Document NE65ry8m36YovxQbbkL17wJrE
J.A. File No. 30-C -l (August, 1956)
Redflash boiler
oil, gas or coal-fired
American-<*>tadaid
hot water or steam heat
12398
A.I.A. Fife No. 30-C-l (August, I 956)
supply I gas-fired
G-2, G-4 and G-6
indirect type ("IS") steam boilers for
hot water supply
typical "IS" installation
TEMPERATURE AND PRESSURE RELIEF VALVE COLO WATER INLET
AIR VALVE
DISCHARGE TO DRAIN HOT MATER OUTLET
TANK HCRMOMETER
RETURN FROM FIXTURES
'FUOOP LINE
standard "IS" equipment -- G-2 all-purpose (steam)
In addition to regular equipment furnished for G-2 allpurpose steam boilers, "IS" boiler equipment includes American-Standard CA-666 immersion operating control for use in storage tank.
G-4 (sfeam) and G-4 (sfeam) American-Standard CA-666 immersion operating control for use in storage tank. American-Standard diaphragm gas valve; Saso automatic pilot switch for non-100% shut-off (100** shut-off controls for LP-air and LP gases consist of Baso combination pilot switch and valve with auxiliary Baso pilot valves. Optional other gases); American-Standard 450-BA-l boiler pressure limit control; resetting low water cut-off; manual shut-off valve; gas pressure regulator (except for LP-gas); steam gauge; safety valve; boiler drains and pilot cocks; insulated jacket; draft hood.
optional equipment G-2 a/f-purpose (steam)
Runner type pilot ignition for use with listed gases (except for G-23-F) if specified on order furnished to meet local Utility codes. Push button electric ignition for use with listed gases. Floor shield for combustible flooring. Add suffix letter "C to boiler number.
G-4 (steam) Runner type pilot for mfd.. nat. and mixed gas non-100% shut-off furnished if specified on order to meet local Utility codes.
G-4 (steamy and G-6 (steam) Pusn button electric ignition for use with mfd.. nat ana mixed gas non-100% snut-off furnished if specified on order.
ratings
boiler number
manufactured, Natural and Mixed gas; LP-Air gas--525-1400 Btu; LP gas
A.6A. input Btu/hr
A.G.A. output Btu/tir
rating-gallons water per ftoura
60* rise 60* rise 100* rise
G-23 FG steam
60,000
48,000
96
71
58
G-24 G steam
90,000
72,000 144 107
86
G-25 G steam 120,000
96,000 192 143 115
G-26 G steam 150,000 120,000 240 179 144
G-27 G steam 180,000
144,000
288 215
173
G-28 G steam 210,000 168,000 336 251 201
G-29 G steam 240,000
192,000
384 287
230
G-210 G steam 270,000 216,000 432 323 259
G-211 G steam 300,000 240,000 480 359 288
Substitute letter " F" for flush or "D" for deluxe jacket.
G-44 steam G-45 steam G-46 steam G-47 steam G-48 steam G-49 steam G-410 steam G-411 steam
180,000
144,000
290 215
175
240,000 192,000 385 290 230
300,000 240,000 480 360 290
360,000 288,000 575 430 345
420,000 336,000 670 505 405
480,000 384,000 770 575 460
540,000 432,000 865 650 520
600,000 480,000 960 710 575
G-66 steam G-67 steam G-68 steam G-69 steam G-610 steam G-611 steam G-613 steam G-615 steam G-617 steam G-619 steam G-621 steam G-622 steam G-625 steam G-628 steam G-631 steam G-633 steam G-637 steam G-641 steam
650,000 780,000 910,000 1,040,000 1,170,000 1,300,000 1,560,000 1,820,000 2,080,000 2,340,000 2,600,000 2,730,000 3,120,000 3,510,000 3,900,000 4,160,000 4,680.000 5,200,000
520,000 624,000 728,000 832,000 936,000 1,040,000 1,248,000 1,456,000 1,664,000 1,872,000 2,080,000 2,184,000 2,496,000 2,808,000 3,120,000 3,328,000 3,744,000 4,160,000
1040 1250 1460 1660 1870 2080 2500 2910 3330 3750 4170 4370 4980 5600 6250 6660 7480 8330
780 935 1090 1250 1410 1560 1870 2190 2500 2810 3120 3280 3740 4210 4680 4990 5610 6250
624 748 874 1000 1120 1250 1490 1750 1990 2250 2500 2620 2900 3360 3740 4000 4490 5000
For altitudes above 2000 ft., ratings should be reduced at the rate of 4% for each 1000 ft. above sea level.
