A-5 oil-fired boilers ater or steam
PLAINTIFF'S EXHIBIT
ft SX-^73
J'-V
00214
: \j r - c i e
rmsr
steam boiler illustrated
The A-5 oil-fired unit is designed for installation in
The A-5 boiler is unmatched in its ability to meet a wide
large homes and small to medium-size apartments and
variety of domestic hot water needs. A unique tankless
commercial buildings. This big performance boiler has 1 heater arrangement lets you match expanding domestic
been engineered specifically for oil operation and is < hot water requirements (from 4 to 16 gpm) by the inser
available as a boiler-burner unit or boiler only in a full ! tion of extra tankless water heaters into A-5 center sec
range of eight sizes for hot water or steam application, ! tions. No need to install a bigger boiler or separate water
with l = B = R approved ratings in the 195,800-622,700 \ heater to handle expanding hot water requirements. A
Btu hr range. The A-5 is built, for long-lasting efficiency I special copper manifold assembly, pre-fabricated to cut
and easy, low-cost installation. Vertical flue design reduces section weight, speeds heat circulation; unique tankless hot water heater adapts to meet varying do-
! , j
installation time and cost, connects multiple heaters in parallel. Special center sections, with heater opening,
mestic requirements; rugged cast iron sections assure j are supplied at no extra cost on all A-5 boilers specified
long, dependable service; wet base construction elimi
for tankless use. This special A-5 tankless heater ar
nates need for special base, keeps floor cool, pre-cast j rangement also permits the use of split systems to
combustion chamber saves on installation time; and I serve different domestic hot water needs. For versatility
American-Standard precision burners are tested for peak I and flexibility in meeting domestic hot water needs, the
oil heating performance.
i A-5 is the answer.
00215
oil-fired boilers
1- -matches jacket and has re movable front panel for ready access to burner and controls; arch-type openings to provide ample air for com bustion and circulation.
2- --all controls are mounted on front of boiler for easy maintenance and adjustment.
3- -permits convenient flame viewing; simplifies burner and control adjustment while boiler is firing. A Vs-inch pipe tap is provided for draft test purposes.
4- * -is available in five models for flange mount ing on boilers. Burners are laboratory tested for clean, efficient firing in all A-5 boiler-burner units.
5- -built into the front of the boiler; provides for easy accurate adjustment of secondary air.
6- -4-inch supply (top) and 2Vi-inch return (bottom) located in both front and back sections, elimi nate need for header on largest steam assembly.
7- -aluminized steel construction permits smaller flue pipe sizes; makes A-5 readily adaptable for gas firing.
8-- ater neater-internal tankless type with finned copper tubing. Unique arrangement permits flexibility in meeting domestic hot water requirements ranging from 4 to 16 gpm.
9--'eater namfola -- connects multiple water heater in parallel and is pre-assembled for quick installation.
10-- aicr cect.cns-are ruggedly constructed of cast iron and feature vertical flue design with large 7-inch top nipple port. Off-center location of nipple port speeds up circulation; projecting studs and horizontal bars extract maximum heat from combustion gases. Sections are easily cleaned from left side and are tested at 2V2 times operat ing pressure.
11-- ':_..:;;:n-heavy glass fiber insulation prevents wasteful heat loss, keeps jacket cool.
12--.emeus;.on cr.cmbar -- high-temperature, pre-cast combustion chamber--provided for all assemblies-heats quickly and evenly.
13-- ecxei-smartly-styled of sturdy steel in sparkling gray finish with modern radius corners.
14-- et esse construction--provides extra heat-absorbing bottom surface and increased water content. Waterways completely surround combustion area, extend beneath boiler, keep floor cool.
