Document NE65ry8m36YovxQbbkL17wJrE

J.A. File No. 30-C -l (August, 1956) Redflash boiler oil, gas or coal-fired American-<*>tadaid hot water or steam heat 12398 A.I.A. Fife No. 30-C-l (August, I 956) supply I gas-fired G-2, G-4 and G-6 indirect type ("IS") steam boilers for hot water supply typical "IS" installation TEMPERATURE AND PRESSURE RELIEF VALVE COLO WATER INLET AIR VALVE DISCHARGE TO DRAIN HOT MATER OUTLET TANK HCRMOMETER RETURN FROM FIXTURES 'FUOOP LINE standard "IS" equipment -- G-2 all-purpose (steam) In addition to regular equipment furnished for G-2 allpurpose steam boilers, "IS" boiler equipment includes American-Standard CA-666 immersion operating control for use in storage tank. G-4 (sfeam) and G-4 (sfeam) American-Standard CA-666 immersion operating control for use in storage tank. American-Standard diaphragm gas valve; Saso automatic pilot switch for non-100% shut-off (100** shut-off controls for LP-air and LP gases consist of Baso combination pilot switch and valve with auxiliary Baso pilot valves. Optional other gases); American-Standard 450-BA-l boiler pressure limit control; resetting low water cut-off; manual shut-off valve; gas pressure regulator (except for LP-gas); steam gauge; safety valve; boiler drains and pilot cocks; insulated jacket; draft hood. optional equipment G-2 a/f-purpose (steam) Runner type pilot ignition for use with listed gases (except for G-23-F) if specified on order furnished to meet local Utility codes. Push button electric ignition for use with listed gases. Floor shield for combustible flooring. Add suffix letter "C to boiler number. G-4 (steam) Runner type pilot for mfd.. nat. and mixed gas non-100% shut-off furnished if specified on order to meet local Utility codes. G-4 (steamy and G-6 (steam) Pusn button electric ignition for use with mfd.. nat ana mixed gas non-100% snut-off furnished if specified on order. ratings boiler number manufactured, Natural and Mixed gas; LP-Air gas--525-1400 Btu; LP gas A.6A. input Btu/hr A.G.A. output Btu/tir rating-gallons water per ftoura 60* rise 60* rise 100* rise G-23 FG steam 60,000 48,000 96 71 58 G-24 G steam 90,000 72,000 144 107 86 G-25 G steam 120,000 96,000 192 143 115 G-26 G steam 150,000 120,000 240 179 144 G-27 G steam 180,000 144,000 288 215 173 G-28 G steam 210,000 168,000 336 251 201 G-29 G steam 240,000 192,000 384 287 230 G-210 G steam 270,000 216,000 432 323 259 G-211 G steam 300,000 240,000 480 359 288 Substitute letter " F" for flush or "D" for deluxe jacket. G-44 steam G-45 steam G-46 steam G-47 steam G-48 steam G-49 steam G-410 steam G-411 steam 180,000 144,000 290 215 175 240,000 192,000 385 290 230 300,000 240,000 480 360 290 360,000 288,000 575 430 345 420,000 336,000 670 505 405 480,000 384,000 770 575 460 540,000 432,000 865 650 520 600,000 480,000 960 710 575 G-66 steam G-67 steam G-68 steam G-69 steam G-610 steam G-611 steam G-613 steam G-615 steam G-617 steam G-619 steam G-621 steam G-622 steam G-625 steam G-628 steam G-631 steam G-633 steam G-637 steam G-641 steam 650,000 780,000 910,000 1,040,000 1,170,000 1,300,000 1,560,000 1,820,000 2,080,000 2,340,000 2,600,000 2,730,000 3,120,000 3,510,000 3,900,000 4,160,000 4,680.000 5,200,000 520,000 624,000 728,000 832,000 936,000 1,040,000 1,248,000 1,456,000 1,664,000 1,872,000 2,080,000 2,184,000 2,496,000 2,808,000 3,120,000 3,328,000 3,744,000 4,160,000 1040 1250 1460 1660 1870 2080 2500 2910 3330 3750 4170 4370 4980 5600 6250 6660 7480 8330 780 935 1090 1250 1410 1560 1870 2190 2500 2810 3120 3280 3740 4210 4680 4990 5610 6250 624 748 874 1000 1120 1250 1490 1750 1990 2250 2500 2620 2900 3360 3740 4000 4490 5000 For altitudes above 2000 ft., ratings should be reduced at the rate of 4% for each 1000 ft. above sea level. .';Am e rican -<$t an d ard 12399 conversion burners lodel IN Inshot gas conversion burner -- ^7tliJRSlH factory assembled (controls regularly furnisH are for 115 volt, 60 cycle current) 4*SJ - -x:''. t.V.