Document MbOabqzbweYLKZNYz76jmL5a
PLAINTIFF'S EXHIBIT
Inter Office
Personnel end OrpenUetlon staff
March 23, 19B3
Mr. R. C. Scott Safety Engineer Van Dyke Plant
cc R. D. Byron J. J. Vhelan
Subject! Bulk ABbeatoa Material Re-Teat - Insulation Material frost Van Dyke Plant Powerhouse
As a result of discrepancies between asbestos testing results fron our Industrial Hygiene Laboratory and the Michigan Department of Public Health (MDPH), the two bulk samples of insulation material received on 26 February 19B3 were forwarded to an outside laboratory for further analysis. Samples were sent to EnvironmentalResearch Group, Inc. of Ann Arbor and analysed by polarised light microscopy (PLM). PLM is the same technique used by MDPH.
The attached analytical report indicates the subject samples did indeed contain asbestos. Specifically, 14 peroent ohrysotile and 22 to 23 percent amosite forms of asbestos were found which is relatively consistent with MDPH results. Conse quently, the insulation material must be regarded as containing asbestos and all aspects of OSHA Asbestos Regulation 29CFR 1910.1001 oust be complied with.
Ve are investigating possible causes of our initial false negative report. We believe it to be related to a possible masking effect in the color changes when both amosite and chryeotile forms of asbestos are present in the sample. StepB have been taken to assure that this does not ooour with future samples. Our initial report of 10 March 19B3 should be disregarded.
If you have further questions, please call on 33-76935*
dw Attachment
D. S. Carruthers, Industrial Hygienist Industrial Hygiene & Toxicology Department Employee Health Services
8006 0078 SCF-FORD-3294
PRODUCED BY FORD
ANALYTICAL REPORT
ENVIRONMENTAL RESEARCH GROUP, INC.
IIV N FIRST ANN ARSON. KJCHICAf. 48104
(313) 662-3104
PROJECT REPORT DATE
9457 03-16-83
L.L J ENT f u REPORT 52
UP* 4bl 11
BAIlPl.ES REC'.'D: 03-14-83
REFER TECHNICAL QUESTIONS TO: KATHRYN Hv BERRY, CIH
CLIENT:
FORD MOTOR COMPANY
CENTRAL LAB INDUSTRIAL HYGIENE 15000 CENTURY DR. DEARCORN. MI 48121 ATTENTION: DAVE CARRUTHERS
APPROVED. KuJ
f
RESIDUAL SAMPLES WILL
BE HELD FO*#R* TWO WEEKS
CLIENT I D. ERG SAMPLE NO. MATRIX
DSC 163/ 03/096269 BULK SAMPLE
PARAMETER
RESULTS
ASBESTOS. BULK ANALYSIS iHi n> CHRYSOTILE AMOSIT CROC)OOLITE
OTHER ASBESTOS FIBER CLASS. MINERAL WO.i.. OTHER COMPONENT
HOMOGENIZED PRIOR TO ANALYSIS FRIABILITY
COMMENTS APPEARANCE FIBRCJS WHITE COLOR
14 25 ND (1)
ND (1) ND (1) MORTAR
YES MODERATE HOMOGENEOUS MATERIAL
UNITS
X X 7.
7.
X
CLIENT 1.0 ERG SAMPLE NO MATRIX
DSC lt-.J 03/096240 BULK SAMPLE
PARAMETER
RESULTS
UNITS
ASBESTOS. BULK ANALYSIS (Pi M> CHRYSOTILE AMOSITS CROC IDOL1TE
OTHER ASCESIOs FIBER GLASS. MINERAL WOui OTHER COMPONENT
HOMOGENIZED Phi OR TOAUAi.VSIS FRIABILITY
14 22 ND (1)
ND (1> ND (1) MORTAR
YES ^ MODERATE
PAGE 1
SEE LAS. PAGE FOR EXPLANATION OF SYMBOLS
/.
xx xx
CONTINUED
PQ8006 0079
PRODUCED BY FORD
ANALYTICAL REPORT
ENVIRONMENTAL RESEARCH GROUP, INC.
ERG PROJECT NO. 9457 - FORD MOTOR COMPANY
03-16-83
COMMENTS' APPEARANCE - HOMOGENEOUS MATERIAL FIBROUS WHITE COLOR
t'
8006 0080
FW - Ml f Jfc.l.0 hti UKT FOH RtSUl.T NA - HOT AH Pi K Alii E TO Tt .T REGUESTED ND - IJOUbfr U-.CTED, OtTECT 1 >)N LIMIT IN <J SO * UAMPlE D/.f'iA.',L 0 SR - SEC AT VACHi 0 REPORT iCR RESULT < - POSITIVE RL'Sui T BUT AT UNGUANTIFIABlE
CDNCEWIRATICN BELOU INDICATED LEVEL TmAU.\ \GU F.IR YOUR BUSINESS !
PACE J IAJT PACE
A m
"o0
PRODUCED BY FORD