, America;;yytandurd
00216
A-5 ratings
boiler numbers steam
water
gross l=B=R output water 8. steam (Btu/hr)
net 1 = B = R ratings!
water & steam steam
(Btu/hr)
(sq. ft.)
l = B=R burner capacity (gph)e
chimney
size (inches)
height (feet)
water content (gallons)
steam boiler
water boiler
A-504-SB(T) A-505-SBIT)
A-506-SB(T) A-507-SB(T) A-508-SB(T) A-509-SB(T) A-510-SB(T) A-511-S B(T)
A-504-W8(T) A-505-WBIT)
A-506-WB(T) A-507-WBIT) A-508-WBIT) A-509-WBIT) A-51Q-WBIT) A-511-W8IT)
261,000 346,000 426,000 508.000 588,000 668,000 748.000 830,000
195,800 259,600 319,600 381,100 441,100 501,100 561,100 622,700
816 1082 1332 1588 1838 2088 2338 2594
2.55 3.30 4.00 4.75 5.55 6.30 7.00 7.65
8x 12 8x 12 12 x 12 12 x 12 12 x 16 12 x 16 12 x 16 16 x 16
15 20 20 20 25 25 25 30
45.6 52.4 59.3 66.1 72.9 79.8 86.6 93.4
57.7 66.7 75.5 84.5 93.4 102.3 111.3 120.2
A-504-SIT) A-505-SIT) A-506-SIT) A-507-SIT) A-508-SIT) A-509-SIT) A-510-SIT) A-511 -S(T)
A-504-WIT) A-505-W(T) A-506-W(T) A-507-W(T) A-508-WIT) A-509-WIT) A-510-W(T) A-51 l-W(T)
261,000 346,000 426,000 508,000 588.000 668.000 748,000 830,000
195,800 259,600 319,600 381,100 441,100 501,100 561,100 622,700
816 1082 1332 1588 1838 2088 2338 2594
2.55 3.30 4.00 4.75 5.55 6.30 7.00 7.65
8 x 12 8 x 12 12 x 12 12 x 12 12 x 16 12 x 16 12 x 16 16 x 16
15 20 20 20 25 25 25 30
45.6 52.4 59.3 66.1 72.9 79.8 86.6 93.4
57.7 66.7 75.5 84.5 93.4 102.3 111.3 120.2
Net i = B = R ratings shown induce allowance for normal piping and pickup load. American-Standard should be consulted before selecting a boiler for installations having unusual piping and pickup requirements.
For complete information on burners and nozzles furnished with A-5 boiler-burner units, see chart on page 6. Note: Suffix "B" denotes boiler-burner unit; "S" denotes steam: ``W" denotes hot water; "T" denotes unit with tankless heater section(s).
control sets for A-5 boiler-burner units
control set
control function
description
standard no. 11 steam no. 13 water
optional no. 12 steam no. 34 water no. 36 water no. 36-Z water
boiler without domestic hot water boiler without domestic hot water, immersion control
thermostat, limit control thermostat, limit control
boiler with year 'round domestic hot water, built-in tankless heater
boiler without domestic hot water, constant circulator operation
boiler with year 'round domestic hot water, built-in tankless heater, using circulator one no. 36-2 control set is required for each zone in addition to the first zone which is controlled by no. 36 control set.
thermostat, limit control immersion operating control thermostat, circulator-limit immersion control thermostat, immersion control relay combination thermostat, zone control relay
A-5 oil-fired boilers are designed and built to comply with the American Society of Mechan ical Engineers' Code and bear their approval symbol. Ratings have been approved by the Institute of Boiler and Radiator Manufacturers.
4 00217
1
boiler
number
number of sections
A-504 A-505 A-506 A-507 A-508 A-509 A-510 A-511
4 5 6 7
8 9 10 11
number and size of tappings
flow return (in.) (in.)