^. tg.....r...c....w.... - ratings draft hood, Hm pipt dimensions A.GJL ratings- Btu input per heur model Nat and Mxd gee Mfggee min max min max IN-150 IN-245 IN-275 80,000 95.000 95.000 150.000 80,000 150,000 245.000 not available not available 275.000 not available not available Gas valve sizes: Vi? inch for IN-150 nat and mxd gases; Vt inch for all other models. input range Btu par hour draft heed and flue pipe sixes inches minimum to 120,000 5 120,000--180,000 6 180.000--250,000 7 250.000--320,000 8 325,000 maximum 9 If flue pipe exceeds 10 ft in length, or contains more than Z elbows, use next sixe larger draft hood and flue pipe. inputs for Arcoleader and Arcoliner boilers in-isob IN-2450 1N-27S0 IN-27SB bailer medal nat mxd mfd nat mxd ONLY nat mxd ONLY maximum gas inputs net mxd ONLY a 3 section 4 saction S section t section Arcoleader Arcoliner 115,000 120,000 160,000 170,000 210,000 200,000 260,000 A' B burner size type of gas a not recommended for gas firing. Lower inputs may be used Jo_conform with the load installed on the boiler, in these cases, a smaller size burner may be selected to meet this requirement. dimensions (inches) Arcoleadcr packaged oil-fired boiler is easily converted to gas-fired heating with the compact Inshot burner. gas inlet front view side view flame spreader standard equipment American-Standard CA-412 thermdstat. Runner pilot ignition. Manual shut-off valve. Control housing. Stainless steel flame spreader. Pilot throttling valve. Pilot filter--with mfd gas burners only. Two mam burner orifices: one drilled for minimum input, factory installed; the second, also drilled for minimum in put, can be drilled to other Inputs as required. modal. IN-150 and IN-245 American-Standard V-600 series combination gas valve, pressure regulator and safety pilot switch, transformer, manual opener. modal IN-275 General Controls KX3H quiet solenoid gas valve, plug-in safety pilot switch, transformer, manual opener. Gas pres sure regulator. optional equipment Self-energizing controls: General Controls T80-A thermo stat, B-60 gas valve and PG9 pilot generator -- if desired, specify on order: burner model IN-150 IN-150 IN-245 IN-275 type of gas Nat. and Mxd. Mfd. Nat. and Mxd. Nat. and Mxd. Select from list below special limit control which must be used with self-energizing controls. 100% safety shut-off, all models, specify on order. Pilot filter--regularly furnished only for Mfd. gas. If desired for Nat, and Mxd. gas, specify on order. instructions for ordering Orders must specify: 1. Type of gas. 2. Btu (heat value of gas) and specific gravity. 3. Pressure available at outlet of gas meter. 4. Optional controls, if Oesired. Note. For orifice drill sizes -- Inshot mam burr optional controls for self-energizing (millivolt) application: number description L-52A10A1A 700-D S44A332 S44A502A104 General Controls immersion limit control General Controls pressure boiler limit control, scale 0-10 lbs. General Controls warm air limit control General Controls fan and limit control page 20 12400 < conversion burners oil Arcoflame arcoflame burner models used with American-Standard oil heating units burner number possible oil firing capacity gallons par hour minimum maximum air tuba affective length diameter mounting used an American-Standard beating unit PH2-5 0.65 3.00 5' 4' hanger Arcoleader boiler--all sizes A-504 PH2-6 0.65 3.00 6%' Arcoliner boiler--all sizes 