.';Am e rican -<$t an d ard
12399
conversion burners
lodel IN Inshot gas conversion burner
-- ^7tliJRSlH
factory assembled (controls regularly furnisH
are for 115 volt, 60 cycle current)
4*SJ - -x:''. t.V.^. tg.....r...c....w.... -
ratings
draft hood, Hm pipt dimensions
A.GJL ratings- Btu input per heur
model
Nat and Mxd gee
Mfggee
min max
min
max
IN-150 IN-245 IN-275
80,000 95.000 95.000
150.000
80,000
150,000
245.000 not available not available
275.000 not available not available
Gas valve sizes: Vi? inch for IN-150 nat and mxd gases; Vt inch for all other models.
input range Btu par hour
draft heed and flue pipe sixes
inches
minimum to 120,000
5
120,000--180,000
6
180.000--250,000
7
250.000--320,000
8
325,000 maximum
9
If flue pipe exceeds 10 ft in length, or contains more than Z elbows, use next sixe larger draft hood and flue pipe.
inputs for Arcoleader and Arcoliner boilers
in-isob
IN-2450
1N-27S0
IN-27SB
bailer medal
nat mxd mfd
nat mxd ONLY nat mxd ONLY maximum gas inputs
net mxd ONLY a
3 section
4 saction
S section
t section
Arcoleader Arcoliner
115,000 120,000
160,000 170,000
210,000 200,000
260,000 A'
B burner size type of gas a not recommended for gas firing. Lower inputs may be used Jo_conform with the load installed on the boiler, in these cases, a smaller size burner may be selected to meet this requirement.
dimensions (inches)
Arcoleadcr packaged oil-fired boiler is easily converted to gas-fired heating with the compact Inshot burner.
gas inlet
front view
side view
flame spreader
standard equipment
American-Standard CA-412 thermdstat. Runner pilot ignition. Manual shut-off valve. Control housing. Stainless steel flame spreader. Pilot throttling valve. Pilot filter--with mfd gas burners only. Two mam burner orifices: one drilled for minimum input, factory installed; the second, also drilled for minimum in put, can be drilled to other Inputs as required.
modal. IN-150 and IN-245
American-Standard V-600 series combination gas valve, pressure regulator and safety pilot switch, transformer, manual opener.
modal IN-275
General Controls KX3H quiet solenoid gas valve, plug-in safety pilot switch, transformer, manual opener. Gas pres sure regulator.
optional equipment
Self-energizing controls: General Controls T80-A thermo stat, B-60 gas valve and PG9 pilot generator -- if desired, specify on order:
burner model
IN-150 IN-150 IN-245 IN-275
type of gas
Nat. and Mxd. Mfd.
Nat. and Mxd. Nat. and Mxd.
Select from list below special limit control which must be used with self-energizing controls.
100% safety shut-off, all models, specify on order. Pilot filter--regularly furnished only for Mfd. gas. If desired for Nat, and Mxd. gas, specify on order.
instructions for ordering Orders must specify: 1. Type of gas. 2. Btu (heat value of gas) and specific gravity. 3. Pressure available at outlet of gas meter. 4. Optional controls, if Oesired.
Note. For orifice drill sizes -- Inshot mam burr
optional controls for self-energizing (millivolt) application:
number
description
L-52A10A1A 700-D S44A332
S44A502A104
General Controls immersion limit control General Controls pressure boiler limit control, scale 0-10 lbs. General Controls warm air limit control
General Controls fan and limit control
page 20
12400
<
conversion burners
oil
Arcoflame
arcoflame burner models used with American-Standard oil heating units
burner number
possible oil firing capacity gallons par hour
minimum
maximum
air tuba
affective length
diameter
mounting
used an American-Standard beating unit
PH2-5
0.65
3.00
5'
4'
hanger
Arcoleader boiler--all sizes A-504
PH2-6
0.65
3.00
6%'
Arcoliner boiler--all sizes
4*
hanger
Severn boiler--all sizes
Oakmont boiler--all sizes
LF-A
3.00
7.00
6%"
6'
flange
A-505--A509
LF-E
3.00
7.00
6%*
6'
flange
Exbrook boiler--all sizes
ES-2-6
0.70
1.50
6%'
Arcoliner boiler--3 & 4 section
4'
hanger
Severn boiler--#17
Oakmont boiler--#84
Up to 1.000 feet altitude. Reduce by 4% for each 1.000 feet altitude above sea level. Possible maximum firing capacity not always used--see catalog or nameplate firing capacity for listed heating unit.
