Document ModVLz9kbVVkzv9X3j93Rgz4k
ll it well known that the working life of a.c. paper The concentration of the additive will be slightly
capacitor* impregnated with askarel* can be extended reduced by a batch treatment process with Fullers'
by the addition to the askarel of small amounts or earth or other adsorbent. In order to allow for this
suitable epoxy compounds, known as `scavengers'. reduction, the initial concentration of the additive
This effect is especially beneficial in the case of has been set at a slightly higher level than would
capacitors operating under arduous service condi otherwise be necessary. In this way, after a batch
tions, such as those subjected to frequent surges.
treatment with an adsorbent of normal activity at a
concentration up to about 1% by weight, the find
However, some epoxy compounds have been found concentration of the additive will be sufficient to give
to be very difficult to control under the practical protection to the capacitors.
conditions obtained in existing capacitor impregna
tion plants.
If the Impregnant is purified by percolation through
Arador 1242 Ei consists of electrical quality Arocior 1242 to which a specially purified epoxy compound hat been added at just above the concentration at which it will be used. This product has been developed to provide convenient processing in the capacitor impregnation plant as well as sufficient activity to give an effective scavenging action in the
a refining column the additive will be initially heavily depleted by the adsorbent. However, the adsorbed! later becomes `saturated' with the additive whilst continuing to remove ionic impurities from the impregnant. The volume of impregnant required to saturate the adsorbent depends upon its mass and activity.
finished capacitor.
The properties of Arocior 1242 El (see Table I) are
The vapour pressure of the additive itself is very much lower than that of Arocior 1242 so that the concentration of the additive will not be reduced during the degassing stage of the process when this is
the same as those of Arocior 1242 except for the following:
Scavenger Content: equivalent to 1.9 to 2.1 mg HCI/p
Dissipation Factor (tan 6) at 100'C, 50 Hz:
<3%
carried out over the usual ranges of temperature and Resistivity at 100'C, 500V, 1 min.:
>1 Teem.
pressure.
Monsanto
MGNS 074167
T
Table 1
Aroelor 1242 El. Tentative Data '
PIIOPEIITY
TEST METHOD
UNITS
Appearance
ASTM D 1702
-
Colour
ASTM D 1702
Density at 20 *C
ASTM D 1810 tilSO/R 649
Refractive Index at 20 *C
ASTM D 1807
Kinematic Viscosity at 20 *C ASTM D 446
FlaahPoint
ASTM D 92
Fire Point
ASTM D 92
Pour Point
ASTM D 97
APHA
g/cm*
--
cSt
c c c
VALUE
dear liquid free from suspended manor and sediment. 60 max. 1.38 to 1,39 1.6260 to 1.6270 66 to 71 163 min. none to boiling point. -18 max.
Neutralisation No. Inorganic Chlorides Water Content Hydrotyiebie Chlorides Scavenger Content
Monsanto ASTM D 1821 ISO/R 780 ASTM D 2441 Monsanto (Appendix 1)
mg KOH/g Ppm ppm ppm mg HCL/g
0.01 max. 0.05 max. 30 max. 1.0 max. 1.9 to 2.1
Volume Resistivity at 100*C,
BOOV, 1 min.
Monsanto
Dissipation Factor (tan 8) at
100*C, BO Hz
Monsanto
Relative Permittivity at 100'C, 60 Ha
Monsanto
Teem % -
> 1 min. < 3 max. 4.7 to 4.9
A suitable method Tor estimating the scavenger content is given in Appendix I. It has sometimes been found difficult lo chan the dielectric test cells that are used to measure thedissipation factor and resistivity of epoxide-containing skarels. We have found that it is helpful first to standardise the cell with pure Aroelor 1242 whose dis sipation factor is already known. If this measurement is satisfactory, the ceil is then rinsed twice with Aroelor
1242 El and the measurement proceeds in the usual way.
This product should be treated from the toxicity and safety aspects in the same way as Arotlor 1242 (se Appendix 2). For further information contact Monsanto at 10-18 Victoria Street, London SWIH ONQ, Telephony 222 5678 or at Place Madou 1,1030 Brussels, Telephony 19.11.01.
2
HONS 074168
Appendix 1
Tm Method for determining the ' quentlty of hydrogen chloride eoevenglng edditlve in Aroelor
1. Prlnolple
0. Additional Notes
(a) The titrant is very stable and does not require frequent restandardization.
(b) No blank correction should be required if good quality reagents an used.
Ttr method involvei titrating the oxirane oxygen in glacial acetic acid with a standard perchloric acid solu tion to a cryttal violet end-point. The titration h carried oet In an excels of quaternary ammonium bromide, which, on contact with perchloric acid, produces hydro gen bromide. The hydrogen bromide, in turn, reacte with the oxirane oxygen.
t. Reagents
(a) Olacial acetic acid (b) Chloroform (e) Perchloric acid eolution--0.1 N in glacial acetic acid
(tandaidin againet polaetium hydrogen phthalate). (d) Crystal violet-1 *, solution in glecial acetic acid. (e) Tetraethyl ammonium bromide solution--dissolve
100 g in 400 cm* of glecial acetic acid.
i. Apparatus
Appendix 2
Toxicity and Safa Handling
1. Avoid skin contact. Protect the hands, preferably by oil-resistant gloves.
2. If skin contict should occur, wash off with sosp and water.
3. if hot Arodor mutt be handled in e doted or confined area provide exhaust ventilation or wear an approved respirator.
4. if Arodor gets in the eyes, flush with large amounts of water. In the event that irritation persists refer the patient to * Phytidan.
5. Exposure to vapours or mists should be avoided.
(a) 10 cm* burette (b) Ulual laboratory glassware
If these precautions sre neglected ecne may develop and excessive exposure may cause liver damage.
4. Procedure
(a) Weigh 2,5 to 3.0 of the askant to the nearest 0.05 g Into a 125 cm* Erlcnmeyer flask.
(b) Add 10 cm* of chloroform, 40 cm* of glacial acetic acid and 10 cm* of tha tetraethyl ammonium bromide solution and swirl to dissolve.
(c) Add I drop of crystal violet indicator and titrate with 0.1 N perchloric Kid to the gmateit colour range (violet to green-blue).
0. Calculation Hydrogen chloride equivalence (mg/g)-^^--^-
where T--litre of penhloric add (cm*) N--normality of penhloric acid W--weight of sample (g)
Caution
Arodor is composed of polychlorinated biphenyls, which tome studies have shown may be an environmental contaminant. Extreme care should be taken to prevent any entry into the environment through spills, lesksge. use, disposal, vaporization or otherwise.
Th* Information In till* bufetin la to our boat knowtodpo tfuo onti occoratt M all tattvetiont. tooommandatitHia or aowwrtowa at* mafa wHbovt puatar^*.
Wieo tit* oondhtona o< vaa am boyond tha* eonvof, MonjMnto Company anti Ho aubatdfarlaa tifKMm any HabHity lor Ion or damage tuflpred Horn oao al tit^oo
tiaia or eufpottione. Fuitiiarmora no ttabttity la accaprati II waa pf any protioct In aaaartianca swith tiioaa data oe awppaaMona Inlrinpat any potent.
fuMStbod by MoftMnto (vrope SA Arodor la a floplatarati Trada Mark
(1/22)
3
PONS