4* hanger Severn boiler--all sizes Oakmont boiler--all sizes LF-A 3.00 7.00 6%" 6' flange A-505--A509 LF-E 3.00 7.00 6%* 6' flange Exbrook boiler--all sizes ES-2-6 0.70 1.50 6%' Arcoliner boiler--3 & 4 section 4' hanger Severn boiler--#17 Oakmont boiler--#84 Up to 1.000 feet altitude. Reduce by 4% for each 1.000 feet altitude above sea level. Possible maximum firing capacity not always used--see catalog or nameplate firing capacity for listed heating unit. arcoflame burner models for boiler conversion burner number possible oil firing capacity gallons par hour minimum maximum a air tuba effective length inches diameter inches mounting PH 2- 8 PH 2-15 PH 2-23 0.65 0.65 0.65 3.00 3.00 3.00 IVz 4 pedestal 14Vz 22Vz 4 4 or flange L-I 3.00 7.00 11 Vs 6 pedestal L-3 3.00 7.00 21 6 pedestal ES-2- 8 ES-2-15 ES-2-23 0.70 0.70 0.70 1.50 1.50 1.50 7Vz 4 pedestal 14V4 4 or 22Vz 4 flange Up to 1,000 feet altitude. Reduce by 4% for each 1.000 feet altitude above sea level. Measured from air tube mounting bolts to end of air tube. serves boilers wi th maximum installed radiation a nonmal piping insulated Btu/hr square feet water or steam water (150 Btu) steam (MC Btu) 204,800 204,800 ' 204,800 477,850 477,850 102,400 102,400 102,400 1365.3 1365.3 1365.3 3285.7 3185.7 682.7 682.7 682.7 853.0 853.0 853.0 1991.0 1991.0 426.5 426.5 426.5 general information Model PH2-5 (or Arcoleader and A-504, and Models PH2-6 and ES-2-6 for Arcoliner, Oakmont and Severn oil heating units are furnished with hanger mounting; mounting acces sories packed separately and are different for each oil heating unit. Specify on order which is desired. Models PH2 and ES-2 burners with 8", 15" and 23" air tube lengths are available with pedestal or flange mounting bracket, packed separately. Specify on order if pedestal or flange mounting bracket is desired. Factory installed solenoid cut-off valve is available for model PH2 burners. If desired, specify with suffix ``M", for example, PH2-6-M. When ordering Arcoflame oil burners be sure to specify nozzle size desired. Nozzles and strainers are as follows; For model PH2--Hollow cone, 60" or 70", 0.65, 0.75, 0.85, 0.90, 1.00. 1.10 and 1.25 gph. Solid cone. 60" or 70\ 1.35, 1.50, 1.65. 1.75, 2.00, 2.25, 2.50. 2.75 and 3.00 gph. For model ES-2: Hollow cone. 80 = . 0.75, 0.85, 1.00, 1.10, 1.25. 1.35 and 1.50 gph. For models L. LF Hollow cone. 80 = . 3.00, 3.50. 4.00 and 4 50 gpn: 60 :, 5 00. 5.50. 6.00, 6.50 and 7.00 gpn. Two-stage fuel unit is available with models PH2 and ES-2 Arcoflame oil burners, and will be furnished when speci fied on order. Two-stage fuel unit is regular equipment with model L Arcoflame oil burners. Vapor installations: Substitute 450-BC-l vapor limit control for 450-BA-l pressure limit control with No. 11 or No. 12 control sets. Electric clock thermostat: Substitute T 852 for CA-412 Thermostat; specify on order control set number with suffix "B". Method of fuel atomization--Mechanical pressure--100 psi. Air supply--Low pressure with squirrel cage fan. Ignition--Intermittent spark, all models. Constant ignition can be used if desired. Motor--PH2 and ES-2 Burners: V hp--1750 rpm. L, LF-A and LF-E Burners.- V, hp--1750 rpm. Approval--All Arcoflame Oil Burners (60 cycle, 115V) are listed by The Underwriters Laboratories, Inc., for No. 1 and No. 2 commercial fuel oil, comply with Commercial Standard CS-75, and are approved by the New York City Board of Standards and Appeals, by the State Fire Marshal of the Commonwealth of Massachusetts and by the Depart ment of State Police, State of Connecticut. .