arcoflame burner models for boiler conversion
burner number
possible oil firing capacity gallons par hour
minimum
maximum a
air tuba
effective length inches
diameter inches
mounting
PH 2- 8 PH 2-15 PH 2-23
0.65 0.65 0.65
3.00 3.00 3.00
IVz 4 pedestal
14Vz 22Vz
4 4
or flange
L-I
3.00
7.00
11 Vs 6 pedestal
L-3
3.00
7.00
21
6 pedestal
ES-2- 8 ES-2-15 ES-2-23
0.70 0.70 0.70
1.50 1.50 1.50
7Vz 4 pedestal
14V4
4
or
22Vz
4
flange
Up to 1,000 feet altitude. Reduce by 4% for each 1.000 feet altitude above sea level. Measured from air tube mounting bolts to end of air tube.
serves boilers wi th maximum installed radiation a nonmal piping insulated
Btu/hr
square feet
water or steam
water (150 Btu) steam (MC Btu)
204,800 204,800 ' 204,800 477,850 477,850 102,400 102,400 102,400
1365.3 1365.3 1365.3 3285.7 3185.7 682.7 682.7 682.7
853.0 853.0 853.0 1991.0 1991.0 426.5 426.5 426.5
general information
Model PH2-5 (or Arcoleader and A-504, and Models PH2-6 and ES-2-6 for Arcoliner, Oakmont and Severn oil heating units are furnished with hanger mounting; mounting acces sories packed separately and are different for each oil heating unit. Specify on order which is desired.
Models PH2 and ES-2 burners with 8", 15" and 23" air tube lengths are available with pedestal or flange mounting bracket, packed separately. Specify on order if pedestal or flange mounting bracket is desired.
Factory installed solenoid cut-off valve is available for model PH2 burners. If desired, specify with suffix ``M", for example, PH2-6-M.
When ordering Arcoflame oil burners be sure to specify nozzle size desired. Nozzles and strainers are as follows;
For model PH2--Hollow cone, 60" or 70", 0.65, 0.75, 0.85, 0.90, 1.00. 1.10 and 1.25 gph.
Solid cone. 60" or 70\ 1.35, 1.50, 1.65. 1.75, 2.00, 2.25, 2.50. 2.75 and 3.00 gph.
For model ES-2: Hollow cone. 80 = . 0.75, 0.85, 1.00, 1.10, 1.25. 1.35 and 1.50 gph.
For models L. LF Hollow cone. 80 = . 3.00, 3.50. 4.00 and 4 50 gpn: 60 :, 5 00. 5.50. 6.00, 6.50 and 7.00 gpn.
Two-stage fuel unit is available with models PH2 and ES-2
Arcoflame oil burners, and will be furnished when speci fied on order.
Two-stage fuel unit is regular equipment with model L Arcoflame oil burners.
Vapor installations: Substitute 450-BC-l vapor limit control for 450-BA-l pressure limit control with No. 11 or No. 12 control sets.
Electric clock thermostat: Substitute T 852 for CA-412 Thermostat; specify on order control set number with suffix "B".
Method of fuel atomization--Mechanical pressure--100 psi.
Air supply--Low pressure with squirrel cage fan.
Ignition--Intermittent spark, all models. Constant ignition can be used if desired.
Motor--PH2 and ES-2 Burners: V hp--1750 rpm. L, LF-A and LF-E Burners.- V, hp--1750 rpm.
Approval--All Arcoflame Oil Burners (60 cycle, 115V) are listed by The Underwriters Laboratories, Inc., for No. 1 and No. 2 commercial fuel oil, comply with Commercial Standard CS-75, and are approved by the New York City Board of Standards and Appeals, by the State Fire Marshal of the Commonwealth of Massachusetts and by the Depart ment of State Police, State of Connecticut.
.^American-/Standard
12401
46
conversion burners
oil
Arcoflame
Arcoflame Oil Burners are sold only in combination with American-Standard CA-701 Stack Control and with one of the standard Arcoflame Control sets listed below. The room thermostat and other controls are manufactured by and for American-Standard and enjoy a high reputation for skillful design and precision manufacture that assures accurate performance.
control sets
Arcoflame standard control sot number
stack number
contents of Acroflame standard control sots
instnimont
No. 11 steam
For boiler without year-round domestic hot water.
