Document MxJnpERNgvG1O48vMDa3yvja
78
CHAPTER 5
1962 Guide And Data Book
Table 12.... Selection of Bonnet Temperature, Register Temperature and Register Delivery (CFM)*"h (Far 8Uhgi Naiing a Heat lost Greater (fan 350,000 8TU/Hri Refilter Delivery Votes* fe CFM par 1000 BTU pe Hr.
10 20 30 A0 50 60 70 80 90 too no !20 ISO 140 ISO 160 170 180 190 200 2)0 220 230 240
140 14.0*
138* 136 134 132 130 128 127 126 125 124 123 121 120 119 118 117 116 115 114 113 112 111 110 109
14.4k
14.8
15.1
15.5
15.9
16.4
16.6
16.9
17.2
17.3
17.6
18-1
18.4
18.7
19.0
19;3
19.6
20.0
!ao.7 20.3
21.1
21.6
22.1
22.5
150 14S 146 143 141 139 137 135 133 131 129 128 127 126 124 123 122 120 119 118 117 116 115 114 113
12.6
12.8 13.1 13.5 13.9 14.2 14.6 14.9 15.3 15-7 16.2 16.4 16.6 16.9 17.3 17.6 17.9 18.4 18.7 19.0 19.3 19.6 20.0 20.3 20.7
. 160
15S 155 152 150 147 145 143 140 138 136 134 132 130 128 127 126 125 124 123 121 120 119 118 117
11.4
11.6 12.0 12.3 12.6 12.9 13.2 13.5 14.0 14.4 14.8 15.1 15.5 15.9 16.4 16.6 16.9 17.2 17.3 17.6 18.1 18.4 18.7 19.0 19.3
170 167 164 161 158 155 152 150 147 145 143 140 138 136 134 132 130 128 127 126 125 124 123 121 120
10.5
10-7 11.0 11.3 11.6 12.0 12.3 12.6 12.9 13.2 13.5 14.0 14.4 14.8 15.1 15.5 15.9 16.4 16.6 16.9 17.2 17.3 17.6 18.1 18.4
180
177 173 170 167 164 161 158 155 152 150 147 145 143 140 138 136 134 132 130 128 127 128
124
9.7 9;9 10.2 10.5 10.7 11.0 11.3 11.6 12.0 12.3 12.6 12.9 13.2 13.5 14.0 14.4 14.8 15.1 15.5 15.9 16.4 16.6 16.9 17.2 17.3
190 186 182 178 175 172 168 165 162 159 156 153 151 148 146 143 141 139 137 135 133 131 129 128 127
9.1 9.3 9.6 9.8 10.0 10.3 10.7 10.9 11.2 11.5 11.8 12.2 12.4 12.8 13.1 13.5 13.9 14.2 14.6 14.9 15.3 15.7 16.2 16.4 16.6
200
196 191 187 183 179 176 172 169 166 163 160 157 154 151 149 147 144 142 140 138 135 133 131 130
8.6 8.8 9.0 9.3 9.5 9.8 9.9 10.3 10-6 10.8 11-1 11.4 11.7 12.1 12.4 12.7 12.9 13.4 13.7 14.0 14.4 14.9 15.3 15.7 15.9
Register temperature, Fahrenheit. (Um upper value in each group.) k Register delivery volume in cubic feet per minute per 1000 Bta. (Use lower mine in each group.) * Bsgister delivtry wlimt is colamp 1 ere for aero length of duct.
(such aa Fig. 2 or Fig. 3, Chapter 12 of the 1961 Guide And Data Book), volume (cfm), and pres sure drop per 100 ft of duct. B. Return air branches.
a. Select a low value of actual duct loss obtained from step b under item A for the suction loss of return duct system.
b. Proceed' in siting return air branches by the name method described for the warm air branches.
C. Trunk ducts for warm air and return air sides ofsystem.
a. Add air volumes of branches to be handled by each trunk duct.
b. The friction loss per 100 ft of trunk duct is deter mined by taking the smaller of the two values for friction foes for the two ducts meeting at the junc tion.
c. 'Determine trunk duct sise by using an air friction chart, volume (cfm), and pressure drop per 100 ft of trank duct.
8- Selection of Blower.
A. Determine total cfm air delivery (the sum of all branch cfm values).
B. Determine static pressure requirement.
a. For furnace-blower combination units it is the sum of bonnet pressure and suction pressure.
b. For blowers separately selected from the furnace it is the sum oi bonnet pressure, suction pressure, filter loss, casing loss, losses through air washers, coils, and other devices.
9. Selection of Furnace.
A. Determine register delivery (the sum of room Bta losses).
B. Determine bonnet capacity. If the ductwork is all lo cated in spaces that have been included in the calcu lated heat loss, the required bonnet capacity can be considered equal to the required Btuh register deliv ery. If the furnace and ductwork are located in spaces not included in the heat loss, the required bonnet capacity of the furnace can be determined from:
Btuh = (cfm) X (temperature rise) X (1.08)
C. Determine allowance for pick-up load. For buildings which are heated intermittently, such aa churches and auditoriums, it is customary to add from 10 to 25 per cent extra furnace capacity for warming of the struc ture.
