CHAPTER 39
1959 Guide
OtactelMC)
Table 3____Number of Defrosts per Year* (100 Percent Running Time) --10 to 5 6-9 f-n 12-14 15-X7 19-20 21-23 24-26 27-29 30-32 33-35 36-39 39-41
Normally dry Normally damp
475 450 400 375 350 300 250 200 175 ISO 100 75 0 800 750 700 625 575 500 425 350 300 225 175 125 100
* The figaiee s>vea not be multiplied by the runnin-time retie lor the period considered.
Extra power consumption allowance must be made where periodic defrosting of an air-source evaporator is required, and where supplemental heating is employed.
The number of defrosting operations required per month or a complete heating season is difficult to evaluate ac curately. It will depend on the detailed design and control of the beat pump, the climate, and the hours of operation. Table 3 gives the range in annual number of defrosts that may be expected on typical small unitary beat pumps.
To obtain a total yearly operating cost, the energy con sumption for cooling must be added to that required for heating. Suggested procedures for calculating cooling en ergy consumption are given in Chapter 46 and 54.
Annual Operating Cost
A tabulation such as is shown by Table 4 may be used for estimating the operating cost for commercial and in dustrial installations. It is necessary to know the monthly kilowatt electric demands and the corresponding kilowatthour consumption for the base electric lead, as well as for the heat pump or any other electric equipment, in order to apply the proper electric tariff. The base loads, shown as Columns 1, 2 and 3 of Table 4, may include lighting, ele vators, office machinery, exhaust and supply fans, circulating pumps, and similar items which are normally essential in a structure and are not affected by a particular air-condition ing design. The heat-pump kilowatt demand, during the month, which is required to satisfy the net day and night heat loss or heat gain (whichever is the greater), can be obtained from manufacturers' data. These resulting kilo watt demands are multiplied by a coincident factor to ob tain the coincident demands, listed in Columns 4 and 7. These coincident demands can be added to the base load demands to obtain the total electric load m Column 10. The coincident factors can best be obtained from published data on amiUr installations. The procedure for finding the heating and cooling kilowatt hours, Columns 5, 6 and 8, has been previously described.
For residential installations, a detailed monthly estimate
generally is not justified unless a monthly demand type of rate is in effect.
In making a power consumption estimate for unitary heat pumps, a detailed breakdown into periods less than a com plete season, or the breaking down into small temperature spans, is not ordinarily justified. Manufacturers of this type of equipment provide estimating procedures which are sim pler to use, yet are of sufficient accuracy for the purpose in tended. These methods usually consist' of an' empirical equation, tabular data, or plotted curves which combine the influences of the me and thermal properties of the struc ture, the beating design temperature, the characteristics of the heat pump, and supplemental heat usage.
HEAT-PUMP COMPONENTS
For the most part, the components used in heat pumps and the practices followed bear a direct relation to the low temperature refrigeration art. This section will outline the major components used and point out characteristics or special considerations which apply to the heat-pump field.
Compressors
Reciprocating compressors are used more than any other type on systems in the general range of Vt to 100 tons, and frequently even larger. A brief description of this type of compressor is given in Chapter 38. For the most economical application, it is general practice to select the reciprocating compressor to provide the desired cooling capacity. The cooling capacity is the evaporator capacity and represents the ability of the compressor to pump refrigerant vapor between the existing temperature limits. When heating, the capacity of a particular compressor is the sum of the evapo rator capacity (i.e., heat-source coil capacity) plus the heat equivalent of the compressor work. - Figs. 13, 14 and 15 in Chapter 38 shows the capacity and power characteristics of typical reciprocating compressors. A compressor normally employed for comfort cooling use will have a clearance volume (ratio of gas volume remaining in cylinder after compression stroke to total swept-cylinder
Table 4 .... Suggested Procedure for Computing the Operating Cost of Commercial and Industrial Heat-Pump System
Period
Bert* load Lighting and Miscelloaeout
Cost Bose Load
Heat Pump
Coinci
dent demand
Heat
Cool
Supplemental tiesdanee Meeting
lIf Used)
Total Hooting and Coating
Total flmJrfc load
Total Cost
Kw KwH 0) (2)
KwH 13)
Kw KwH KwH Kw KwH U) (5) (6) 17) 18)
KwH 19)
Kw KwH (10) (ID
(12)
June July
May
Fil in one tine for e
bh throu ;b May
LI
The Heat Pump
573
volume) of about 5 percent. The capacity drop off at low evaporator temperatures corresponding to' low heat-source temperatures is also evident. The drop off in power at low evaporator and condensing 'temperatures is also evident.
If the-compressor has low clearance volume, say 2Yt per cent, than it is more suitable for low-temperature operation, and will provide, for example, about 15 percent greater re frigerating capacity at an evaporator temperature of OF and a condenser temperature of 110 F. However, this com
pressor has somewhat more power demand under maximum cooling load conditions than does one of medium clearance.