CA-412 450-BA-l
thermostat pressure limit control
No. 12 steam
For boiler with year-round domestic hot water; built-in heater.
CA-412 450-BA-l CA-666
thermostat pressure limit control immersion operating control
No. 13 water
For boiler without year-round domestic hot water; immersion control tor new boiler.
CA-412 CA-655
thermostat immersion limit control
No. 23 water
For boiler without year-round domestic hot water; constant circulator operation.
CA-412 CA-655 CA-666-R
thermostat immersion limit control rev. acting low limit control
No. 14 water
For boiler without year-round domestic hot water; clamp-on control for existing boiler.
CA-412 251-MJ
thermostat clamp-on limit control
No. 15 water
For boiler with year-round domestic hot water; storage4ank heater; using circulator.
CA-412 CA-655 CA-666 CA-295
thermostat immersion limit control immersion operating control relay transformer
No. 16 water
For boiler with year-round domestic hot water; built-in tankless heater; using circulator.
CA-412 CA-655 CA-666-DT CA-295
thermostat immersion limit control immersion control double throw switch relay transformer
No. 26 water
For boiler with year-round domestic hot water; built-in tankless heater; using circulator.
CA-412 CA-655 CA-666-AO
CA-295
thermostat immersion limit control
immersion control double throw switch with adjustable differential
relay transformer
No. 16-Z water
2-Zone control, for boiler with year-round domestic hot water; built-in tankless heater; using circulators. NOTE; For each additional zone, add 1 No. CA-412 thermostat and 1 No. CA-295 relay transformer.
No. 19 warm air For gravity furnace.
2 CA-412 CA-655 CA-666 CA-666-R 2 CA-295
CA-412 CA-805
thermostats immersion limit control immersion operating control rev. acting low limit control relay transformers
thermostat limit control
No. 20 warm air For forced warm atr unit.
CA-412 CA-815-S
thermostat fan and limit control
When ordering Nozzles be sure to specify solid or hollow cone nozzle and size desired. Nozzles are shown on pages 45 and 50.
selecting the proper size nozzle for the burner
Boiler efficiencies range from 50% to 80%. The latter is used with some boilers designed for oil burning.
CONVERSION BOILERS are coal burning boilers converted to oil.
For rapid circulation:
OIL BURNING boilers
CONVERSION boilers
for steam (240 Btu)
nozzle size = installed radiation
(g p.h.)
300
installed radiation 250
for water (150 Btu)
nozzle size = installed radiation
(g p.h )
500
installed radiation 400
The Net installed radiation, sauare feet, plus the equivalent load of the domestic hot water or otner appliances connected to the Odder, equals the INSTALLED RADIATION.
12402
dimensions and data--{inches)
burners | 011
Arcoflame
model PH2
model L (pedestal mounted)
model
PH2-5
A 14% BS diameter air tube-4'
PH2-f
15Vi 6%
PH2-2
16% 8
PH2-15
23% IS
PH*.
31% 23
models LF-A, LF-E (flange mounted)
model ES-2
12403
OIL CONNECTION
combustion parts
AOJUSTMINT HOCK
ADJUSTMENT HOCK SCtlW
combination number i
2
3 4
firing rata tph
.65 to 1.10 .90 to 1.25
1.30 to 1.75 1.80 to 2.302.35 to 3.00
static disc marking
.65 to 1.10 .90 to 1.75
.90 to 1.75 1.80 to 3.00 1.80 to 3.00
turbulator marking .65 to 1.10 .90 to 1.75
.90 to 1.75 1.80 to 2.30 2.35 to 3.00
nszzla spray angla 1 typa 60"-70" Hollow 60"-70" Hollow
60"-70" Solid 60-70" Solid 60'-70 Solid
model L-- air diverter and electrode setting
MIN. CLEARANCE FROM ELECTRODES TO METAL PARTS
TOP VIEW ELECTRODE HOLDER
SET SCREW
size of nozzle--hollow cone--gallons per hour . . . spray angle degrees............................................................... dimension "D" inches..........................................................