The design procedure outlined above results in a duct system which has been described as a trunk-and-branch
system. A trunk duct may or may not be reduced in size
as each branch duct leaves the trunk. If the trunk duct is not reduced as each branch duct leaves the trunk duct, the
trunk duct take-off fittings designated as EP1 to EP4 in
Fig. 7 are used. The air velocity within a uniformly sized
trunk duct decreases as air leaves it through the branch ducts. It is therefore desirable to reduce the trunk duct size
frequently enough that the air velocity within it does not
drop below about 350 fpm. The simplified procedures which have been outlined are
based upon an assumed air temperature of 70 F surrounding
Worm Air Heating Systems
79
Toble 13 .... Determination of Free Area and Total Pressure Loss of Register for 22 Deg Deflection of Air** * * Register Free Area in Square Inches (Upper vela* in eod groapl Pressure lou io ladies of Water (lower rates in each group)
ResdentioJ Use
Residential Use
Distance tree Register to Opposite WaO
'rrCte Reg. Size or fqpirataaf
Cfm
Reg. Size or Equivalent
Pressure loss
Cta 31-34 35-3? JiO-49 50-59 60-69 70-79 80-69 A' 1
Up to 59.
10 x 4 10 x 6
.01 .01
100-119
12 x 6 14x4
.02 .02
700-739 .
243 0.02
186 0.03
127 0.06
85 0.11
60-69
10x6 12 x 4
.01 .02
120-129
12 x 6 24 x 6
.02 .02
740-779
271 208 141
94
0.02 0.03 0.05 0.10
70-99 *
10x8 12x6
.02 .02
130-169
14x6
.02 780-819
230 157
105
0.02 0.05 0.09
170-189
14 x 8
.02 820-859
Distance From Register to Opposite Wa0
254 173 115 0.02 0.04 0.08
Cfm 190-209
Up to 18
19-21
2224
2527
2B-3Gj 31-34 35-39 40-49 50-59
860-899
A
68 49 38 29 24 19 0.02 0.03 0.05 0.08 0.11 0.16
900-930
278 190 126 0.02 0.04 0.08
304 207 138 0.02 0.04 0-07
210-229
82 60 45 35 28 23 0.02 0.03 0.04 0.06 0.10 0.13
940-979
332 226 151 108 0.02 0.03 0.07 0.12
230-249
71 54 42 34 28 22 0.02 0.04 0.06 0.08 0.11 0.17
980-1019
360 245 163 118 0.02 0.03 0.06 0.11
250-269
84 63 49 40 32 25 0.02 0.03 0.05 0.07 0.10 0.16
1020-1059
390 265 177 127 0.02 0.03 0.06 0.11
270-299
100 76 60 48 38 30 0.02 0.03 0.04 0.06 0.09 0.13
1060-1099
285 190 137 0.03 0.06 0.10
300-339
96 73 60 48 37 0.02 0.04 0.05 0.07 0.11
1100-1139
307 204 147 0.03 0.05 0.09
340-379
122 95 78 61 47 33 0.02 0.03 0.04 0.06 0.09 0.18
1140-1179
330 220 158 0.02 0.05 0.09
380-419
117 94 75 58 39 0.02 41.03 0.05 0.08 0.15
1180-1219
353 235 169 0-02 0.04 0.08
420-459
142 113 91 70 47 0.02 0.03 0.04 0.06 0.13
1220-1259
376 251 180 0.02 0.04 0.08
460-499
168 135 108 83 56 0.02 0.03 0.04 0.06 0.11
1260-1299
401 267 192 136 0.02 0.04 0.07 0.13
500-539
159 126 97 66 0.02 0.03 0.05 0.10
1300-1339
426 284 204' 144 0.02 0.04 0.07 0.13
540-579 580-619 62(0659 660-699
185 147 113 '77 0.02 0.03 0.04 0.08
1340-1379
212 0.02
169 0.03
192' 0.02
130 0.04
147 0.03
88 0.08
100 0.07
51 0.18
1380-1419
59 0.15
1420-1459
217 166 0.02 0.03
113 0.06
75 0.13
1460-1500
452 301 217 154 109 0.02 0.04 0.06 0.12 0.22
479 319 230 163 116 0.02 0.04 0.06 0.12 0.21
508 338 244 172 122 0.02 0.03 0.06 0.11 0.20
536 356 256 182 129 0.02 0.03 0.06 0.10 0.19
* Total pressure (itetis plus velority) loee is baaed oa FLAT FACE ADJUSTABLE BAB TYPE and doee NOTiociude stockhead.
, Talara ob the right erf line A and A' should not be need in applications such aa eburebra. auditoriums, sad oooccrt holla. Valots oa right erf line B end B' should not be aged in applications such as residential work, motion picture tbeaten, court rooms, and schnola. Fr floor and baseboard registers where a velocity of approximately 100 FPM is used. the free --- - CFM X U4-------------;--*->- ^?M
of OAL