-It is obvious that more total heat capacity can be obtained at low outdoor temperatures by deliberately oversizing the compresor. The compressor is oversized in order to obtain
more heating capacity so it is necessary to provide some type of capacity reduction to bring the cooling capacity into balance. This can be done by means of two-speed motor drives, cylinder cutouts, or other methods as described in Chapter 38. The disadvantage of this arrangement results from the fact that the greater number of operating hours that occur at the higher suction temperatures must then be served with the compressor in the unloaded condition which generally causes lower efficiency. Therefore, the annual- op erating cost will tend to rise. It is also true that the addi tional first cost of the oversized compressor must be economi cally justified by the gain in heating capacity. One method proposed for increasing the heating output at low tempera tures involves the use of staged compression in which one compressor may pump from --20 F suction temperature to 40F condensing temperature and a second compressor com press the vapor from 40 F to 120 F. In such an arrangement it is possible to interconnect any two compressors so that they are in parallel, both pumping from say 45 F to 120 F at the normal cooling rating point, while at some predeter mined outdoor temperature on heating they are reconnected so that they pump in staged relationship.
Fig. 8 shows the performance of such a pair of compressors for compressors of both medium and low clearance volume. It is apparent that at low suction temperatures the recon nection into a staged relationship does provide some added capacity. Also, it should be understood that the motor selec tion involved must be based upon the maximum loading con ditions for summer operation even though the low stage compressor has a greatly reduced power requirement under the heating condition.
11 1I LOW CLEARANCE, r^T ME HUM CLfAfiANCf
ALMLLa. (.OPERATION
1M -
S' RATING
r POINT= 1002
LOW CLEARANCE
STAGED OPERATICw
" --MEDIUM CLEARANCE 1
J CROSS-OVER POINT !
J'l Itii rrl1NOT
CLEARANCE STAGED COMPRESSORS
CAPACITIES FOR RESPECTIVE
HC VTING RANGcl 1 1 1 1 | . | (cooling* RANGcf
SUCTION TEMP.-F Fig. 6.... Comparison of Parallel and Staged Operation
The coefficient of performance will be approximately the same whether they are coupled in parallel or compoundstaged at any set of operating conditions depending some what on the motor characteristics when lightly loaded.
A rotary compressor has characteristics similar to a re ciprocating compressor except that it is by nature pos sessed of low clearance and high volumetric efficiency. From this standpoint it is well suited to heat-pump service, pro viding about 30 percent greater capacity at 0 F--110 F lift than a medium-clearance reciprocating compressor. How ever, this characteristic tends also to increase the power de mand at the maximum cooling load conditions. At this time, reciprocating compressors are most widely used for heat pumps, with rotary compressors restricted to the first stage of a staged-compression system and not used during the cooling cycle.
Heat Transfer Components
Refrigerant-to-air and refrigerant-to-water heat exchang
ers, as previously described in the section Heat Sources and Sinks, are similar to heat exchangers used in current airconditioning practice. A refrigerant subcooler coil may be employed either in conjunction with an indoor air coil, or, on systems with a ventilation air supply, to preheat ventila tion air. A substantial gain in capacity and coefficient of performance can result.
Refrigeration Components
Refrigerant piping, receivers, expansion devices and re frigeration accessories in heat pumps are usually the same as those used in other types of refrigeration and air-conditioning systems (see Chapter 38).
A reversing valve is used to change the system from the cool ing to the heat operation. This change-over requires the use of a valve, or valves, in the refrigerant circuit,* except where the change is accomplished in fluid circuits external to the re frigerant circuit (see Table 1). Reversing valves are usually pilot-operated by means of solenoid valves which admit bead and suction pressures to move the operating elements.
Expansion devices for controlling the refrigerant flow are normally thermostatic expansion valves as described in Chap ter 38. Special requirements may sometimes be presented. If the circuiting is so arranged that the refrigerant line upon' which the control bulb is placed can become the compressor discharge line, the resulting pressure developed in the power element of the valve may Be excessive, requiring the use of a special control charge or pressure-limiting element. When a thermostatic expansion valve is applied to an outdoor air coil, a special cross-charge is desirable to limit the superheat at low temperatures, and thereby obtain a better utilization of the coil.
When mi expansion valve is attached to a coil that is
operated as a condenser, a bypass with a check valve is normally provided as indicated in Table i.
On small factory-built systems, capillary tubes arc nor mally used as expansion devices. While a single capillary tube on both heating and cooling is sometimes employed, better efficiency and performance can be obtained by using a more restrictive capillary tube for heating than for cooling. This may be accomplished by using two capillary tubes in either a series or parallel arrangement with a check valve to bypass one for cooling or to block one for heating, respectively.
On an air-source heat pump that must operate over a wide range of evaporating temperatures, a capillary tube will tend to pass refrigerant at an excessive rate at low back pressures, causing liquid floodback to the compressor. In some cases suction line accumulators or charge-control devices are employed to minimize this effect.