"D" is distance from Oiverter to Nozzle Tip
3.00 0
CO
O
00
o
00
00
3.50 4.00
0 v
4.50 V*
5.00 60" Vi
5.50 6.00
60" 60"
v V*
6.50 60" Vz
7.00 60" Vz
model ES-2 fuse on/y with 800 hollow <one nosxlo)
P L *M STa 01L lZ E ft
12404
(
*V>. .:5'',r;^3
V-
combustion chambers
heat Lib-O-Rator moldked,rcfra''or'',,
combustion chambers
heat Lib-O-Rator
Heat Lib-O-Rator Molded Refractory Combustion Chambers are de signed for and can be used with Models PH2, LF-A, LF-E, and ES-2 Oil Burners and fit the following Boiler-Burner Units:
boiler
Arcoliner Oakmont Severn A-5
Exbrook
153-T 154-T 155-T 156-T
84 85 86 87 88 89
17 21 25 29 33 37
A-504 A-505 A-506 A-507 A-508 A-509 A-510 A-511
207 208 209 2010 2011 2012 2013
boat Lib-O-Rator
number 4 5 6
00 1 2 3
1 2 3 14-A 15-A 16-A
17-A
7
8
maximum firing rate
tPh 1.35 1.65 2.00 1.50 1.75 2.25 3.00
1.75 2.25 3.00 2.55 3.30 5.55
7.65
4.50
6.50
dimensions
size no: 00, I, 2, 3,
i-s, 2-s, 3-s, V i a
plan view front viaw size no: 4, S a $
A-5 boiler
plan view
sectional view 4 section boiler
sectional view 5 thru 11 section boiler
chamber no.
14-A 15-A L6-A 16-A 16-A 17-A 17-A 17-A
no. of sections
4 5 6 7 8 9 10 11
A
15Vz 15Vi 21V2 21Vz 2IV2 27V2 27Vz 27V2
12405
AMERiCAJj-^tandard
combustion chambers
Refractory
made from
combustion chambers firebrick
< jMa ? : * V
DRAFT
side view (cutaway) for nozzles below IV* gallons
Fig. 1
side view (cutaway) for nozzles of
IVi gallons and over
Fig. 2
DRAFT
dimensions
burner model
nozzle size epn
PH2 L, LF ES-2
0.65* 0.75*
1.00*
1.25* 1.35* 1.50 1.65 1.75 2.00 2.25 2.50 3.00
3.00 3.50 4.00 4.50 5.00 5.50 6.00 6.50 7.00
0.75o
1.00*
1.35* 1.50
spray ancle and typo cone
(H=hollow; S=olid)
combuition clumber
>ize-inches L w Ha
floor ol C.C. min. watt to C.L. of thickness nozzle "C" inches
60'Hor70*H 7 7 14
8 8 14
,"r
10 10 14 11 11 14
60* S or 70 S
12 13
11 11
14 14
" 14 12 14
15 12 14
It 15 12 14
" 16 13 14
r 17 13 14
" 18 14 14
4
4V4 5 5 5 5
5V4
5Vi
5V4 6 6
6-6V4
2V6 2Vz
2V4 2Vz 2Vz
2Vt 2Vz 2Vz 2W 2Vz 2Vz 2Vz
80 "H ** "
60 H
"
16 18 18 16 18 18 18 18 18 20 20 19 20 22 20 22 22 20 22 22 20 24 22 20 24 24 22
8
8 8 9 10
10 10
11 11
4 4
4V5 4Vz 4V4
4Vz 4Vi 4Vi 4V2
80H
n
II
11 11 14 12 12 14 13 13 14 14 14 14
5% 6 6Vz 7
2Vz
2Vi 2Vt 2Vi
The height of combustion chamber "H" is a minimum. The fire" brick should always be carrrad high enough to cover 2 inches of water backed surfaces.
a For nozzle sizes below 1.50 gallons per hour, build chamber rec* tangular; see Fig. 1. For nozzle sizes of 1.50 gallons per hour or larger, build chamber as shown in Fig. 2.
NOTE: Use Nozzles with Spray Angles specified in table above. Do not attempt to bum more oil with these burners than specified on page 45. If width of the larger sized chambers shown in the table cannot be obtained, increase length of chamber by amount of width re* duced. Never reduce width by more than 3".
A-5 boiler
A-7 boiler
' i TO 3-^
tl 3Vr ill-
no. of sections
A
B
5 16 18 6 18 18 7 20 22 8 22 22 9 24 22 10 24 22Vz 11 26 22Vz
sectional view 4 section boiler
sectional view 5 thru 11 section boiler
front view cutaway A-70B-SO thru A-712-SO
boiler no.
chamber length (inside)
A-705 A-706 A-707 A-708 A-709 A-710 A-711 A-712
27Vi 32Yi 37Vi 38 41 44 47 50
12406