(2)-4 (2)-4 (21-4 (2)-4 (2)-4 (2)-4 <2)-4 (2)-4
(4)-2V4 (4)-2V'2 (4)-2Va (4)-2Va (4)-2Vs
(4)-2Va (4)-2Va (4)-2Vz
A
I6V2 21 25V2 30 341/2 39 43V2 48
B
13Vi 16% 16% 16% 16% 16% 16% 16%
dimensions (inches)
CD
E
9 UV2
9V2
9 IIV2
9%
10 12
10
10 12
10
10 12
10
12 13
11
12 13
11
12 13
11
F
15V2 20 24V2 29 33V2 38 42V2 47
6 flush jacket
22% 27% 31% 36% 40% 45% 49% 54%
H jacket extension
47% 52% 56% 61% 65% 70% 74% 79%
assemblage of sections
boiler number
A-504 A-505 A-506 A-507 A-508 A-509 A-510 A-511
arrangement of sections from front of boiler (with tankless heater opening)
1 2 3 4 5 6 7 8 9 10 11
FX CT CT BX FX CT CT CT BX FX CT CT CT C BX FX CT CT CT C C BX -- -- -- --
FX CT CT CT C c C BX -- -- -- FX CT CT CT CT c C C BX -- -- FX CT CT CT CT c C c C BX -- FX CT CT CT CT c c c C C BX
arrangement of sections from front of boiler (less tankless heater opening)
1 2 3 4 5 6 7 8 9 10 11
FX C c BX FX C c C BX FX c c c C BX FX c c c c c BX -- -- -- -- FX c c c c c c BX -- -- -- FX c c c c c c c BX -- -- FX c c c c c c c c BX -- FX c c c c c c c C C BX
FX-front connecting section
CT-center section with tankless heater opening
C -center section without tankless heater opening
BX-back connecting section
control tappings
location
size
on boiler (inches)
steam
control used
F 2% low water cut-off
not used
G % pressure limit control
temperature limit control
H % operating control, tankless heater not used
J V2 pressure gauge
combination altitude gauge and thermometer
K % not used
operating control, tankless heater
N
L % not used
reverse acting control
2-inch blow-off in
back section. 2-lnch safety or relief valve on top of beck section.
Mm American'- Standard
00218
no. 530 tankless heater ratings
boiler number
number of heaters
ratings* (gpm)
A-504--A-511 A-504--A-511 A-505--A-511 A-508--A-511 A-510--A-511
1 2 3 4 5
4 7 10 13 16
Gallons of water per minute raised from 40"F to 140*F with 200"F boiler water temperature.
The above table shows the recommended number of heaters to be used with each boiler and the ratings attained if more than one heater is connected in parallel. Additional heaters can be added if the heaters are serving different systems and it is not likely that heaters will all be in use at the same time.
No. 530 tankless heater available for single purpose or multiple parallel hook-up. Copper manifolds (illustrated below) for two, three or four-heater parallel arrangement furnished with No. 530 heater if specified.
Provision for tankless heater is available when specified. If suffix letter "T" is added on order to unit or boiler numbers, the following number of center sections with heater openings will be furnished.
boiler or unit number
A-504-T
A-505-T A-506-T A-507-T A-508-T
A-509-T A-510-T A-511-T
number of openings
2 3
4
Note: Additional openings can be specified on order. Cover piate for water heater openings will be furnished if specified on order for "T" type units and boilers.
tankless heater piping
front of
boiler
. V4' copper %"xV5"*W"
elbow
copper tee
2-heater manifold piping
Note: Single arrangement or any com bination of the above manifold piping arrangements can be used. Water heat ers are assembled in boiler starting with the second section from front of boiler. Heeter cover plates are marked "steam" and "water." When installing in a steam boiler the word `'steam" should read at the top, when installing in a water boiler, the word "water" should read at the top.
6
3-beater manifold piping
00219
minimum piping recommendations
oil-fired boilers
boiler number
A-504 A-505 A-506 A-507 A-508 A-509 A-510 A-511
gravity
supply (in.)
return (in.)
ZV2 2% (21-2 (2)-2 (21-2V2 (2)-2Va (2)-2Vz (2)-2Vz
2Vz 2V2 (2)-2 (2)-2 (2)-2% (2)-2% (2)-2% (2)-2%
forced
supply return (in.) (in.)
IV2 IV2 22 22 22 2V2 2V2 2Vi 2V2 2V2 2% 2% 2%
boiler number
A-504 A-505
A-506 A-507 A-508 A-509 A-510 A-511
riser (in.)