^American-/Standard 12401 46 conversion burners oil Arcoflame Arcoflame Oil Burners are sold only in combination with American-Standard CA-701 Stack Control and with one of the standard Arcoflame Control sets listed below. The room thermostat and other controls are manufactured by and for American-Standard and enjoy a high reputation for skillful design and precision manufacture that assures accurate performance. control sets Arcoflame standard control sot number stack number contents of Acroflame standard control sots instnimont No. 11 steam For boiler without year-round domestic hot water. CA-412 450-BA-l thermostat pressure limit control No. 12 steam For boiler with year-round domestic hot water; built-in heater. CA-412 450-BA-l CA-666 thermostat pressure limit control immersion operating control No. 13 water For boiler without year-round domestic hot water; immersion control tor new boiler. CA-412 CA-655 thermostat immersion limit control No. 23 water For boiler without year-round domestic hot water; constant circulator operation. CA-412 CA-655 CA-666-R thermostat immersion limit control rev. acting low limit control No. 14 water For boiler without year-round domestic hot water; clamp-on control for existing boiler. CA-412 251-MJ thermostat clamp-on limit control No. 15 water For boiler with year-round domestic hot water; storage4ank heater; using circulator. CA-412 CA-655 CA-666 CA-295 thermostat immersion limit control immersion operating control relay transformer No. 16 water For boiler with year-round domestic hot water; built-in tankless heater; using circulator. CA-412 CA-655 CA-666-DT CA-295 thermostat immersion limit control immersion control double throw switch relay transformer No. 26 water For boiler with year-round domestic hot water; built-in tankless heater; using circulator. CA-412 CA-655 CA-666-AO CA-295 thermostat immersion limit control immersion control double throw switch with adjustable differential relay transformer No. 16-Z water 2-Zone control, for boiler with year-round domestic hot water; built-in tankless heater; using circulators. NOTE; For each additional zone, add 1 No. CA-412 thermostat and 1 No. CA-295 relay transformer. No. 19 warm air For gravity furnace. 2 CA-412 CA-655 CA-666 CA-666-R 2 CA-295 CA-412 CA-805 thermostats immersion limit control immersion operating control rev. acting low limit control relay transformers thermostat limit control No. 20 warm air For forced warm atr unit. CA-412 CA-815-S thermostat fan and limit control When ordering Nozzles be sure to specify solid or hollow cone nozzle and size desired. Nozzles are shown on pages 45 and 50. selecting the proper size nozzle for the burner Boiler efficiencies range from 50% to 80%. The latter is used with some boilers designed for oil burning. CONVERSION BOILERS are coal burning boilers converted to oil. For rapid circulation: OIL BURNING boilers CONVERSION boilers for steam (240 Btu) nozzle size = installed radiation (g p.h.) 300 installed radiation 250 for water (150 Btu) nozzle size = installed radiation (g p.h ) 500 installed radiation 400 The Net installed radiation, sauare feet, plus the equivalent load of the domestic hot water or otner appliances connected to the Odder, equals the INSTALLED RADIATION. 12402 dimensions and data--{inches) burners | 011 Arcoflame model PH2 model L (pedestal mounted) model PH2-5 A 14% BS diameter air tube-4' PH2-f 15Vi 6% PH2-2 16% 8 PH2-15 23% IS PH*. 