, MEASUREMENT AND CONTROL October 16, 1972 (Second review)_____________________________________________________________ A standard must redact a "minimum essential" installation. A "minimum essentiol standard is one that places primoiy emphasis on the lowest cost facility, in terms of both initio) installed and continuing cost, consistent with reasonable safely and return an investment considerations. "Continuing cost" includes oil costs associated with maintaining and operating the facility, including such indirect costs as lost profits resulting from unreoson* able outages. Pleose direct your comments accordingly. 1. [ 1 Approved 2- Approved with comments or suggestions given below ' Noted -- Not qualified to comment < Disapproved for reosons noted below Comments (Pleose print clearly. To help subcommittee, be specific. Provide exomples, reasons, give suggested rewording, etc) R.fr.2 This section specifies that supplied-air or self-contained resplratc ------ eha-1-1 be--w<rr>-t)y--etnployoeg-enfHtfSGd--ln-dlawafttl-l-n^--asbestos insulation. This assumes that permissible JWA exposurs Hmtt; ars antomatloally------ exceeded on an dlsmtml-.Hrnr npArahlnrui-flad hA.nnAj reapi rnt--nry pr/dAr^vi. -- devl cp*. . are--automatic al-ly-necessary ------------------------- ;-------------------------------- -- We believe Section 3.^.2 should be amended to specify that resplratc protection shall be worn on asbestos Insulation dismantling operations anytime the asbestos dust concentration cannot be controlled below permi ____ slble TWA exposure celling limits by .dampening with water or other-----suitable means.______________________________________ _________________________________ M.2 This section Is not very clear. What does"----- and be required to-do s----- " refer to? Some amplification appears In order for clarity. 6.(1 Is there sound justification for including an unexposed filter for --------analysis .aJnnp; wlt.h ear.h anmpl eted sample? TM b drmhlea aampTp imnlysln costs and further loads up analysis technicians resulting In even slower return of analysis results._________ _____________________________________ ________ .This stondord might b referred to 0 5 {-10 25^ 50 75 100 limes per yeor. SIGNED. , plant or dept Belle Plant _date_2z1P-72 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 - PUP 0902982 SC-DP-03915