2V2 3 3 4 4 4 4 4
combustion chamber dimensions
Heat Lib-O-Rator molded refractory combustion chambers
A-504"
A-505 through A-511
return (in.)
IV. IV. iv 1% 1% 1V2 1% 1V4
equalizer (in.)
iya iy2 iya 2 2 2 2 2
top view
m
Chamber number 14-A
Heat Lib-O-Rator refractory combustion
chambers are stand* ard equipment on A-5 boiler-burner units; optional with
boiler only.
boiler number
A-505
A-506 A-507 A*508 a.sna
A-510 A-511
sectional view
Heat Lib-O-Rator
chamber number
15-A 15-AA 16-A 16-A 17-A 17-A 17-A
A On.)
15% 20
21% 21% 27% 27% 27%
ERICAAvfrMi-dard
00220
;
oil-fired boilers
oil burner specifications
boiler number
burner number
diameters--(inches)
choke
disc
A-504 A-505 A-506 A-507
A-508 A-509
A-510
OH-5 45WU-3506 45WU-3606 62A-7056-1
62A-7056-1 62A-7056-1
96-7506-1
3 Vs 3 Vs 5
5 5
5
2>/a 21/a 3
3 3A
3%
r=8=R burner capacity (gph)
number required
nozzle data
gph each
spray angle
ig i
2.55 one
2.50
60'
3.30
two
1.65 70"
4.00 4.75
two 2.00
two (U-2.25 (11-2.50
70"
80" 80"
COD
5.55 two
2.75
6.30 two (11-3.00 (11-3.25
80"
7.00
two
3.50
80"
type
solid solid solid hollow hollow hollow hollow hollow solid
oo
00 00
A-511
96-7506
5
3%
e stage fuel unit is regular equipmen on DH-5.
Two stage fuel unit is optional on DH-5. standard on all other burners on chart.
Electronic flame safeguard equipmeni-62A-7056-l-F burner with electronic flame safeguard control is available instead of 62A-7056-I burner for A-507, A-508 and A-509 boiler-burner units. 96*7506 burner is available for A-510 boiler-burner unit. For installation requiring Factory Mutual Approval and in states and
7.65
two (11-3.50
80"
solid
(11-4.00
solid
Remove disc when installed in boiler, if firing rate exceeds 5.75 GPH
municipalities with regulations more stringent than Underwriters' Laboratories, Inc., oil burners with special electronic flame safe guard controls are available for A-5 boiler-burner units as follows: 62A-7056-I-FFM burner for A-507, A-508, and A-509; 96-7507 burner for
A-510 and A-511.
APPROVAL: American-Standard oil burners (115 volt/60 cycle) are listed with Underwriters' laboratories, Inc. for No, 1 and No. 2 grades of fuel oil, distillate or catalytic cracked. They are approved by the New York City Board of Standards and Appeals, the State Fire Marshal of the Commonwealth of Massachusetts and the Dept, of State Police, State of Connecticut.
sample specification for A-5
Contractor shall furnish and install, as indicated on plans, ............ oil fired boiler(s) having a firing rate of............gph and an I = B = R gross output of............ Btuh. Boiler(s) shall be constructed of cast iron in accordance with A.S.M.E. requirements for low pressure heating boilers and bear the A.S.M.E. symbol. Each section shall be factory tested at 2Vz times maximum working pressure of 50 lbs. for water. Boiler(s) shall have l = B = R ratings. Boiler(s) shall be com posed of cast iron sections with vertical flues. Manufac turers will furnish boilers with an aluminized steel canopy.
Water or steam trim as required. Oil burners shall include controls as herein described. (Note: include description of controls as required and other burner features and com bustion chamber as desired.)
Boiler shall be equipped with tankless heater(s) having a rating of............ gpm. If more than one heater is required to meet requirements a copper manifold factory assembled will be installed by the contractor as recommended by the manufacturer to connect the heater in parallel arrangement.
rm No 4}:-2 (f ?v )
AMERICA M RAOIATOR & STANDARC JiTARY CORPORATION
I. WEST 40TH STREET -
.ORK 16, NfcV. YO<k
00221