31% 23 models LF-A, LF-E (flange mounted) model ES-2 12403 OIL CONNECTION combustion parts AOJUSTMINT HOCK ADJUSTMENT HOCK SCtlW combination number i 2 3 4 firing rata tph .65 to 1.10 .90 to 1.25 1.30 to 1.75 1.80 to 2.302.35 to 3.00 static disc marking .65 to 1.10 .90 to 1.75 .90 to 1.75 1.80 to 3.00 1.80 to 3.00 turbulator marking .65 to 1.10 .90 to 1.75 .90 to 1.75 1.80 to 2.30 2.35 to 3.00 nszzla spray angla 1 typa 60"-70" Hollow 60"-70" Hollow 60"-70" Solid 60-70" Solid 60'-70 Solid model L-- air diverter and electrode setting MIN. CLEARANCE FROM ELECTRODES TO METAL PARTS TOP VIEW ELECTRODE HOLDER SET SCREW size of nozzle--hollow cone--gallons per hour . . . spray angle degrees............................................................... dimension "D" inches.......................................................... "D" is distance from Oiverter to Nozzle Tip 3.00 0 CO O 00 o 00 00 3.50 4.00 0 v 4.50 V* 5.00 60" Vi 5.50 6.00 60" 60" v V* 6.50 60" Vz 7.00 60" Vz model ES-2 fuse on/y with 800 hollow <one nosxlo) P L *M STa 01L lZ E ft 12404 ( *V>. .:5'',r;^3 V- combustion chambers heat Lib-O-Rator moldked,rcfra''or'',, combustion chambers heat Lib-O-Rator Heat Lib-O-Rator Molded Refractory Combustion Chambers are de signed for and can be used with Models PH2, LF-A, LF-E, and ES-2 Oil Burners and fit the following Boiler-Burner Units: boiler Arcoliner Oakmont Severn A-5 Exbrook 153-T 154-T 155-T 156-T 84 85 86 87 88 89 17 21 25 29 33 37 A-504 A-505 A-506 A-507 A-508 A-509 A-510 A-511 207 208 209 2010 2011 2012 2013 boat Lib-O-Rator number 4 5 6 00 1 2 3 1 2 3 14-A 15-A 16-A 17-A 7 8 maximum firing rate tPh 1.35 1.65 2.00 1.50 1.75 2.25 3.00 1.75 2.25 3.00 2.55 3.30 5.55 7.65 4.50 6.50 dimensions size no: 00, I, 2, 3, i-s, 2-s, 3-s, V i a plan view front viaw size no: 4, S a $ A-5 boiler plan view sectional view 4 section boiler sectional view 5 thru 11 section boiler chamber no. 14-A 15-A L6-A 16-A 16-A 17-A 17-A 17-A no. of sections 4 5 6 7 8 9 10 11 A 15Vz 15Vi 21V2 21Vz 2IV2 27V2 27Vz 27V2 12405 AMERiCAJj-^tandard combustion chambers Refractory made from combustion chambers firebrick < jMa ? : * V DRAFT side view (cutaway) for nozzles below IV* gallons Fig. 1 side view (cutaway) for nozzles of IVi gallons and over Fig. 2 DRAFT dimensions burner model nozzle size epn PH2 L, LF ES-2 0.65* 0.75* 1.00* 1.25* 1.35* 1.50 1.65 1.75 2.00 2.25 2.50 3.00 3.00 3.50 4.00 4.50 5.00 5.50 6.00 6.50 7.00 0.75o 1.00* 1.35* 1.50 spray ancle and typo cone (H=hollow; S=olid) combuition clumber >ize-inches L w Ha floor ol C.C. min. watt to C.L. of thickness nozzle "C" inches 60'Hor70*H 7 7 14 8 8 14 ,"r 10 10 14 11 11 14 60* S or 70 S 12 13 11 11 14 14 " 14 12 14 15 12 14 It 15 12 14 " 16 13 14 r 17 13 14 " 18 14 14 4 4V4 5 5 5 5 5V4 5Vi 5V4 6 6 6-6V4 2V6 2Vz 2V4 2Vz 2Vz 2Vt 2Vz 2Vz 2W 2Vz 2Vz 2Vz 80 "H ** " 60 H " 16 18 18 16 18 18 18 18 18 20 20 19 20 22 20 22 22 20 22 22 20 24 22 20 24 24 22 8 8 8 9 10 10 10 11 11 4 4 4V5 4Vz 4V4 4Vz 4Vi 4Vi 4V2 80H n II 11 11 14 12 12 14 13 13 14 14 14 14 5% 6 6Vz 7 2Vz 2Vi 2Vt 2Vi The height of combustion chamber "H" is a minimum. The fire" brick should always be carrrad high enough to cover 2 inches of water backed surfaces. a For nozzle sizes below 1.50 gallons per hour, build chamber rec* tangular; see Fig. 1. For nozzle sizes of 1.50 gallons per hour or larger, build chamber as shown in Fig. 2. NOTE: Use Nozzles with Spray Angles specified in table above. Do not attempt to bum more oil with these burners than specified on page 45. If width of the larger sized chambers shown in the table cannot be obtained, increase length of chamber by amount of width re* duced. Never reduce width by more than 3". A-5 boiler A-7 boiler ' i TO 3-^ tl 3Vr ill- no. of sections A B 5 16 18 6 18 18 7 20 22 8 22 22 9 24 22 10 24 22Vz 11 26 22Vz sectional view 4 section boiler sectional view 5 thru 11 section boiler front view cutaway A-70B-SO thru A-712-SO boiler no. chamber length (inside) A-705 A-706 A-707 A-708 A-709 A-710 A-711 A-712 27Vi 32Yi 37Vi 38 41 44 47 50 12406